E. Maintenance and service

Examination before trial run

1. Check the water tank is filled with water, and open the water outlet tap till water flow out.
2. Check the water pressure is normal (0.15Mpa~0.7Mpa).
3. Check the air inlet or outlet is well connected; and the air outlet pipe heat insulation is completed.
4. Check the power supply voltage is normal, whether according with the nameplate requirement.

(Range ± 10%).

5. Check whether the equipped parts are screwed /locked well.
6. Check whether the wirings are according with the Circuit diagram, and the earth-wire is

connected.

7. Check whether the wind inlet and outlet has been cleaned up and no obstacle.
8. Check whether the condensate drain pipe is connected well and no blockage.
9. After power-ON, check the control panel display is normal.

Trial running

1. After the machine starts, to hear and determine whether there is abnormal sound or collision

during operation, if there is abnormal sound, stop the unit immediately and check for it until there
is no abnormal sound to continue operation.

2. For the first time power on, the compressor will have 3 minutes delay protection function.
3. Observe whether the drainage of condensate water is smooth, prevent the chassis stagnant or

spill water.

4. For the first time discharge hot water or start the units after a long time closure, the water tap of

outlet pipe may flow muddy water, this is a normal phenomenon, and continue to drain for a period
of time can be cleared.

5. After stop operation for a long time, there may have condensation water hereabout the air outlet or

pipe (especial in humidity weather), this is a normal phenomenon, use a dry washcloth to clean it
or by air dry.

6. The advance setting parameters of the operation panel has been set at the factory, users no need

to reset it, the maintenance person should be carefully set if needed.

Maintenance and service

1. After carry and move the unit by the first time installation, and connects the water pipes and filled

the tank with water. The machine should be rest for 1-2 hours before start trial running.

2. The water heater inlet filter needs to be cleaned once per 3 months. At the same time, per half

year we suggest draining all the storage water and repeatedly wash for 2-3 times to remove the
dirt and sediment.

3. To keep the unit in good heating performance, suggest cleaning the Air inlet /outlet filter net per

month, or using high pressure air tube to clean the Heat exchanger. Be careful not to damage the
copper tube.

4. Clean the Electric Heater per 6 months. (When clean the Electric Heater or Heat Exchanger must

cut off power supply.)

5. Change the Anode (Magnesium rod) per 6 months for better anticorrosion and antiscale.

According to different water quality, change the Anode rod when it’s expended.

6. When clean the Tank, Electric Heater, Heat Exchanger or Anode rod must cut off power supply.
7. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a

similarly qualified person.

8. Special statement: for what does not in accordance with the requirements of above maintenance

and service work lead to the failure problem, does not apply to our warranty scope.

Summary of Contents for RS-3.6FAD/260LX9

Page 1: ...ALL IN ONE Heat Pump Water Heater INSTALLATION AND OPERATION INSTRUCTIONS Please read this user s manual carefully before operate the unit...

Page 2: ...t the unit is STOP operation when disconnecting the power supply to the unit Disconnect all electric power supplies before servicing 3 This appliance is not intended for use by persons including child...

Page 3: ...heat pump it may cause the dangerous to people or damage the system 9 To make the system more efficiency please install the main unit at a place with good ventilation 10 Do not put or install the ope...

Page 4: ...2 B Description of heat pump Unit constructions outside...

Page 5: ...Electric Heater hole is only for the unit with Auxiliary heater models other models without auxiliary heater function are not available 3 There are two Circulation Water Hole for optional connection...

Page 6: ...ction 3 If install as Fig 2 the unit can be installed by the middle of the wall and connect the air inlet and outlet pipe for air exchange The distance of the unit and wall or other obstacle should no...

Page 7: ...pe The safety valve should be connected by a small rubber pipe interlinked with atmosphere this pipe must not be blocked in order to drain the water when the tank s pressure exceeds 0 7MPa 14 Water in...

Page 8: ...de by themselves 3 Before installation it s better to reserve a water supply pipe interface hot water outlet pipe interface and drainage pipe interface Among them the water supply pipe and hot water o...

Page 9: ...7 D Operation panel instruction 1 Panel Operation...

Page 10: ...8 D Operation panel instruction 2 Panel Display Cloud icon flashing during the connect with the internet always lighting after connected with the internet no lighting means no cloud control function...

Page 11: ...temp amendment 5 5 0 C Compressor F21 Compressor start delay 0 10 3 minute F28 Econ mode turn on or off electric heater 0 1 1 F29 Heat pumps working or not in heater mode 0 1 1 Defrost F31 Defrost sta...

Page 12: ...ctronic expansion valve EEV F70 EEV opening query 0 480 F71 EEV control mode 0 2 0 F72 Manually set EEV opening 100 480 350 F73 Set EEV superheat degree 15 15 5 F74 Set EEV discharge temp 85 110 92 F7...

Page 13: ...r temp is too high 2 Change the Electric heater A7 Exhaust temperature too high 1 Lack of refrigerant 2 Mix with air in system 3 Lack of lubricating oil 1 Supply refrigerant 2 Re vacuumizing and fill...

Page 14: ...ration for a long time there may have condensation water hereabout the air outlet or pipe especial in humidity weather this is a normal phenomenon use a dry washcloth to clean it or by air dry 6 The a...

Page 15: ...ation panel back panel and top cover of the unit follow the below steps Fig 5 6 to process Fig 5 Fig 6 Top cover disassemble Remove all the item 2 screws of the top cover 1 push up the top cover verti...

Page 16: ...ig 7 Fig 8 2 Loose the power wire from the terminal block to avoid the wire get stuck when move up the top shell 3 Remove all the screws item 2 from the Back panel item 5 two sides decoration bar item...

Page 17: ...ump without auxiliary electric heater 2 1 Comp Fan Valve Elect R S C BLACK 12V RED 220V 5 COMPRESSOR LOW HI BXS N LOW PRESURE PROTECTOR HI PRESURE PROTECTOR RETURN GAS TEMP SENSOR EXHAUST TEMP SENSOR...

Page 18: ...OWER SUPPLY YELLOW GREEN Transformer WATER TEMP SENSOR OPERATION PANEL ELECTRIC HEATER YELLOW GREEN 4 WAY VALVE FAN MOTOR YELLOW GREEN ELECTRIC HEATER PROTECTOR PRESURE PROTECTOR Electronic expansion...

Page 19: ...17 G Annex list ITEM NAME SPECIFICATION QUANTITY REMARK 1 Safety valve 1 2 Manual 1...

Page 20: ......

Reviews: