11

4. Error Handling:

ERROR

CODE

ERROR STATUS

REASONS

ERROR HANDLING

A1

Thermal sensor

alarm

Water temp. sensor open

circuit or short circuit.

1. Check the water temp. sensor

connection.

2. Change the water temp. sensor.

A2

Condenser coil

sensor alarm

Condenser coil temp.sensor

open circuit or short circuit.

1. Check the condenser coil temp.

sensor connection.

2. Change the coil sensor.

A3

Exhaust sensor

alarm

Exhaust temp. sensor open

circuit or short circuit.

1. Check the exhaust temp. sensor

connection.

2. Change the exhaust temp. sensor.

A4

Ambient temp.

sensor alarm

Ambient temp. sensor open

circuit or short circuit.

1. Check the Ambient temp. sensor

connection.

2. Change the ambient temp. sensor.

A5

Low /High pressure

alarm

1.1. High pressure protection

switch off.

1.2. Ambient temp. too high or

water heat exchanger dirty
block.

2.1. Low pressure protection

switch off.

2.2. Leakage of refrigerant.

1.1Check

or

change

the

high

pressure protector.

1.2. Check if the surround temp. is

too high, or clean the heat
exchanger of water tank.

2.1. Check or change the low

pressure protector.

2.2. Supply refrigerant and check if

there is any leakage.

A6

(Auxiliary) electric

heater protection

overheat alarm

1. Electric heater protection

switch off.

2. Tank water temp. too high.

1. Check if the water temp. is as LCD

display, or if water temp. is too
high.

2. Change the Electric heater.

A7

Exhaust temperature

too high

1. Lack of refrigerant.

2. Mix with air in system.

3. Lack of lubricating oil.

1. Supply refrigerant.
2.

Re-vacuumizing,

and

fill

in

refrigerant.

3. Change the lubricating oil of

compressor.

A8

Condensate drain

hole blocked

1.condensate pipe blocked

2.Machine drain hole blocked

1.Check condensate pipe is blocked

or not.

2.Check machine drain hole is

blocked or not.

A9

Return gas temp.

sensor alarm

Return gas temp. sensor open

circuit or short circuit.

1.Check the Return gas temp.

sensor connection.

2. Change the ambient temp. sensor.

- -

Screen no display or

display insufficiency

1. No plug in power.

2. Mainboard and operation

panel communication break

off.

1. Check the power line and voltage.
2. Reconnect the line of

mainboard and operation panel.

3.

Change

the

mainboard

or

operation panel.

NOTE:

1. When the unit has error, the buzzer of the operation panel will make an alarm sound, and there will

show “Alarm” on the screen panel.

2. “ERROR CODE” will show on temperature display location by alternately.
3. Part of the error alarm can be automatically restored (resumed). That is the appeared alarm can be

eliminated by electronically controlled self-test.

4. Some of the error alarm is caused by large fluctuation of the external power, by this, just power off and

restart the unit to clear the error.

5. When the machine has error alarm and restart still can not eliminated error, please contact the after

service as soon as possible for solution.

Summary of Contents for RS-3.6FAD/260LX9

Page 1: ...ALL IN ONE Heat Pump Water Heater INSTALLATION AND OPERATION INSTRUCTIONS Please read this user s manual carefully before operate the unit...

Page 2: ...t the unit is STOP operation when disconnecting the power supply to the unit Disconnect all electric power supplies before servicing 3 This appliance is not intended for use by persons including child...

Page 3: ...heat pump it may cause the dangerous to people or damage the system 9 To make the system more efficiency please install the main unit at a place with good ventilation 10 Do not put or install the ope...

Page 4: ...2 B Description of heat pump Unit constructions outside...

Page 5: ...Electric Heater hole is only for the unit with Auxiliary heater models other models without auxiliary heater function are not available 3 There are two Circulation Water Hole for optional connection...

Page 6: ...ction 3 If install as Fig 2 the unit can be installed by the middle of the wall and connect the air inlet and outlet pipe for air exchange The distance of the unit and wall or other obstacle should no...

Page 7: ...pe The safety valve should be connected by a small rubber pipe interlinked with atmosphere this pipe must not be blocked in order to drain the water when the tank s pressure exceeds 0 7MPa 14 Water in...

Page 8: ...de by themselves 3 Before installation it s better to reserve a water supply pipe interface hot water outlet pipe interface and drainage pipe interface Among them the water supply pipe and hot water o...

Page 9: ...7 D Operation panel instruction 1 Panel Operation...

Page 10: ...8 D Operation panel instruction 2 Panel Display Cloud icon flashing during the connect with the internet always lighting after connected with the internet no lighting means no cloud control function...

Page 11: ...temp amendment 5 5 0 C Compressor F21 Compressor start delay 0 10 3 minute F28 Econ mode turn on or off electric heater 0 1 1 F29 Heat pumps working or not in heater mode 0 1 1 Defrost F31 Defrost sta...

Page 12: ...ctronic expansion valve EEV F70 EEV opening query 0 480 F71 EEV control mode 0 2 0 F72 Manually set EEV opening 100 480 350 F73 Set EEV superheat degree 15 15 5 F74 Set EEV discharge temp 85 110 92 F7...

Page 13: ...r temp is too high 2 Change the Electric heater A7 Exhaust temperature too high 1 Lack of refrigerant 2 Mix with air in system 3 Lack of lubricating oil 1 Supply refrigerant 2 Re vacuumizing and fill...

Page 14: ...ration for a long time there may have condensation water hereabout the air outlet or pipe especial in humidity weather this is a normal phenomenon use a dry washcloth to clean it or by air dry 6 The a...

Page 15: ...ation panel back panel and top cover of the unit follow the below steps Fig 5 6 to process Fig 5 Fig 6 Top cover disassemble Remove all the item 2 screws of the top cover 1 push up the top cover verti...

Page 16: ...ig 7 Fig 8 2 Loose the power wire from the terminal block to avoid the wire get stuck when move up the top shell 3 Remove all the screws item 2 from the Back panel item 5 two sides decoration bar item...

Page 17: ...ump without auxiliary electric heater 2 1 Comp Fan Valve Elect R S C BLACK 12V RED 220V 5 COMPRESSOR LOW HI BXS N LOW PRESURE PROTECTOR HI PRESURE PROTECTOR RETURN GAS TEMP SENSOR EXHAUST TEMP SENSOR...

Page 18: ...OWER SUPPLY YELLOW GREEN Transformer WATER TEMP SENSOR OPERATION PANEL ELECTRIC HEATER YELLOW GREEN 4 WAY VALVE FAN MOTOR YELLOW GREEN ELECTRIC HEATER PROTECTOR PRESURE PROTECTOR Electronic expansion...

Page 19: ...17 G Annex list ITEM NAME SPECIFICATION QUANTITY REMARK 1 Safety valve 1 2 Manual 1...

Page 20: ......

Reviews: