APPENDIX D – CHIMNEY INSTALLATION CRITERIA
CHIMNEY INSTALLATION
1.
A clean out tee is required on both installations
(see items 1 and 6 in illustration).
2.
Four-inch pellet vent pipe is required on both
chimney and fireplace installs (see item 2 in
illustration).
3.
Top of chimney must be sealed and flashing
used (see item 4 in illustration).
4.
Install storm collar above flashing to prevent
leakage (see item 4 in illustration).
5.
Vertical termination cap (type L pellet) must be
used on all installations. If wind conditions are
present, then utilize a high-wind cap (see item 5
in illustration).
PELLET QUALITY
Vertical installation into old chimneys are
susceptible to creosote build up if not done
properly. Poor quality pellets or pellets with a high
moisture content
can
also create creosote and the
risk of a chimney fire. We suggest trying several
bags of different pellets to determine which ones
will give you a vibrant, hot flame. Avoid pellets that
burn rich (smoky, orange flame), and make sure to
keep fire pot clean and free of ash build-up.