7
Parameter
Description
Can be
checked
by Sendo-
Pro/the-
Senda B
(app)
Can be
changed
by Sen-
doPro/
theSenda
B (app)
Can be
changed
by the-
Senda P
Brightness set-
point value C1
Value range in lux/
measurement off
x
x
x
Brightness
actual value C1
Check brightness
actual value
x
Room correction
factor C1
Room correction
factor
x
x
Brightness
measurement
value C1
Lux meter bright-
ness value in lux
x
Detection sensi-
tivity (PIR)
Value range in
increments
x
x
x
Lighting time
delay
Value range in
seconds/minutes
x
x
Short-term
presence
Short-term pre-
sence: ON/OFF
x
x
Energy saving
mode
Selection: eco/eco
plus
x
x
Presence switch-
on delay
Value range in
seconds/minutes
x
Presence time
delay
Value range in
seconds/minutes
x
x
Switch on dim-
ming value C1
Value range in %
x
Configuration
type C1
Selection: Auto/Man
x
x
x
Control speed
Selection: standard/
average/fast
x
Minimum dim-
ming value
Value range in %
x
Maximum dim-
ming value
Value range in %
x
Switch off
brightness
Value range in
minutes/hours/
never off
x
Staircase light
function
Selection: ON/OFF
x
x
Dimming speed:
man. dimming
Selection: standard/
fast
x
Response after
man. dimming
Selection: school/
office
x
Standby time
Value range in
seconds/minutes
Permanently on
x
Standby dim-
ming value
Value range in %
x
IR group address
C1
Selection: all/I/II/III
(app to VIII)
x
Scene 1 C1
Value range in %
x
Scene 2 C1
Value range in %
x
Configuration
button/RC
Selection: Enabled/
Disabled
x
LED motion
display
OFF/ON
x
L
The selection of parameters is limited with the theSenda P.
Checking the set values:
With the SendoPro and the theSenda B/app, parameters can
be checked by gradually sending the values to the detector. If
the sent value is below the set parameter, the LED lights up
briefly. If the sent value is equal to or above the set parameter,
the LED lights flickers for 2 s.
Detection zone
The detection area is divided into two independent detec-
tion zones (see 4. Installation, detection area). For a maxi-
mum range, zone 1 and zone 2 are activated. If a limitation
of the detection area is required, zone 1 or zone 2 can be
deactivated.
Value range
Adjustable values from SendoPro/
theSenda/app
Z1, Z2, Z1 and Z2
Function C1
The lighting channel C1 can be operated in switching mode or
in the constant light control function. The function is set via
the <Function C1> parameter.
Value range (with SendoPro/theSenda B/app)
Switching
Lighting channel C1 is in the switching mode function
Control
Lighting channel C1 is in the constant light control function
Brightness setpoint value C1
The brightness setpoint value defines the minimum required
brightness. The current brightness is measured below the
presence detector. If the brightness is below the setpoint
value and presence is detected, the light is switched on (for
the fully automatic device configuration type).
Value range
Adjustable values from SendoPro/theSenda B/app
10–3000 lux
Adjustable values from theSenda P
10, 15, 300,
500, 800 lux
Deactivation of brightness measurement (brightness
measurement has no effect)
The lighting channels only switch according to presence
and absence.
SendoPro/theSenda B/app
Measurement
off
theSenda P
button
Brightness actual value C1
The brightness actual value can be checked for monitoring
purposes. To check, see the "Parameters via remote control"
table.
Room correction factor C1, brightness measurement
value C1
The room correction factor is a measure of the different
brightness measurements at the ceiling and on the work
surface (the brightness value depends on the ambient
conditions).