"Office" configuration type (in single and open-plan 
offices):

†

y

After manual dimming, the constant light control remains 

temporarily active with the current brightness value as the 

new brightness setpoint value.

†

y

The new brightness setpoint value only applies while some-

one is present.

†

y

After the lighting time delay, the set brightness setpoint 

value is restored.

Switching mode

 

The switching response is controlled by presence and 
brightness. 

 

The lighting channel switches on in darkness and when 
someone is present. The lighting switches off if there is 

sufficient brightness or during periods of absence after 

the set lighting time delay. 

 

The light is switched on with the switch-on dimming 
value. 

 

The button can be used to change the intensity of the 

artificial light when someone is present. If the lighting is 

switched on with the button, it remains switched on for 
at least 30 min. If people have left the room (before), the 
lighting switches off after the set time delay. 

Standby (orientation light)

 

After the lighting time delay, the lighting is set to the 
standby dimming value (1–25% of the lamp output). 

 

The standby time can be set between 0 s and 60 min or 
permanently. 

 

If the room brightness is above the brightness setpoint 
value, the lighting switches off. If the room brightness is 
below the brightness setpoint value, the lighting swit-
ches to the standby brightness. If someone reenters the 
room, the detector switches back automatically (fully 
automatic device) or after pressing the button (semi-
automatic device) to the set brightness setpoint value.

Lighting time delay

 

The minimum time delay (10 s – 60 min) is adjustable 
and can increase to max. 30 min or decrease back to the 
set minimum time. 

 

With settings ≤ 2 min or ≥ 30 min, the time delay 
remains unchanged at the set value. If someone briefly 

enters and leaves an unoccupied room within 30 s, 
the lighting switches off early after 2 min (short-term 
presence).

Button control

 

The lighting can be switched or dimmed manually via a 
button. 

 

A short button press switches the light on or off; a long 
button press dims the light (brighter or darker). 

 

If the lighting is switched off manually, it remains 
switched off as long as people are present. The lighting 
switches on again after the time delay has elapsed. 

Fully or semi-automatic device

 

Fully automatic device: the lighting is switched on and 
off automatically.

 

Semi-automatic device: the lighting must be switched on 
manually. It is switched off automatically.

Staircase light function

 

If the staircase light function is activated, the detector is 
used as a staircase automatic device. It is not possible to 
switch the lighting off manually. 

 

If the staircase light function is deactivated, the lighting 
can be switched on and off manually.

eco and eco plus

Settings for ideal switching response and maximum energy 

savings.

8.  Settings

The thePassa P360-221 DALI presence detector features two 

different operating modes:

 

Broadcast (factory setting)

 

Addressable

Both operating modes can be selected with the SendoPro or 

the theSenda B/app.

Parameter

Selection

Type

thePassa P360-111 DALI (broadcast)

thePassa P360-221 DALI (addressable)

 

The presence detectors are supplied with basic settings 
ready for operation. 

 

With SendoPro and the theSenda B/app, parameters can 
be checked, adjusted and optimised during start-up. 

 

With the theSenda P, parameters can only be adjusted. 

Broadcast <thePassa P360-111 DALI>

Teach-in via button

†

†

Press the button for > 15 s 

 

The currently measured brightness value is adopted as 
the brightness setpoint value.

 

L

The teach-in function via the button can be disabled using 
the SendoPro or the theSenda B/app remote controls 

when the "Configuration button/RC" parameter is set to 

"disabled".

Parameters via remote control

The following parameters can be checked or changed via 

the remote control for support during start-up as well as 

servicing:

Parameter

Description

Can be 

checked 

by Sendo-

Pro/the-

Senda B 

(app)

Can be 

changed 

by Sen-

doPro/

theSenda 

B (app)

Can be 

changed 

by the-

Senda P

Detection zone

Selection: Z1 / Z2 / 

Z1+Z2

x

x

Function C1

Selection: 

switching/control

x

x

Summary of Contents for thePassa P360-221 DALI UP WH

Page 1: ...ting disconnect the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installa...

Page 2: ...tangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detec tion zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Lighting channel Li...

Page 3: ...by connecting the P terminals Presence is detected collectively by all the detectors The master measures the brightness processes the button information and controls the lighting The other detectors slaves merely provide presence information e g thePassa P360 Slave UP Master DALI DA DA S1 S2 P N L Slave P N L N L EVG Only for the addressable operating mode Master master parallel switching Several ...

Page 4: ...t function button Select thePassa P360 221 DALI as the type in the SendoPro Select Menu right function button then Control com mands left function button Open DALI configuration with Open right function button For the DALI configuration there are 3 options available y y Group assignment unaddress only DALI EBs without a group address are processed y y Group assignment all all connected DALI EBs ar...

Page 5: ...SendoPro remote control or the theSenda B app for SendoPro theSenda B app select the Control commands menu L LChanging the lighting group for DALI EBs use the Sendo Pro or the theSenda B app to change the DALI configura tion via the Change group assignment command L LWith the button the whole DALI configuration must be re executed L LA video on configuring the lighting groups can be found at https...

Page 6: ...ghting can be switched or dimmed manually via a button A short button press switches the light on or off a long button press dims the light brighter or darker If the lighting is switched off manually it remains switched off as long as people are present The lighting switches on again after the time delay has elapsed Fully or semi automatic device Fully automatic device the lighting is switched on ...

Page 7: ...tor If the sent value is below the set parameter the LED lights up briefly If the sent value is equal to or above the set parameter the LED lights flickers for 2 s Detection zone The detection area is divided into two independent detec tion zones see 4 Installation detection area For a maxi mum range zone 1 and zone 2 are activated If a limitation of the detection area is required zone 1 or zone 2...

Page 8: ...t the Brightness measurement value C1 parameter Using the theSenda B remote control Set up the theSenda B according to the drawing and move a few steps away from the measurement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After thi...

Page 9: ...assa P360 221 DALI detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted range are automatically set t...

Page 10: ...ton RC Selection Enabled Disabled x Parameter Description Can be checked by Sendo Pro the Senda B app Can be changed by Sen doPro theSenda B app Can be changed by the Senda P LED motion display OFF ON x L LThe selection of parameters is limited with the theSenda P Checking the set values With the SendoPro and the theSenda B app parameters can be checked by gradually sending the values to the detec...

Page 11: ...d or ente red values outside the permitted range are automatically set to the appropriate limit value The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 C2 parameter for monitoring pur poses The default value is 0 3 theSenda B and the theSenda Plug app Connect the theSenda B with the corresponding theSenda Plug app Select th...

Page 12: ...da B app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End group assignment End configuration of the lighting groups x Change over to broadcast opera ti...

Page 13: ... can be selected and sent to the detector with the SendoPro and the theSenda B app With the theSenda P the sensitivity can be reduced by one increment by pressing the button or raised by pressing the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitive L LBy selecting the presence test mode the set sensitivity increment is not changed L...

Page 14: ... SendoPro theSenda B app Switch off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range with SendoPro theSenda B app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range wi...

Page 15: ...0 x 5 m IH 3 5 m 100 m2 moving radially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Co...

Page 16: ...nts and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...

Page 17: ...17 ...

Reviews: