background image

4

6.  Start-up

Initial operation of thePassa P360-111 DALI 

(broadcast) → factory setting

 

L

After the start-up phase (30 s), the detector is ready for 
operation.

Initial operation of thePassa P360-221 DALI 

(addressable), unconfigured system

†

†

The operating mode can be switched from broadcast to 

addressable with the SendoPro remote control or the the-

Senda B/app:

†

†

Select the <thePassa P360-111 DALI> parameter as the 

detector type.

†

†

Open the DALI configuration ("Control commands" menu in 

the SendoPro).

†

†

Send the <Change over to addressable operating mode> 

parameter to the detector.

†

†

After the changeover, select <thePassa P360-221> as the 

detector type for further parameterization. 

After the first changeover to the addressable operating mode 

(thePassa P360-221 DALI), the detector restarts, identifies all 

connected DALI lights, assigns short addresses and manages 

them in a list. 

 

Depending on the system size, the LED on the detector 

flashes (5 x ON briefly every 3 s) for up to 3 min.

If no DALI EBs are connected to the detector or a DALI line is 

interrupted

 

▻ the LED flashes (LED is switched on and flashes 2 x OFF 

briefly every 3 s). 

If the system is functioning, the detector switches to confi

-

guration mode and waits for the configuration of the lighting 

groups. 

 

▻ The LED flashes (2 x ON briefly every 3 s). 

As long as the configuration has not been carried out, the 

system is in the following operating state:

 

Detector is in broadcast mode.

 

Function is in switching mode (only presence detection, 
no light measurement).

 

All lights are controlled with 100% switch-on dimming 
value.

 

The operating mode is fully automatic device.

 

All connected buttons are active. Switching on and off as 
well as dimming are possible.

 

Time delay: 10 min.

Configuring the lighting groups with

 

SendoPro

 

theSenda B/app

 

Buttons or theSenda S

Configuring the lighting groups with SendoPro

Right function button

Right button

Up button

Down button

Left function button

†

†

Select "thePassa P360-221 DALI" as the type in the 

SendoPro.

†

†

Select "Menu" (right function button) then "Control com-

mands" (left function button).

†

†

Open "DALI configuration" with "Open" (right function 

button).

For the DALI configuration, there are 3 options available:

†

y

"Group assignment (unaddress.)": only DALI EBs without a 

group address are processed.

†

y

"Group assignment (all)": all connected DALI EBs are con-

figured. 

NOTE

: All existing group assignments with group 

number 1 or 2 are deleted.

†

y

"Change group assignment": the next existing EB is 

searched for and selected. 

†

†

Use the Up or Down button to select the required group 

assignment and press "Send" (right function button) to 

start the configuration. 

 

L

The remote control must be directed to the detector! The 
LED is switched off.

 

A DALI light starts to pulse (random order).

†

†

Select the required C1 or C2 channel with the button and 

assign it to the DALI EB by pressing "Send" (right function 

button). 

 

▻ As confirmation, the light dims to 20%. 

 

The next DALI light starts to pulse. One after the other, 
the lighting groups are assigned to all the lights. 

 

For group assignment (unaddress.) or (all): if all DALI EBs 
are assigned to a lighting group, the detector terminates 

the configuration process and restarts (startup phase of 

30 s). The detector then switches to the normal opera-

ting mode and the configuration is completed.

 

L

If necessary, the configuration process can be ended by 

pressing "End" (left function button). 

 

In this case, the system is not ready for operation.

 

If "Change group assignment" has been selected, use the 
right ">" button to switch to the next DALI EB without 
changing the lighting group.

†

†

When all required changes have been made, end the confi

-

guration process by pressing "End" (left function button).

Configuring the lighting groups with the theSenda B/app

†

†

Connect the theSenda B with the corresponding "theSenda 

Plug" app.

†

†

Place the theSenda B under the detector (direct the remote 

control towards the detector).

†

†

Select "thePassa P360-221 DALI" as the type in the "the-

Senda Plug" app.

†

†

In the "DALI configuration" menu, select the required group 

assignment.

Summary of Contents for thePassa P360-221 DALI UP WH

Page 1: ...ting disconnect the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installa...

Page 2: ...tangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detec tion zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Lighting channel Li...

Page 3: ...by connecting the P terminals Presence is detected collectively by all the detectors The master measures the brightness processes the button information and controls the lighting The other detectors slaves merely provide presence information e g thePassa P360 Slave UP Master DALI DA DA S1 S2 P N L Slave P N L N L EVG Only for the addressable operating mode Master master parallel switching Several ...

Page 4: ...t function button Select thePassa P360 221 DALI as the type in the SendoPro Select Menu right function button then Control com mands left function button Open DALI configuration with Open right function button For the DALI configuration there are 3 options available y y Group assignment unaddress only DALI EBs without a group address are processed y y Group assignment all all connected DALI EBs ar...

Page 5: ...SendoPro remote control or the theSenda B app for SendoPro theSenda B app select the Control commands menu L LChanging the lighting group for DALI EBs use the Sendo Pro or the theSenda B app to change the DALI configura tion via the Change group assignment command L LWith the button the whole DALI configuration must be re executed L LA video on configuring the lighting groups can be found at https...

Page 6: ...ghting can be switched or dimmed manually via a button A short button press switches the light on or off a long button press dims the light brighter or darker If the lighting is switched off manually it remains switched off as long as people are present The lighting switches on again after the time delay has elapsed Fully or semi automatic device Fully automatic device the lighting is switched on ...

Page 7: ...tor If the sent value is below the set parameter the LED lights up briefly If the sent value is equal to or above the set parameter the LED lights flickers for 2 s Detection zone The detection area is divided into two independent detec tion zones see 4 Installation detection area For a maxi mum range zone 1 and zone 2 are activated If a limitation of the detection area is required zone 1 or zone 2...

Page 8: ...t the Brightness measurement value C1 parameter Using the theSenda B remote control Set up the theSenda B according to the drawing and move a few steps away from the measurement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After thi...

Page 9: ...assa P360 221 DALI detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted range are automatically set t...

Page 10: ...ton RC Selection Enabled Disabled x Parameter Description Can be checked by Sendo Pro the Senda B app Can be changed by Sen doPro theSenda B app Can be changed by the Senda P LED motion display OFF ON x L LThe selection of parameters is limited with the theSenda P Checking the set values With the SendoPro and the theSenda B app parameters can be checked by gradually sending the values to the detec...

Page 11: ...d or ente red values outside the permitted range are automatically set to the appropriate limit value The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 C2 parameter for monitoring pur poses The default value is 0 3 theSenda B and the theSenda Plug app Connect the theSenda B with the corresponding theSenda Plug app Select th...

Page 12: ...da B app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End group assignment End configuration of the lighting groups x Change over to broadcast opera ti...

Page 13: ... can be selected and sent to the detector with the SendoPro and the theSenda B app With the theSenda P the sensitivity can be reduced by one increment by pressing the button or raised by pressing the button Value range Incre ment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 Sensitive 5 Very sensitive L LBy selecting the presence test mode the set sensitivity increment is not changed L...

Page 14: ... SendoPro theSenda B app Switch off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range with SendoPro theSenda B app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range wi...

Page 15: ...0 x 5 m IH 3 5 m 100 m2 moving radially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Co...

Page 16: ...nts and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Theben AG Hohenbergstr 32 72401 Haigerloch GERMANY Phone 49 7474 692 0 Fax 49 7474 692 150 Hotline Phone 49 7474 692 369 hotline theben de Addresses telephone numbers etc www theben de ...

Page 17: ...17 ...

Reviews: