The Ajax security system allows conducting tests for checking the functionality of connected 
devices. 

The tests do not start straight away but within a period of 36 seconds when using the standard 
settings. The test time start depends on the settings of the detector scanning period (the 
paragraph on “Jeweller” settings in hub settings). 

 

Signal Strength Test

 

 

Attenuation Test

 

 

FireProtect Self Test

 

Pursuant to the requirements of the standard EN50131, the level of the radio signal sent by 
wireless devices is decreased during the test mode. 

Detector Testing 

Prior to installing FireProtect, check the smoke detector. To test, switch on the device and press 
the touch-sensitive button in the logo center for 10 seconds - the detector will test the smoke 
chamber with the electronic simulation of smoke generation and then will switch on the siren for 
8 seconds. 

You will receive the corresponding notification in the application regarding the test result and 
detector status. 

Installing of the device 

Selection of the Detector Location 

The performance efficiency of the detector depends on its location. 

Location of FireProtect as a security system element determines its remoteness from the hub 
and presence of any obstacles between the devices, hindering the radio signal and sound 
transmission: walls, inserted floors, large-size objects located within the room. 

Check the signal level at the installation location

 

If the signal level is one division, we cannot guarantee stable operation of the security system. 
Take possible measures to improve the quality of the signal! As a minimum, move the device - 
even 20 cm shift can significantly improve the quality of reception. 

If, after moving, the device still has a low or unstable signal strength, use a radio signal range 
extender ReX. 

The detector should be installed at the ceiling in the highest point where hot air and smoke are 
concentrated.  

If there are any beams at the ceiling, protruding by 30 or more centimeters from the ceiling 
level, then the detector should be installed between every two beams. 

Detector installation process 

Before installing the detector, make sure that you have selected the optimal location and it is in 
compliance with the guidelines contained in this manual! 

Summary of Contents for FireProtect

Page 1: ...b The communication range is up to 1 300 meters if there are no obstacles In addition the detector can be used as part of third party security central units due to the Ajax uartBridge or Ajax ocBridge Plus integration module Buy fire detector with carbon monoxide sensor FireProtect Plus The detector is set up via a mobile application for iOS and Android based smartphones The user is notified of al...

Page 2: ...connected to a security system the detector will also send an alarm signal to the hub the user and private security company will receive the respective notifications The detector detects smoke using an optical coupler consisting of an infrared emitter and photoelectric receiver located in a smoke chamber If smoke penetrates into the chamber the photoelectric receiver detects it based on the distor...

Page 3: ...tector to the Ajax Security System Connecting to the hub Before starting connection Following the hub instruction recommendations install the Ajax application on your smartphone Create an account add the hub to the application and create at least one room Go to the Ajax application Switch on the hub and check the internet connection via Ethernet cable and or GSM network Ensure that the hub is disa...

Page 4: ...ATION SDN BHD www thcomm com my info thcomm com my 3 Select Add the countdown will begin 4 Switch on the device To make sure that the detector is on press the on off button the logo will light up red for a second ...

Page 5: ...cted to the hub will appear in the list of devices of the hub in the application Update of the detector statuses in the list depends on the device inquiry time set in the hub settings with the default value 36 seconds Connecting the Detector to Third Party Security Systems To connect the detector to a third party security central unit using the Ajax uartBridge or Ajax ocBridge Plus integration mod...

Page 6: ...erature Rapid temperature rise The alarm state for rapid temperature rising Temperature Temperature of the device Measured on the processor and changes gradually Signal Strength Signal strength between the hub and the detector Battery Charge Battery level of the device Backup Battery Charge Backup battery level of the device Lid The tamper mode of the device which reacts to the detachment ...

Page 7: ...us between the hub and the device Smoke detector State of the smoke detector Smoke detector dust level Dust level of smoke chamber Firmware Detector firmware version Device ID Device identifier Setting Up the Detector Devices FireProtect Setting Value First field Device name can be edited ...

Page 8: ...f rapid temperature rise detected Signal Strength Test Switches the device to the signal strength test mode FireProtect self test Starts FireProtect self test User Guide Opens the detector User Guide Unpair Device Disconnects the sensor from the hub and deletes its settings Indication Event Indication Detector switch on LED lights up green for 1 second Detector switch off The logo blinks red three...

Page 9: ... the device Selection of the Detector Location The performance efficiency of the detector depends on its location Location of FireProtect as a security system element determines its remoteness from the hub and presence of any obstacles between the devices hindering the radio signal and sound transmission walls inserted floors large size objects located within the room Check the signal level at the...

Page 10: ...of opening the SmartBracket panel removing the detector from the ceiling you will receive the notification Do not install the detector outside the premises outdoors in places with fast air circulation near a ceiling fan air conditioner air exhaust open doors and windows nearer than a meter from the vertical projection of the cooking surface nearby any metal objects or mirrors causing attenuation a...

Page 11: ...pensated up to some level and then cleaning will be required the detector will send the respective notification The detector also signals about the contaminated smoke chamber or a failure using a long sound signal once every minute and a half How to clean up the smoke chamber Batteries installed in the detector ensure up to 4 years of autonomous operation If the batteries are discharged the securi...

Page 12: ...dimensions 132 х 132 x 31 mm Weight 216 g Complete Set 1 FireProtect FireProtect Plus 2 Batteries CR2 pre installed 2 pcs 3 Battery CR2032 pre installed 1 pcs 4 Installation kit 5 Quick Start Guide Warranty Warranty for the AJAX SYSTEMS MANUFACTURING LIMITED LIABILITY COMPANY products is valid for 2 years after the purchase and does not apply to the pre installed battery If the device does not wor...

Reviews: