Downstream Slug Interrupt
Definition:
The Slug Release line is disconnected going to the downstream Logic Assembly.
Action:
Logic Assemblies downstream of the Function Module will not slug release when the Slug
Release Line is turned ON either at the Function Module itself or upstream of the Function
Module.
Configuration: JP1 is on 2-3 and JP2 is on 1-2.
Upstream Slug Interrupt
Definition:
The Slug Release line is disconnected going to the upstream Logic Assembly.
Action:
Logic Assemblies upstream of the Function Module will not slug release when the Slug
Release Line is turned ON either at the Function Module itself or downstream of the
Function Module.
Configuration: JP1 is on 1-2 and JP2 is on 2-3.
Zone Status Indication
Definition:
Indicates full or empty status of the downstream zone at two output locations.
Action:
Takes an input from one of several user selectable inputs, process it through Zone Status
ON Delay and Zone Status OFF Delay and outputs to the ZS Relay on TB3 and Zone
Status Output on TB5.
Configuration: Choose the input that determines the zone’s empty or full status.
Downstream logic signal (identical to Downstream Sensor signal of a Single
Accumulation Logic Assembly) as the input:
JP4 is on 1-2 or 2-3 and JP5 is on 1-2 or NC.
Auxiliary sensor or external signal (from a PLC for example) as the input:
JP4 is NC and signal is input to TB4
The output transition of the Zone Status from OFF to ON or ON to OFF will only occur if the time delay
set by the Zone Status ON and Zone Status OFF Delay potentiometers have expired. A non-zero delay
setting will effectively filter out transitions that only occur for the set time. This is typically used to indicate
a zone is full only after a product is detected for period of time indicative of a full and accumulated lane.