background image

 

Pagina 29 di 35

 

 

AD1100TE-STD.EN-00 - Subject to change without notice 

 

TFT DryAir 

Menu 

Parameter 

Description 

Unit of 

measurement 

Default 

Value 

Set 

Value 

rC08 

Setting cycle time for PWM control

 

10/sec 

5,0 

 

rC09 

Setting time delay start regulation 3 points from the request (allows the 
adjustment of the adjustment with the times of operation of the burner)

 

Sec 

30 

 

rC10 

Setting set-delta temperature for over temperature mode adjustment 3 points for 
burner (set-point reactivation [RC01] + set-delta [RC10]> Reactivation temperature, 
the output of the burner control goes OFF)

 

°C 

10,0 

 

rC11 

Setting time delay insertion electric heaters of reactivation to request activation in 
control mode mixed steam/water + electricity (With CF02> 7). If the value is 0, the 
function is disabled: 

Min 

 

CF-- 

CF01 

Parameters selection on the display: 
0 = Status 
1 = Temperature di reactivation 
2 = Probe input % relative or absolute humidity or DewPoint  
3 = DewPoint value calculated (with RH% probe + post-treatment temp.) 
4 = Absoluted humidity value calculated  (with probe RH% + post-treatment temp.) 
5 = Temperature of pre-treatment (if any probe) 
6 = Temperature of post-treatment (if any probe) 

Num. 

 

CF02 

Reactivation type: 
0 = No 
1 = Electric first step (step 1) 
2 = Electrical second step (2 steps) 
3 = Electrical third step (3 steps) 
4 = Electrical PWM control 
5 = Steam (PWM control with converter) 
6 = Throttle adjustment with 3 points 
7 = Gas adjustable on / off (on / off burner, reg. High heat, low heat) 
8 = Steam / Water propor Electric first step (step 1) 
9 = Steam / Water propor Electric second step (2 steps) 
10 = Steam / Water propor Electric third step (3 steps) 
11 = Steam/Water propor Electric command PWM 

Num. 

 

CF03 

Type adjusting pre-treatment: 
0 = No 

1 = Cooling 
2 = Heating 

Num. 

 

CF04 

Type adjusting post-treatment: 
0 = No 

1 = Cooling 
2 = Heating 

Num. 

 

CF05 

(*) Type control probe post-treatment: 
0 = No 
1 = NTC 
Probe 2 = 4...20mA

 

Num. 

 

CF06 

(*) 

Setting the minimum value for probe post-treatment in version 4 ... 20mA

 

°C 

-30,0 

 

CF07 

(*) 

Setting maximum value to probe post-treatment in version 4 ... 20mA

 

°C 

70,0 

 

CF08 

(*)

Type control probe Humidity/DewPoint 4 ... 20mA: 

0 = No 
1 = Relative humidity probe % 
2 = probe DewPoint 
3 = Probe Absolute humidity g/Kg

 

Num. 

 

CF09 

(*) Setting the minimum value for probe Humidity / DewPoint

 

%-°C-g/Kg 

0,0 

 

CF10 

(*) Setting maximum value for humidity probe / DewPoint

 

%-°C-g/Kg 

100,0 

 

CF11 

Type of reactivation probe: 
0 = Probe NTC HT Eliwell 
1 = Probe NTC HT Carel 
2 = probe PT1000 (not available) 

Num. 

 

CF12 

Control rotor is stationary

OFF = Disable 
On = Enable 

OFF/On 

On 

 

CF13 

Selection mode dehumidification control: 
0 = from AIL4 analo input (Input 4…20mA) 
1 = from Dewpoint Value calculated (with probe RH% + T) 
2 = from absolute humidity value calculated (with probe RH% + T) 

Num. 

 

 
 
 

 
 
 

 
 
 

 
 
 

 

Summary of Contents for AD1100TE

Page 1: ...2017 TFT DryAir Dehumidifier AD1100TE Technical manual Unit 400Vac 3Ph 50Hz...

Page 2: ...nnel 11 General instructions 11 Specification for the expulsion channel of moist air 12 Specifications for the input channel of reactivation air 12 Specifications for the channels of process air and d...

Page 3: ...0 Spare Parts List 21 Component data 22 Electrical connections Preliminary Information Security 23 Electrical data 23 HOW TO CONNECT THE POWER SUPPLY 24 Electrical wiring 25 Description of adjustment...

Page 4: ...off input power before opening any panel of the dehumidifier Allow the unit to cool down before maintenance work at least 15 minutes after turning off After power failure or mains disconnection an au...

Page 5: ...onnel will invalidate the warranty as will the use of non approved spare parts In order for the warranty to be valid the customer must scrupulously documented any repair and maintenance Rivolgersi sem...

Page 6: ...tions that could generate a fulguration risk MOVING PARTS This symbol identifies hazards associated with moving parts HOT SURFACES This symbol identifies the presence of exposed hot surfaces that will...

Page 7: ...midifier works in a continuous process with two air streams process air and reactivation air As shown in the figure a honeycomb rotor dehumidifier consists of a honeycomb adsorbent rotor which is rota...

Page 8: ...adsorbents are impregnated desiccants With the advanced silica gel rotor are no granules and no dusting It stops adsorbing moisture hen moisture is in equilibrium with the moisture in the passing or s...

Page 9: ...ical panel The electrical panel is located inside the unit Switches and indicators of operation are located outside the dehumidifier Possibility of operation The mode selector on the outside of the de...

Page 10: ...ocal regulations Do not get close and do not insert any objects into moving parts WORKERS HEALTH AND SAFETY The operator s workplace must be kept clean tidy and free from objects that might hinder mov...

Page 11: ...he process air duct must be isolated in order to avoid the formation of condensation on the outside if the temperature inside the duct falls below the dew point of the ambient air If there is a risk o...

Page 12: ...duct Horizontal Vertical Expulsion Expulsion 1 Slop down 2 Vertical expulsion of moist air 3 Wire mesh 4 Condensate drainage Specifications for the input channel of reactivation air This channel must...

Page 13: ...aminants such as exhaust gas vapor or harmful emissions To prevent the ingress of moist air in the air intake of process or reactivation the intake of the outside air must be positioned at least 2 met...

Page 14: ...the dehumidifier to the electricity grid through the general switch and switch the main switch ON and check for the voltage at the terminal L N or L1 L2 L3 of the dehumidifier 8 Start the dehumidifier...

Page 15: ...s may differ from one installation to another Improper maintenance can result in decreased performance Filters The dehumidifier is equipped with two separate filters one for the process air and one fo...

Page 16: ...nstallation start up performed by TFT is required to validate the full warranty Inspection During installation or when you need to work on the unit you must strictly follow the rules reported on this...

Page 17: ...never use steam or other cleaning agents that could damage it Take away and leave to the site manager any keys providing access to the control panel Unpacking The packaging may be dangerous for operat...

Page 18: ...ateral panels and the cover In the case of handling by forklift truck put a spacer between the security structure of the unit and the forks of the lift to avoid damaging to the panels In the case of h...

Page 19: ...s too high the rotor is stationary malfunction of reactivation coil check fans and motors check the flow rates and the dampers check the engine and the belt check the reactivation coil The dehumidifie...

Page 20: ...Volt Ph Hz 400 3 50 Auxiliary power 24 V Connection Outlet Process Air 200 mm Connection Inlet Process Air 250 mm Connection Outlet Wet Air 160 mm Connection Inlet Reactivation Air 160 mm Weight 150...

Page 21: ...ecommended Comment Motordrive Motor a gear 230V 1Ph 50Hz 3g min grease for low temperature 1 1 belt rotor V Sezione trapezoidale 1 tensioning device 1 Process fan DKHR250FSB0714FFIE 1 Reactivation fan...

Page 22: ...BM Rotek Model SGM65 30 Speed g min 2590 2500 3 0 3 6 Power kW 0 37 0 155 11 VA Voltage V 400 230 230 Frequency Hz 50 60 50 60 50 60 Ampere A 0 65 0 68 0 015 Power factor Cos n a n a n a Protection cl...

Page 23: ...hed to the unit The power cables must be protected upstream against the effects of short circuit and overload by an appropriate device complies with regulations and laws The section of the cables must...

Page 24: ...FT DryAir HOW TO CONNECT THE POWER SUPPLY To supply electrical power to units AD remove the top panel use the special cable in the rear or side panel and connect the power cord to the terminal block i...

Page 25: ...Pagina 25 di 35 AD1100TE STD EN 00 Subject to change without notice TFT DryAir Electrical wiring See attached diagrams...

Page 26: ...function flashing it indicates absolute humidity or value DewPoint calculated fixed it indicates absolute humidity or DewPoint value read by the probe Indication cooling air pre and or post treatment...

Page 27: ...l Only vis Y_3P Indication value position of 3 point burner valve Only vis InrH Indication value relative humidity absolute humidity or DewPoint C g Kg Only vis HAbS Indication value of absolute humid...

Page 28: ...Setting the set point of pre treatment temperature Function disabled with parameter CF03 0 C 10 0 St06 Differential set point of pre treatment temperature the differential works all on one side above...

Page 29: ...eps 3 Electrical third step 3 steps 4 Electrical PWM control 5 Steam PWM control with converter 6 Throttle adjustment with 3 points 7 Gas adjustable on off on off burner reg High heat low heat 8 Steam...

Page 30: ...heating On Output reactivation of output pre cool it Pre heating OFF On OFF CF15 Operating settings General alarm unit OFF The unit continues to operate while keeping the process air control also in...

Page 31: ...You have enabled the after treatment without enabling the corresponding probe CF04 0 and CF05 0 No action Automatic A02 Alarm configuration You have enabled the display of the value of moisture withou...

Page 32: ...35 AD1100TE STD EN 00 Subject to change without notice TFT DryAir RESET alarms press the ESC key for about 3 seconds on the terminal display LED or put the AUTO 0 MAN 0 and bring it back to its previ...

Page 33: ...positioned in the fully closed is 0 while the fan continues to operate If the parameter FA01 OFF with the open contact of the first step step1 it will also stop the ventilation the fan of reactivation...

Page 34: ...Pagina 34 di 35 AD1100TE STD EN 00 Subject to change without notice TFT DryAir Notes...

Page 35: ...t to change without notice TFT DryAir By TECNOFRIGO TUSCANY srl Via J F Kennedy 25 27 29 56020 Capanne Z Ind Fontanelle Pisa Tel 39 0571467351 Fax 39 0571469217 e mail info tecnofrigo it info tftdryai...

Reviews: