background image

Texmate, Inc. Tel. (760) 598-9899  •  www.texmate.com

FL-B101Q-HZ_manual (d0059)

Page 7

Setpoint Adjust

The bargraph has the option to have up to 4 setpoints (two 9A Form C relays and two 4A Form A relays)  installed. Each relay may 

be set to activate either above or below its setpoint by inserting jumper clips on the Relay Activation header which is located on the 

Display Driver Board. See the layout diagram on Page 4 for the exact location. The steps to setup the setpoints are as follows:

1)  SELECT THE RELAY ACTIVATION MODE FOR EACH INSTALLED RELAY

Make sure that the required relays have been installed in the meter. Refer to the component layout on Page 11 for relay posi-

tions. If a jumper clip is installed in a specific relay position on the Relay Activation Mode Header, that relay will activate when 

the display bar is lower that the programmed setpoint. If no jumper clip is installed in a specific relay position on the Relay 

Activation Mode Header, that relay will activate when the display bar is equal to or higher that the programmed setpoint. The 

Diagrams below show some of the various possibilities for relay activation.

Default

SP1, SP2, SP3, and SP4 all activate when input is equal to or higher than set point.

SP2 and SP4 activate when input is lower than set point. SP1 and SP3 activate when input 

is equal to or higher than set point.

SP2 activate when input is lower than set point. SP1, SP3  and SP4 activate when input is 

equal to or higher than set point.

1

3 4

2

sP

1

3 4

2

sP

1

3 4

2

sP

SP1 and SP3 activate when input is lower than set point. SP2 and SP4 activate when input 

is equal to or higher than set point.

SP1, SP2, SP3, and SP4 all activate when input is lower than set point.

1

3 4

2

sP

SP1 and SP2 activate when input is lower than set point. SP3 and SP4 activate when input 

is equal to or higher than set point.

1

3 4

2

sP

1

3 4

2

sP

100

0

25

50

75

SP1 SP2 SP3 SP4

Zero Span

SP2

SP1

SP3

SP4

2)  ADJuST THE SETPOINT FOR EACH RELAY 

The setpoint for each relay is set by the front panel buttons marked SP1, SP2, SP3 and 

SP4. When a front panel button is pressed and held down, the associated setpoint is directly 

changed. The direction of change will be either up or down, as indicated by the UP and DOWN 

indicator LEDs. After the indicator LED lights up there is a 0.5 second delay before any change 

occurs. To reverse the direction of change, release the button and then press down again. As 

there are no menus or sub-menus to navigate, the programming and setup is quick and easy. 

Setpoints are indicated on the bar display by an ON segment if the bar is below the setpoint 

and with an OFF segment if the bar display is above the setpoint.

Summary of Contents for FL-B101Q-HZ

Page 1: ...upply AC DC Auto sensing wide range supply PS1 std 85 265 VAC 50 400 Hz 95 300 VDC 4 2W PS2 15 48 VAC 50 400 Hz 10 72 VDC 4 2W Operating Temp 0 to 50 C Storage Temp 20 C to 70 C Relative Humidity 95 n...

Page 2: ...there are no menu or sub menus to navigate the programming and setup is quick and Span Buttons Span Zero Buttons Zero Set Point Button SP1 SP2 SP3 SP4 Front Panel Buttons Zero Button The Zero Button s...

Page 3: ...d Mode 3 Hysteresis Band between SP1 SP2 This mode enables the Hysteresis function In order for Hysteresis to function SP2 must be set to a value greater than SP1 and SP2 should be selected as High h...

Page 4: ...and carefully lever the plastic catch up and tilt the Display Board assembly forward Then repeat this action with the bottom catches Step 5 Remove the entire Display Board assembly by sliding it out o...

Page 5: ...SPAN but ton is pressed the input signal being applied must be more than 5 higher or lower than the previously memorized value of the input signal that was being applied when the other button was last...

Page 6: ...20mA If now the scaling has to be changed to read zero to full scale for an input of 0 to 20mA only the low 4 mA end needs to be recalibrated The high 20 mA end of the scaling is left untouched and so...

Page 7: ...d SP4 activate when input is lower than set point SP1 and SP3 activate when input is equal to or higher than set point SP2 activate when input is lower than set point SP1 SP3 and SP4 activate when inp...

Page 8: ...color overrides the SP1 color STEP A ENTER COLOR SET MODE Hold down ALL four setpoint buttons SP1 SP2 SP3 and SP4 and apply power to the meter The meter will light up in the Color Set Mode Release all...

Page 9: ...utton adjust the analog output as measured on the external multimeter to be the required value 20mA in this example When the HI button is pressed the UP or DOWN indicator LED shows the direction of ch...

Page 10: ...0 to 20 mA 4 to 20 mA or V 0 to 10 V output is header selectable Pin 19 Programming LOCK By connecting the LOCK pin to the COMMON pin the meter s programmed parameters can be viewed but not changed P...

Page 11: ...omponent Glossary SPAN Turn Clockwise to Increase Reading To the Right Rear SPAN Potentiometer Pot If provided the 15 turn SPAN pot is always on the right side as viewed from the rear of the meter Typ...

Page 12: ...I series IO board The adapter snaps on the 36x144 mm 1 42 x5 69 case and enables single unit or stack mounting in an existing 6 edgewise pointer meter cut out 100 0 25 50 75 100 0 25 50 75 SP1 SP2 SP3...

Page 13: ...6 Metal Surround Case includes screw mounting clips 25 OP MTLCLIP Screw Mounting Clips 2 pc to screw tighten slide brackets 8 OP N4 144X36 144x36mm clear lockable front cover NEMA 4X splash proof 30 O...

Reviews: