Overview of Display Modes, Scaling Capabilities and Operating Modes
Input Hi
Input Low
std
Input Hi
Input Low
std Inv
Standard Scaling
Standard display mode selected and
scaled so bar increases as input signal
increases from Low to Hi.
Inverse Scaling
Standard display mode selected and
scaled so the bar increases as the input
signal decreases from Hi to Low.
CH1
CH2
Standard Display Mode
min_max
SP1
SP2
SP3
SP4
dual bar rvsd
SP1
SP2
SP3
SP4
Display with 4 Set Points
With Standard display or Center point
mode selected, the setpoints are
indicated by an ON segment outside
the bar display area and by an OFF
segment inside the bar display area.
Horizontal or Reverse Mounting
Meters can be mounted horizontally in
the panel and for those applications that
require an opposite growth of the bar,
the meter can be vertically or horizontally
mounted upside down
Mode 0 Channel Inputs
Horizontal and Reverse Mounting
with Custom Face Plate Installed
Mode 3 Hysteresis Band between SP1 & SP2
This mode enables the Hysteresis function. In order for Hysteresis to function, SP2 must be set to a value greater than SP1, and SP2 should be
selected as High (h) Setpoint (See page 7). When these conditions are met, and Mode 3 is selected, then a Hysteresis band is created for the
SP1 relay, with the upper limit of SP2 and the lower limit of SP1. SP2 relay continues to operate normally.
• For a tank filling application SP1 is set to a Low (L) Setpoint. SP1 relay can control a pump that fills the tank
With Mode 3 selected, SP1 relay activates for inputs less than the SP1 level. Once activated, SP1 relay will
stay ON until the tank is filled to the SP2 level.
• For a tank emptying application SP1 is set to a High (h) Setpoint. SP1 can control a pump that empties the
tank. With Mode 3 selected, SP1 relay activates for inputs greater than the SP2 level. Once activated, SP1
relay will stay ON until the tank is emptied to the SP1 level.
MODE
1
3
2
Tank Filling
SP1
Tank starts
filling when
level is at or
below SP1
SP2
SP1
Tank stops
filling when
level is at SP2
SP2
Tank Emptying
SP1
Tank stops
emptying when
level is at SP1
SP2
SP1
Tank starts
emptying when
level is at or
above SP2
SP2
MODE
1
3
2