CL-B101D40-TCRTD Manual (d0099)

Page 5

Example

Example

From Thermocouple

or RTD Type Selection 

Mode See Page 4

STEP A

STEP B

See Example Above

of Bargraph Display 

Scale Range

DIGITAL SPAN SELECTION

FOR BARGRAPH DISPLAY

STEP C

To Digital Span Selection

for Analog Range Output or

Bargraph Center Point

Display Mode Selection

on Page 6

STEP A  Enter the Calibration Sub Menu Mode

 

1)  Press the 

P

 and   buttons at the same time. 

Display toggles between [CAL] and [oFF]. 

 

2)  Press the 

P

 button. Display toggles between 

[bhi] and the previous setting.

STEP B  Set the Digital Span of the Bargraph Display (See 

example above)

 

1)  Using the   and   buttons, adjust the display 

to the desired high parameter reading, e.g. 

6000 counts.

 

2)  Press the 

P

 button. Display toggles between 

[bLo] and the previous setting.

 

3)  Using the   and   buttons, adjust the display 

to the desired low parameter reading, e.g. 4000 

counts.

 

4) Press the 

P

 button. Display changes from 

[4000] to [dP].  

Brightness Selection

STEP C

   

 

Press the 

P

 button. Display toggles between [br] 

and the previous brightness setting.

 

Set the Bargraph and Digital Display Brightness

 

1)  Using the   and   buttons, adjust the display 

to the desired brightness setting (4 is the 

brightest setting).

 

2)  Press the 

P

 button. Display toggles between 

[Anhi] and the previous [Anhi] setting.

Note:

 If at this point, the display skips directly to STEP G and 

toggles between [Cto] and [oFF], the software is detecting 

that the optional analog output hardware is NOT installed.

Digital Span Selection For Bargraph Display

Bargraph does not light 

up for Input Signals up to 

3999 counts 

Bargraph lights up for 

Input Signals above 

4000 counts

Bar

High

Bar

Low

Bar

High

Bar

Low

0

25

75

100

50

0

25

75

100

50

No bargraph display

Digital display

No bargraph display

Digital display

An example of setting the 

digital span of the bargraph 

display to be different than 

the digital display range

The bargraph can be set to display full scale (0-101 bars) any portion 
of the digital reading from a minimum of 100 counts to a maximum of 
12,000 counts. This provides higher resolution bargraph indication for 
those applications where the normal operating input signal range is less 
than the desired full scale display range of the digital display.

For Example:

If the full scale range of the meter has been set from -1999 to 
9999 (0-12,000 counts), but the normal operating range of the 
input signal is between 4000 & 6000. The bargraph high parame-
ter [bhi] can be set to 6000 and the bargraph low parameter [bLo] 
can be set to 4000. 

This means that although the meter could digitally display a signal 
from -1999 to 9999 (0-12,000 counts), the bargraph display only 
begins to function at a reading of 4000, and reaches full scale 
indication at a reading of 6000. Although the digital display will 
continue reading up to 9999 before indicating overrange, the bar-
graph display will indicate its overrange by flashing for readings 
above 6000.

Summary of Contents for CL-B101D40-TCRTD

Page 1: ...or below Lo each setpoint Digital display blanking Decimal point setting Four level brightness control LEOPARD FAMILY Input Specs Depends on Input signal conditioner A D Converter 14 bit single slope...

Page 2: ...direction indicated by the arrow When an alternative dotted line is shown this indicates that an alternative logic branch will be followed when a particular option is present When two buttons are sho...

Page 3: ...999 seconds Pump PUM Hysteresis hYSt Hysteresis hYSt Hysteresis hYSt Setpoint 3 SP3 Setpoint 4 SP4 Operational Display MAIN MENU BRIGHTNESS AND SETPOINT VIEW MODE Bargraph Center Point Display Selecti...

Page 4: ...E STEP A Calibration Mode STEP B Calibration Mode To Digital Span Selection for Bargraph Display Page 5 cAL out iP branch will only appear if the analog output option is installed otherwise cAL on goe...

Page 5: ...between Cto and oFF the software is detecting that the optional analog output hardware is NOT installed Digital Span Selection For Bargraph Display Bargraph does not light up for Input Signals up to...

Page 6: ...igh and AnLo analog low can be reversed to provide a 20 to 4mA output The digital span selected can be as small as two counts when using the analog output to function as a Control or Alarm Driver Smal...

Page 7: ...nd 18 see Rear Panel Pinouts on page 10 Using the and buttons adjust the analog output to the desired low value as measured on the multimeter cLo may be adjusted to any value from 0 3 mA to 18 mA mA o...

Page 8: ...Press the P button Display toggles between PUM and on or oFF STEP F Select Pump PUM on or oFF 1 Using the and buttons select the Pump to be ON or OFF When PUM is selected ON and SP2 is set at a value...

Page 9: ...Bargraph Color when the bar is ABOVE SP2 Setpoint 1 Using the and buttons select the desired bargraph color grn oran or red 2 Press the P button Display toggles between CSP3 and the previous color se...

Page 10: ...p Form A relays An analog output module is also shown as installed The CL B101D40 TCRTD uses plug in type screw terminal con nectors for all input and output connections The power supply connections p...

Page 11: ...5A SP4 SP3 SP2 SP1 SP1 SP2 SP3 SP4 Relay Modules with 4 Isolated 5A Form A Relays Output Carrier Board Output Carrier Board Relay Module Relay Module Input Signal Conditioner Analog Output Module Mai...

Page 12: ...the back panel back into the case Apply power to the meter 4 Enter the program mode and select the type of thermocouple J K R T the resolution 0 1 or 1 and the display units C or F See Page 4 of the d...

Page 13: ...10 72VDC Input Modules Partial List See www texmate com IT10 Thermocouple J K R T Selectable C F 1 0 1 IT11 RTD 100 Pt Selectable 3 4 wire C F 1 0 1 385 392 IT15 RTD 1000 Pt Selectable 3 4 wire C F 1...

Reviews: