DN-107NE display series
4-2
OPERATION
CHAPTER 4
In order to enter the sequence to modify the parameters, the Advance key “*” must be
pressed and held for three seconds. After this, the first parameters will be displayed, with the digit
flashing.
There are then two options:
1-
Modify the parameter value
By pressing the Advance key "*", the values and the parameter number correlatively can
be selected.
To increase the parameter value, press the “+” key. After parameter 7 it returns to 1.
2- Select another parameter
In order to select another parameter, the parameter number must be made to flash using
the “*” key and then the new parameter may be selected using the “+” key. The number if the
parameter is: The left one when the decimal dot is activated in 2 digit displays. In 3 or more digits
displays the third digit starting from the right.
In order to exit the sequence for modifying parameters, parameter F must be selected
then press "*".
0 = Protocols TCP/IP and UDP/IP
1 = Protocol Modbus/TCP. Function 06h and Function 10h ASCII
2 = Protocol Modbus/TCP. Function 5h and Function 10h Word
Allows for code selection to indicate that the block has been completely sent.
Value
End of block
0
CR
0Dh
1
LF
0Ah
2
CR LF
0Dh 0Ah
3
LF CR
0Ah 0Dh
4
03h
5
02h
6
* CR
2Ah 0Dh
7
04h
4.2.3.1. Parameter 1:Protocol
4.2.2. Exit modify parameters
4.2.3. Function of each parameter
4.2.3.2. Parameter 2:End of Block. Only TCP/IP and UDP/IP protocols
4.2.1. Enter to modify parameters