4 Transmitter
12
4.2.2.
Scaling
There are three types of min./max. values:
1
The measuring range: The maximum sensor performance is in
this range. Measuring range, see table (below).
2
Standard scaling: The output signals are assigned to this
measuring range as standard:
◦
during delivery if no entries are made in the order code
◦
after exchanging the unit, the measuring range recorded in
the instrument is applied as standard.
The transmitter even retains its scaling with the voltage
disconnected.
Measuring range, see table (below).
3
The maximum settings for the manual scaling
◦
The maximum limits can be calculated as follows:
X = difference between MIN. and MAX. value of the
standard scaling
(Max. value of standard) + (50 % of X)
(Min. value of standard) - (50 % of X)
◦
It is thus possible to scale beyond the measuring range, e.g.
for the adjustment of the scaling limits to standard values of
a PLC.
With the alarm definition, however, the physical measuring
range limits are decisive.
Pos: 28 /TD/Produktbeschreibung/Übersicht/MUF 63xx/Tabelle Skalierung MUF 6321 @ 3\mod_1241617696391_79.doc @ 32646 @
Measuring range/
standard scaling
Maximum scaling
0 to 100 Pa
-50 to 150
0 to 10 hPa
-5 to 15
0 to 20 hPa
-10 to 30
0 to 50 hPa
-25 to 75
0 to 100 hPa
-50 to 150
0 to 500 hPa
-250 to 750
0 to 1000 hPa
-500 to 1500
0 to 2000 hPa
-1000 to 3000
-100 to 100 Pa
-200 to 200
-10 to 10 hPa
-20 to 20