7 Maintaining the product
74
7.8.
Condensate container
The fill level of the condensate trap can be read from the markings
on the condensate trap. A warning message (
, red flashing light)
is displayed if the fill level in the condensate trap reaches 90 %.
The fill level of the condensate trap can be read from the markings.
Draining the condensate trap
The condensate consists of a weak mix of acids. Avoid skin
contact. Make sure that the condensate does not run over
the housing.
CAUTION
Condensate entering the gas path.
Damage to sensors and flue gas pump
!
> Do not empty the condensate trap while the flue gas pump is in
operation.
1.
Unlock the condensate trap and pull it vertically off the
measuring box.
2.
Open the condensate outlet on the condensate trap: Pull out
approx. 5 mm against the stop.
3.
Let the condensate run out into a sink.
4.
Wipe off any drops still on the condensate outlet with a cloth
and close the condensate outlet.