TI150 Series Battery Charger/Conditioner
19
6
Unit Care and Maintenance
Figure 6.2.2 – Multimeter reading
continuity
Figure 6.2.3 – Multimeter reading
open circuit
Checking DC Voltage at the DC Output Cable
In order to properly test the dc output the unit needs to be connected to a battery. Make sure to reconnect
the DC Output Cable according to Section 5 Pre-Operation procedures. Then, plug the unit into the
appropriate line voltage. Once this is accomplished, set your digital multimeter to measure dc voltage.
Place the positive probe (red) of the multimeter on the positive terminal (red) of the DC Output Cable. Next,
place the negative probe (black) on the negative terminal (black) of the DC Output Cable. The multimeter
display should read between 12.0 and 14.25 Vdc for the TI15014 series charger (see Figure 6.2.4) and
between 24.0 and 28.5 Vdc for the TI15028 series charger (see Figure 6.2.5). If the unit is not providing
any output voltage refer to Section 8 under Troubleshooting. Otherwise, contact the Tesla™ Customer
Service at (302) 324-8910.
Figure 6.2.4 – Multimeter reading typical
12 V power cell voltage
Figure 6.2.5 – Multimeter reading typical
24 V power cell voltage
Once the TI150 Series Battery Charger/Conditioner has fully passed function
test procedures, the unit is ready for use.