8
ENG
– Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
– Label the system when charging is complete (if not already).
– Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on
completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the
site.
14. Decommissioning(Annex DD.11)
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment
and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task
being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of
reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
• Mechanical handling equipment is available, if required, for handling refrigerant cylinders;
• All personal protective equipment is available and being used correctly;
• The recovery process is supervised at all times by a competent person;
• Recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the
system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and
the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and
checked.
15. Labelling(Annex DD.12)
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label
shall be dated and signed. Ensure that there are labels on the equipment stating the equipment contains
flammable refrigerant.
16. Recovery(Annex DD.13)
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good
practice that all refrigerants are removed safely. When transferring refrigerant into cylinders, ensure that only
appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for
holding the total system charge is available. All cylinders to be used are designated for the recovered refrigerant
and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete
with pressure relief valve and associated shut-off valves in good working order. Empty recovery cylinders are
evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment
that is at hand and shall be suitable for the recovery of flammable refrigerants. In addition, a set of calibrated
weighing scales shall be available and in good working order. Hoses shall be complete with leak-free
disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory
working order, has been properly maintained and that any associated electrical components are sealed to
prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the
relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable
level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process
shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the compressor
body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out
safely.
Summary of Contents for TA71FFUL-2432IAW
Page 1: ...PORTABLE AIR CONDITIONER USER MANUAL Ver 2021 RO SLO SRB ENG BG GR BIH MNE HR MKD...
Page 59: ...59 BG T 3 15A 250VAC IEC R290 13 2 R290...
Page 61: ...61 BG 6 DD 3 1 2 3 4 5 CO2 6 7 8 9...
Page 62: ...62 BG 7 DD 4 1 2 8 DD 5 9 DD 6 10 DD 7 11 DD 8...
Page 63: ...63 BG LFL 25 OFN 12 DD 9 OFN OFN OFN 13 DD 10 OFN 14 DD 11 a b...
Page 64: ...64 BG c d e f g h 80 i j k 15 DD 12 16 DD 13...
Page 65: ...65 BG GG 2 GG 4 GG 5 IEC 60079 15 2010 a b c 5 d...
Page 66: ...66 BG 5 e 5...
Page 67: ...67 BG 2012 19 1 2 3 4 5 6 7 8 9 10 1 1 AAA 1 5V 1 1...
Page 68: ...68 BG 18 45 1 1 2 2 3 3 4 4 5 6 1 2 3 4 5 6...
Page 69: ...69 BG 1 A B C 2 B A 3 4 18 45 cm...
Page 70: ...70 BG WiFi WIFI Wi Fi...
Page 71: ...71 BG COOL HEAT Cool 18 C 32 C 64 F 90 F Heat 13 C 27 C 55 F 81 F 24 C 27 C 75 F 81 F FAN COOL...
Page 72: ...72 BG FAN DRY Fan Dry 3 7 8 7 8...
Page 73: ...73 BG 24 C 5 Timer Timer 5 Timer Timer...
Page 74: ...74 BG 7 AAA 1 5V 7...
Page 77: ...77 BG 24 C 24 5 5 9 1 10 11 9 10 11...
Page 78: ...78 BG FULL TANK 1 2 3 4 5 6 1 2 3 1 2 12 7 mm 4 5 12 13 12 13 14 15 14 15...
Page 79: ...79 BG Dry 1 2 3 1 2 12 7 mm 4 5 C D A B C D...
Page 80: ...80 BG 40 C 104 F 16 16 https tesla info wp content uploads pdf TeslaTTPWiFiapp pdf...
Page 81: ...81 BG 18 C 35 C 64 F 95 F 30 90 10 C 25 C 50 F 77 F 30 90 30...
Page 83: ...83 24 13 12 TESLA 1 2 2 1 2 2 TESLA 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10...
Page 84: ...84 2 11 2 12 3 4 5 6 7 8 112 115 119 112 1 2 1 2 3 113 1 2 3 2 114 4 5 114 1 113 1 2...
Page 85: ...85 2 3 115 4 115 1 2 1 3 1 1 10 02 9700970 02 9700971 9 30 19 00 10 00 16 00...
Page 86: ...86...
Page 87: ...87 GR GWP R410A 2088 R134a 1430 R290 3 R32 675 6 50kg Wi Fi 20dBm 2412MHz 2472MHz 2014 53 EN 8...
Page 88: ...88 GR T 3 15A 250VAC IEC R290 13 m2 R290...
Page 90: ...90 GR 4 5 CO2 6 7 8 9 7 DD 4...
Page 91: ...91 GR 1 2 8 DD 5 9 DD 6 10 DD 7 11 DD 8 LFL 25 OFN 12 DD 9...
Page 92: ...92 GR OFN OFN OFN 13 DD 10 OFN 14 DD 11 a b c d e f g h 80 i j k 15 DD 12...
Page 93: ...93 GR 16 DD 13 GG 2 GG 4 GG 5 IEC 60079 15 2010 a b...
Page 94: ...94 GR c 5 d 5 e 5...
Page 95: ...95 GR 2012 19...
Page 96: ...96 GR 1 2 3 4 5 6 7 8 9 10 Continuous drain outlet 1 1 AAA 1 5V 1 1...
Page 97: ...97 GR 45cm 1 1 2 2 3 3 4 4 5 6 1 2 3 4 5 6...
Page 98: ...98 GR 1 A B C 2 3 4 45cm...
Page 99: ...99 GR WiFi WIFI Wi Fi...
Page 100: ...100 GR 18 C 32 C 64 F 90 F 13 C 27 C 55 F 81 F 24 C 27 C 75 F 81 F...
Page 101: ...101 GR 3 7 7 7 8...
Page 102: ...102 GR 24 C 5 5...
Page 103: ...103 GR PROBE FAILURE FULLTANK On Off 7 AAA 1 5V 7...
Page 104: ...104 GR 18 C 32 C 64 F 90 F 24 C 27 C 75 F 81 F 13 C 27 C 55 F 81 F...
Page 105: ...105 GR 1 C 1 F 2 6 1 C 1 F 3 5 23 C 73 F 23 C 73 F 20 C 68 F 20 C 68 F 23 C 73 F 23 C 73 F...
Page 106: ...106 GR 24 C 1 24 5 5 9 1 cm 10 11 9 10 11...
Page 107: ...107 GR FULLTANK 1 2 3 4 5 6 1 2 3 12 7mm 4 5 12 13 12 13 14 15 14 15...
Page 108: ...108 GR 1 2 A 3 12 7mm 4 5 A B C D...
Page 109: ...109 GR 40 C 16 16 SmartWiFi https tesla info wp content uploads pdf TeslaTTPWiFiapp pdf...
Page 110: ...110 GR 18 C 35 C 64 F 95 F 30 90 10 C 25 C 50 F 77 F 30 90 30...
Page 112: ...112 6 7 service TESLA TESLA 8 9 TESLA 10 email warranty gr comtrade com...
Page 113: ...113 1 Service 2 Service 3 Service 4 Service 5 Service 6 Service 7 Service 8 Service 9 Service...
Page 141: ...141 MK 3 15 250VAC IEC R290 13 2 R290...
Page 143: ...143 MK 2 6 7 8 9 7 4 1 2...
Page 144: ...144 MK 8 5 9 6 10 7 11 8 LFL 25 OFN 12 9 OFN...
Page 145: ...145 MK OFN OFN 13 10 OFN 14 11 80 e 15 12 16 13...
Page 146: ...146 MK 2 GG 4 GG 5 IEC 60079 15 2010 a...
Page 147: ...147 MK 5 5 Rashodovanje 5...
Page 148: ...148 MK 2012 19...
Page 149: ...149 MK 1 2 3 4 5 6 7 8 9 10 Continuous drain outlet 1 1 2 x AAA 1 5V 1 1...
Page 150: ...150 MK 45 cm 1 1 2 3 3 4 4 5 6 1 2 3 4 Zaklju ati Prevuci na 5 6...
Page 151: ...151 MK 1 2 3 4 45 s 40...
Page 152: ...152 MK WiFi WIFI Wi Fi...
Page 154: ...154 MK Fan High Medium Low Dry...
Page 155: ...155 MK 24 C Tajmer 5 Tajmer Tajmer Tajmer 5 Tajmer Tajmer Tajmer...
Page 156: ...156 MK Tajmer 7 MAX 7 AAA 1 5V...
Page 158: ...158 MK 9 1 10 11 9 10 11 1 2 3 4 5 6 12 12...
Page 159: ...159 MK 1 2 3 1 2 12 7 mm 4 5 13 13 14 15 14 15 Dry 1 A 2 1 2 12 7 mm 3 4 A B...
Page 160: ...160 MK Cool ili Dry Cool C D 40 C 104 F...
Page 162: ...162 MK WiFi https tesla info wp content uploads pdf TeslaTTPWiFiapp pdf...
Page 164: ...164 1 30 2 3 3 12 12 12...
Page 165: ...165...
Page 166: ...166 Customer signature m C C V 15 1 2 3 C C V C C V...
Page 251: ......
Page 252: ...www tesla info...