2. General Operation

Description of Turnkey and funktion keys

Turnkey D 1 sets:

m
m

m
m
m

Change of room temperature inHeat circuit A and/or B out of the main menu

“Home”-key (press) out of all other menus

Choose a menue point through turning and pressing (= Cursor funktion).

Change and save Data through turning and pressing

Display the Cursor through pressing.

Loading the standard program

“Help”-key: Nearley every Menue has a Help. To leave the Help press key D1.

Announcements status report from the main menue, if the cursor is not visible (see page 27).

reserved for the maintainance (fundamental settings), pin secured.

Display Submenue of Temperatures, Running time, Switch impulses, Running mode, emergancy run, Bath Summer
mode and Machine Data.

Turnkey D 2 sets:

Funktion key F 1:

Funktion key F 2:

Funktion key F 3:

Funktion key F 4:

Funktion key F 5:

Funktion key F 6:

Terms, which are

, are more near described on page 28!

underlined

Chimney cleaning Function, also Fast heating Function

Immediate storage charging. The storage will be charged at any time without changing the Charging time program.

Page 2

IDM-Mainmenue 30/07/02 11:02

Heat circ A:
Heat circ B:

Heatpump: on
[1]

32°C,

next

outd-
temp:

19

°C

20,7°C

21,2°C

Buffertemp.:

52°C

D1

D2

F1

F2

F3

F4

F5

F6

Note: In principle all attitudes on the regulation can be accomplished through
turn and press of the right turn-key D2 to.

Summary of Contents for HGL-Heatpump

Page 1: ...Users manual TERRA HGL Heatpump Expenditure Sept 2005 TERRA HGL_ Bedienung_Sept05 engl cdr Expenditure Sept 2005 TERRA HGL_ Bedienung_Sept05 engl cdr h e a t p u m p ...

Page 2: ... 15 Automatic heatpump connection 15 16 Loading buffer once 16 17 ActivateBath Summer mode 17 18 Activate presence operation 18 19 Activate emergency operation 19 20 Cooling 20 21 Cement floor heating program 21 23 Display all temperatures 23 24 Display operating hours and switch impulses 24 25 Display relais status 25 26 Display installation details 26 27 Error display 27 28 Glossary 28 7 2 4 4 1...

Page 3: ...ely You will contain important notes and for the sure and economical operation of the plant Installation and maintenance can involve dangers by high Plant pressures high temperatures and volta ge carrying Parts and being and must be done by ex perts Heat pumps may only be installed by competent ex perts and put into operation only by a company which is trained by IDM energy systems GmbH For work o...

Page 4: ...e fundamental settings pin secured Display Submenue of Temperatures Running time Switch impulses Running mode emergancy run Bath Summer mode and Machine Data Turnkey D 2 sets Funktion key F1 Funktion key F2 Funktion key F3 Funktion key F4 Funktion key F5 Funktion key F6 Terms which are are more near described on page 28 underlined Chimney cleaning Function also Fast heating Function Immediate stor...

Page 5: ...erature Sunshade is displayed in Summer mode Shows the actual outside temperature Shows the Day and Time Shows the heating circuit operation mode Heating Circuit Operation with Nominaltemp Heating Circuit Operation with temperature saving Pump in operation Heat Circuit Operation in Heating program 21 7 C Shows the measured room temperaturewith attached ambient temperature feeler Announcement conta...

Page 6: ... blocking times cooling D1 D2 Submenu 1 Page 2 back Settings domesticwater Cement floor heating program D1 D2 Expert Level domestic water back desired domestic water temp 47 C times for loading buffer should be set D2 D2 D2 1 2 D2 D2 6 7 8 9 next desired domestic water temp D2 47 C D2 D2 back D2 D2 D2 3 4 next D2 D2 5 Settings domesticwater Note Consider during attitude of the desired water temper...

Page 7: ...for Heat circ B 22 C 20 C for Heat circ A 1 2 3 for Heat circ A D1 D1 D1 21 C 4 5 for Heat circ B D1 D1 D1 19 C D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 19 C 20 7 C 21 2 C next D1 D2 roomtemperature desired for Heat circ B 22 C 20 C for Heat circ A ...

Page 8: ...ct curve 10 room temp day 22 C night 16 C influence room off quota 100 Seite 6 D1 D2 Heat circ A settings heating program non freezing on function heating program constant at 35 C back next D2 D2 D2 D2 1 2 D2 D2 3 4 5 6 7 8 9 D2 D2 D2 D2 Heat circ A B next room temp day 20 C night D2 D2 D2 D2 8 C D2 D2 back 6 Desired room temperature Nominaltemperatur desire Version 2 D1 D2 IDM Mainmenu 30 07 00 1...

Page 9: ...er rooms connected to the heat circuit Note The room influence can only be switched on if it s switched on in the service menu Page 7 D2 D2 D2 D2 1 2 D2 D2 3 4 5 6 7 8 9 D2 D2 D2 D2 Heat circ A B next influence room on quota D2 D2 D2 D2 98 D2 D2 back D1 D2 Heat circ A settings heating program non freezing on function heating program constant at 35 C back next D1 D2 IDM Mainmenu 30 07 00 11 02 cloc...

Page 10: ...0 60 80 C 2 5 8 11 14 17 20 23 25 Vorlauftemperatur Außentemperatur Steilheit der Kennlinie Note If the appropriate heating circle is defined in the Service menue as floor or wall heating circle can be adjusted with characteristic maximally 10 Page 8 D1 D2 Heat circ A settings heating program non freezing on function heating program constant at 35 C back next D1 D2 IDM Mainmenu 30 07 00 11 02 cloc...

Page 11: ...tching and the heating times have no effect Heat circuit A is switched off Except for Antifreeze function The heating circuit A runs in cooling operation The temperature must be set for heat circuit A The Mainmenu shows cooling and the pump for heat circuitA Note In the case of use of the external contact the mode of operation of the heating circles depending upon attitude in the specialist level ...

Page 12: ...ay D2 D2 unequal D2 D2 settings heat program D2 D2 next D1 To copy the Heat Time from Monday to Tuesday The cursor position is onto unequal As soon the Heat times are copied to Tuesday it says unequal again The Heat time copying from Tuesday to Wednesday and from Wednesday to Thursday etc is done in the same way like from Monday toTuesday Page 10 D2 D2 D2 D1 D2 Heat circ A settings heating program...

Page 13: ...ct sees in addition the description of function The warm water storage is charged after the set loading times The buffertank will always be loaded as soon the buffer temperature is below the setTemperature always off The buffertank is not been heated to provide warm water Note D2 D2 back D2 D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 19 C 20 7 C 21 ...

Page 14: ... 06 30 bis 22 00 06 30 bis 20 00 D2 D2 D2 D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 19 C 20 7 C 21 2 C next D1 D2 Submenu 1 Page 1 Bufferloading loading program Settings bufferloading back next General settings Set power blocking times cooling To copy the bufferloading time from Monday to Tuesday The cursor position is onto unequal As soon the buf...

Page 15: ... t operate D2 D2 D2 05 00 bis 22 00 06 30 bis 22 00 06 30 bis 20 00 D2 D2 D2 D1 D2 set power blocking periodes back periode 1 06 00 till 22 00 o clock periode 2 00 00 till 00 00 o clock periode 3 00 00 till 00 00 o clock D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 19 C 20 7 C 21 2 C next D1 D2 Submenu 1 Page 1 Bufferloading loading program Settings ...

Page 16: ...m water The heatpump is disconnected and won t supply any warm water to the buffertank or into heating on off Note In the case of use of the external contact the heatpump connection depending upon attitude in the specialist level can depend on the switching status of the external contact sees in addition the description of function D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B He...

Page 17: ...into the heating the engagement of the heat pump is retarded at the adjusted time e g although a solar plant is present Yes no time setting D1 D2 General Settings Summer Winter change autom Switch on heat p yes 30 min 21 Date Time 31 07 00 11 02 o clock Heatpump on Runtime circulation pump 3 Minutes back D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 1...

Page 18: ... buffer are shown Note The buffer loading once can just get activated if there is a heat pump connected The loading just starts if the actual temperature is below 46 C and the desired temperature It stays activated until the actual temperature is 10 C above the set temperature reaches 55 C or the heatpump is switched off by the max temperature of the heatpump D1 D2 IDM Mainmenu 30 07 00 11 02 cloc...

Page 19: ...n Install details 1 D2 2 3 Bath Summer operation D2 F6 D2 D2 4 5 6 7 Bath Summer operation D2 D2 off D2 D2 back Note The Bath Summer operation mode sets the outside temperature onto constant 7 C This makes it possible that you can use the Heating also during the summer Not used Heating circuits must be switched off In the main menu and under the displayed Temperatures there are no temperatures sho...

Page 20: ... D2 D2 back F4 Note The Bath Summer operation mode sets the outside temperature onto constant 7 C This makes it possible that you can use the Heating also during the summer Not used Heating circuits must be switched off In the main menu and under the displayed Temperatures there are no temperatures shown D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 1...

Page 21: ...f D2 D2 back Note In this function secures the heat supply if e g a sensor is fefect Note The emergency operation switches off as soon you leave the window D1 D2 Submenu 2 Temperatures operating hours impulses Bath Summer operation back Relais Status F1 F2 F3 F4 F5 F6 Emergency operation Install details D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 19...

Page 22: ...ircuits The temperature is only valid for the cooling not for heating You can also set the switch differential and the min temperature The mixer mixes the flow temperature onto the min temperature 2K Hinweis To use the cooling function you need to have a room sensor D2 D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 19 C 20 7 C 21 2 C next D1 D2 Submenu...

Page 23: ...ently the temperature is increased daily by 5 C up to the adjusted maximum temperature of the heating circles With this maximum inlet tempe rature the heating circles are heated for 4 days At the end the flow temperature of the desired heating circles is lowered again around 5 C per day to 25 C While the cement heating are the heating programs for the heating circles not actively the heating circl...

Page 24: ...04 10 02 D2 D2 30 07 04 10 05 30 07 04 10 02 D2 D2 D1 D2 General Settings Summer Winter change autom Switch on heat p yes 30 min 21 Date Time 31 07 00 11 02 o clock Heatpump on Runtime circulation pump 3 Minutes back D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 19 C 20 7 C 21 2 C next D1 D2 Submenu 1 Page 1 Bufferloading loading program Settings buff...

Page 25: ...e groundwaterreturn Fühler 5 flow heat circuit A Fühler 6 buffertemperature Fühler 7 domestic water Fühler 8 flow HGL Fühler 9 flow heat circuit B Fühler 10 room heat circuit A Fühler 11 room heat circuit B Fühler 12 ext contact Note The sensors 4 6 7 9 10 and 11 just shows a temperature if there is a sensor connected Sensor 12 always shows ext cont D1 D2 Submenu 2 Temperatures operating hours imp...

Page 26: ... Imp medium heatpump temperature 38 C back F1 F2 F3 F4 F5 F6 D2 1 2 D2 D2 D2 3 D2 back Go to the window overview temperatures as described in chapter 23 D1 D2 Overview temperatures sensor 1 15 C sensor 2 39 C sensor 3 34 C sensor 4 53 C sensor 5 32 C sensor 6 51 C F1 F2 F3 F4 F5 F6 sensor 7 49 C sensor 8 57 8 C sensor 9 32 C sensor 10 20 7 C sensor 11 21 2 C sensor 12 ext cont ...

Page 27: ...Heat circuitA open Relay 4 Mixer Heat circuitA close Relay 5 Heatpump 2 Relay 6 Pump Heat circuit B Relay 7 Mixer Heat circuit B open Relay 8 Mixer Heat circuit B close Relay 9 cooling valve Relay 10 Mixer HGL open Relay 11 Mixer HGL close Relay 12 circulation pump Relay 13 error display Triac 1 exchanger pump 0 off Triac 2 loading pump 0 off Triac 3 pump heat circuitA 0 off D1 D2 Submenu 2 Temper...

Page 28: ...gram version WP 04 01 07 HGL Start up date 02 07 01 Telefone service 1234567890 back 1 D2 2 3 Installation details D2 F6 D2 D2 4 5 D2 back D1 D2 Submenu 2 Temperatures operating hours impulses Bath Summer operation back Relay Status F1 F2 F3 F4 F5 F6 Emergancy operation Install details D1 D2 IDM Mainmenu 30 07 00 11 02 clock Heat circ A Heat circ B Heatpump on 1 32 C outd temp 19 C 20 7 C 21 2 C n...

Page 29: ...rking You can find out which by going to overview temperatures page 17 The relation between operation hours and switch impulses is bad The gap between flow and return temperature of the heat pump is too big Check mixers The heat pump was switched off by the Max temperature threshold and will switch back on as soon the temperature reaches 49 C Displayed Errors 1 High pressure 2 Low Pressure 3 Therm...

Page 30: ...ted heating circuit indipendend from the temperature outdoor from heatprogram and from Summer Winter change Coleration between the outdoor temperature and the flow temperature from heating Individual attitude of the heat curve a higher attitude causes higher flow temperatures The temperature the respective heat circuit is provided Indipendedend from the function of the heat circuit norm safe opera...

Reviews: