20.
Replace the thermoformed front panel and the
lift-off cover.
D.
When this procedure is complete, the operator may
restart the unit. In many cases, a new pump seal will
experience a small amount of leakage for a short time.
This is normal. After a few moments, the new seal will
take seat and the leak will stop.
Stationary member
Figure 5.1H
Rotating member
Figure 5.1I
Aligning impeller and
spring
Figure 5.1J