background image

The rotary switch on the controller, located in the

upper left corner, needs to be set to the proper

protocol (1=MSTP, 2=ARCnet, 3=Modbus). Contact

your BMS engineer for information of which

protocol is being used.

1.  On the 

Router

 screen make sure to change

PORT S1 value to specific network number for

communication protocol.

2.  On the 

IP

 screen make sure to set the IP

Network to 

0

 if not already.

Safety switches

High pressure switch (HPS1)

: If HPS1 is open,

compressor #1 will turn off and the controller

will issue an alarm. After manually resetting

HPS1, the HPS1 alarm will reset. Following

a minimum time off delay, compressor #1

will turn on. If the controller records 3 high

pressure start/restart failure incidents within

1 hour, compressor #1 is locked out and the

controller will issue an alarm. The compressor

lock-out can be reset in the EQ2 display pad or

by cycling the power of the controller. Refer to

the IOM for more information.

• For systems with two circuits, this is the same

for compressor #2, Y2 and HPS2.

Low pressure switch (LPS1)

: If LPS1 is open

after the LPS1 by-pass time, the controller

will issue an alarm and compressor #1 turns

off. After 30 seconds (fixed), the LPS1 alarm

will reset. Following the minimum time-off

delay, the compressor #1 will turn on. If the

controller records 3 low pressure start/restart

failure incidents within 1 hour, compressor #1

is locked out and the controller will issue an

alarm. The compressor lock-out can be reset

in the EQ2 display pad or by cycling the power

of the controller. Refer to the IOM for more

information.

• For systems with two circuits, this is the same

for compressor #2, Y2 and LPS2.

Safety shutdowns

Smoke detector (optional)

: When a smoke

detector (SD) is provided, it is wired directly

to the controller. If smoke is detected, the

controller will shut down the unit. The alarm

can be reset in the EQ2 display pad or by

cycling the power of the controller.

• If a compressor fails to start 3 times in an

hour due to high pressure switch lock out. The

alarm can be reset in the EQ2 display pad or by

cycling the power of the controller.

• If a compressor fails to start 3 times in an

hour due to low pressure switch lock out. The

alarm can be reset in the EQ2 display pad or by

cycling the power of the controller.

• If a compressor fails to start 3 times in an hour

due to DX LAT or suction line temperature lock

out. The alarm can be reset in the EQ2 display

pad or by cycling the power of the controller.

If the controller detects an SAT sensor failure. The

alarm can be reset in the EQ2 display pad or by

cycling the power of the controller.

TEMPMASTER® IS A REGISTERED TRADEMARK OF JOHNSON CONTROLS © 2021 Johnson Controls. All rights reserved. Subject to change

without notice. 100 JCI Way, York, Pennsylvania USA 17406-8469.

Summary of Contents for LS-1628

Page 1: ...y terminals located on the bottom of the controller All output connections wire into the blue terminals located on top of the controller Refer to the wiring diagram included with the unit for the conn...

Page 2: ...nostic The Standby screen shows the program name version number date of revision issue and the current operational condition mode of the unit i e UNOCCUPIED SCHEDULE is the initial condition Press the...

Page 3: ...Tech settings Occupancy control SF min setting enable settings Admin Misc setup BAS ModStat config Admin Calibration Allows manual of sensor readings used for testing of unit and sensor calibration Ad...

Page 4: ...l light when the current sensor closes for compressor 1 HPS1 and LPS1 should always have the light on FRZ1 will light when the DXLAT1 sensor is below 38 F Clg Mode will be on when OAT is above 55 F an...

Page 5: ...occupancy control unit enable supply fan minimum run settings ZAT SAT reset on off emergency heat enable and many more Please refer to specific unit sequence of operation for specific run conditions...

Page 6: ...d a zone sensor if needed The following four charts show all avaibable options for the four selectable drop down menus These options can be added to the unit or may have come from the factory Figure 1...

Page 7: ...ents the current value the offset given This screen is used for testing purposes to enable an operational state or to calibrate a sensor reading Figure 16 Calibration screen Note The Calibration scree...

Page 8: ...of the setpoint screens available from the Setpoints DB screen Figure 18 Cooling 1 setpoint These setpoints are all adjustable the sensor is NOT adjustable and is for information only Limits and safe...

Page 9: ...by writing to manual occ control point occ enable 24 7 operation runs continuously unit does not have an unoccupied mode unless the occupancy enable is changed S S switch on off signal control could b...

Page 10: ...recommend weekly schedules Leave the Date Range to NO Make sure to set the time to the hours for occupied schedule unless otherwise stated by customer 5 Click Save Schedule button on bottom of screen...

Page 11: ...ekly view or daily Misc status screen The Misc Setup screen can be accessed by selecting the Misc Setup link from the Unit Status screen The Misc Setup screen includes navigating buttons for BAS setup...

Page 12: ...t point by pressing the desired button A drop down menu will give you your choices 4 Press the button of your desired choice The select choice will appear on your button You may need to scroll by usin...

Page 13: ...upied condition and place unit in occupied mode for a set period of time adjustable 30 minutes default 7 Manual Ovrd Select to manually force Occupied or Unoccupied Mode Figure 25 Occupancy control Se...

Page 14: ...lures navigate to the Calibration screen by press the Setup link on the Home screen Now press the calibration link to display the Calibration screen Show all points Remember the unit will receive the...

Page 15: ...points are for the modulation of the supply fan speed The supply fan will modulate to maintain the setpoint Default is 3900 cfm The SF setpoint may need to be adjusted check with your TAB contractor...

Page 16: ...or the 10 minute countdown timer for the heating mode change over to cooling mode On the very bottom of the screen are links to other screens 6 Reheat HGRH screen The reheat displays that reheat is in...

Page 17: ...re links to other screens 8 Dehumidification 1 screen The first line has the status of the OAT and the dehum lower limit setpoint see SOO The OAT must be above the lower limit setpoint and the OADP mu...

Page 18: ...mer for the cooling mode change over to heating mode On the very bottom of the screen the type of heat is displayed You have completed the startup of the 100 Outside Air unit Before you leave make sur...

Page 19: ...should be set to no The rotary switch on the controller located in the upper left corner need to be set to the proper protocol 1 MSTP 2 ARCnet contact the FMOC for correct BACnet Device Instance numbe...

Page 20: ...ecords 3 low pressure start restart failure incidents within 1 hour compressor 1 is locked out and the controller will issue an alarm The compressor lock out can be reset in the EQ2 display pad or by...