background image

Password enter screen

There are 3 levels of passwords used in the

program, User, Admin and Factory passwords. User

passwords are not used often as most of those

screens are for READ OUT sensors and unit data.

Most changes will require an ADMIN PASSWORD

because these are specific configuration and are not

meant to be changed unless authorization has been

given. Once an ADMIN password has been entered

ALL screens and buttons below that level will not

need a password to be re-entered unless it requires

a Factory password. Factory password protected

changes that must be performed by an authorize

service tech, please contact the manufacturer's

technical service representative if assistance is

required. The password will timeout after 5 min of

screen inactivity and need to be reentered, when

this happens you will be brought back to the 

Unit

Status

 screen.

Note: 

You will need to switch the keyboard

input to numbers to enter the password.

Figure 5: Enter password

Table 1: Reference table for main screens.

Navigation

button

Description

Password

Reference

Unit status

Main settings and modification screen

None

Tech settings

Occupancy control, SF min setting, enable settings

Admin

Misc. setup

BAS, ModStat, config

Admin

Calibration

Allows /- of sensor readings – used for testing of unit and sensor

calibration

Admin

Unit config

Shows unit information, serial number, operational configuration, factory

options

Admin

Setpoints/DB

Adjustment to “adjustable” setpoints.

Note: 

Some setpoints/DBs are not adjustable from factory

Admin

Settings, controls, and options

Procedures for setting up the date and time,

schedule of occupancy, modifying parameters of

operation, and selectable options, such as adding

zone sensor and safety switches. For specific

operational information for this unit, refer to

the unit specific 

Sequence of Operations 

provided

separately.
The controller will be pre-configured from the

factory with the necessary options for the unit to

operate properly. However, some items may need

to be modified in the field as required. This can be

achieved in the field through the EQ2 display.

Unit status screen

From the 

Unit status

 screen, most of the status

screens can be accessed. Also, the alarm reset will

appear on the home screen if the controller is in an

alarm state. Once alarm is reset, the 

Reset Alarm

text will hide itself.

Quick Start Guide for Equipment Touch and LS-1628 Unit Controller, Standard 3.1.5 Program

3

Summary of Contents for LS-1628

Page 1: ...y terminals located on the bottom of the controller All output connections wire into the blue terminals located on top of the controller Refer to the wiring diagram included with the unit for the conn...

Page 2: ...nostic The Standby screen shows the program name version number date of revision issue and the current operational condition mode of the unit i e UNOCCUPIED SCHEDULE is the initial condition Press the...

Page 3: ...Tech settings Occupancy control SF min setting enable settings Admin Misc setup BAS ModStat config Admin Calibration Allows manual of sensor readings used for testing of unit and sensor calibration Ad...

Page 4: ...l light when the current sensor closes for compressor 1 HPS1 and LPS1 should always have the light on FRZ1 will light when the DXLAT1 sensor is below 38 F Clg Mode will be on when OAT is above 55 F an...

Page 5: ...occupancy control unit enable supply fan minimum run settings ZAT SAT reset on off emergency heat enable and many more Please refer to specific unit sequence of operation for specific run conditions...

Page 6: ...d a zone sensor if needed The following four charts show all avaibable options for the four selectable drop down menus These options can be added to the unit or may have come from the factory Figure 1...

Page 7: ...ents the current value the offset given This screen is used for testing purposes to enable an operational state or to calibrate a sensor reading Figure 16 Calibration screen Note The Calibration scree...

Page 8: ...of the setpoint screens available from the Setpoints DB screen Figure 18 Cooling 1 setpoint These setpoints are all adjustable the sensor is NOT adjustable and is for information only Limits and safe...

Page 9: ...by writing to manual occ control point occ enable 24 7 operation runs continuously unit does not have an unoccupied mode unless the occupancy enable is changed S S switch on off signal control could b...

Page 10: ...recommend weekly schedules Leave the Date Range to NO Make sure to set the time to the hours for occupied schedule unless otherwise stated by customer 5 Click Save Schedule button on bottom of screen...

Page 11: ...ekly view or daily Misc status screen The Misc Setup screen can be accessed by selecting the Misc Setup link from the Unit Status screen The Misc Setup screen includes navigating buttons for BAS setup...

Page 12: ...t point by pressing the desired button A drop down menu will give you your choices 4 Press the button of your desired choice The select choice will appear on your button You may need to scroll by usin...

Page 13: ...upied condition and place unit in occupied mode for a set period of time adjustable 30 minutes default 7 Manual Ovrd Select to manually force Occupied or Unoccupied Mode Figure 25 Occupancy control Se...

Page 14: ...lures navigate to the Calibration screen by press the Setup link on the Home screen Now press the calibration link to display the Calibration screen Show all points Remember the unit will receive the...

Page 15: ...points are for the modulation of the supply fan speed The supply fan will modulate to maintain the setpoint Default is 3900 cfm The SF setpoint may need to be adjusted check with your TAB contractor...

Page 16: ...or the 10 minute countdown timer for the heating mode change over to cooling mode On the very bottom of the screen are links to other screens 6 Reheat HGRH screen The reheat displays that reheat is in...

Page 17: ...re links to other screens 8 Dehumidification 1 screen The first line has the status of the OAT and the dehum lower limit setpoint see SOO The OAT must be above the lower limit setpoint and the OADP mu...

Page 18: ...mer for the cooling mode change over to heating mode On the very bottom of the screen the type of heat is displayed You have completed the startup of the 100 Outside Air unit Before you leave make sur...

Page 19: ...should be set to no The rotary switch on the controller located in the upper left corner need to be set to the proper protocol 1 MSTP 2 ARCnet contact the FMOC for correct BACnet Device Instance numbe...

Page 20: ...ecords 3 low pressure start restart failure incidents within 1 hour compressor 1 is locked out and the controller will issue an alarm The compressor lock out can be reset in the EQ2 display pad or by...

Reviews: