Figure 26: Module status screen
BACnet device
From the
Home
screen, press the
Setup
button,
then press the
Misc. Status
button to get to the
Misc. Status
screen. Press the
BAS Setup
button to
enter the BAS Setup screen. Select
Communication
menu option, this will open the communication
screen and allow you to enter BAS information.
The
BACnet Device Instance
being utilized in the
field will be unique for each unit. The Autogenerate
Device ID should be set to
no
. The rotary switch
on the controller, located in the upper left corner,
need to be set to the proper protocol (1=MSTP,
2=ARCnet) contact the FMOC for correct BACnet
Device Instance number and protocol. The BACnet
Device instance could already be populated always
check to verify correct number.
Network router and IP screens
The router and IP network number can be checked
and manually changed by using the related menus.
To access the
Router
screen, select
Router
on the
BAS screen. To access the
IP
screen select
IP
on the
BAS screen.
Quick Start Guide for Equipment Touch and LS-1628 Unit Controller, Standard 3.1.5 Program
19