16 Alarms
Alarm
code
Displayed message
Reset
Delay
Relè
Action
ALA01
Sensor B1 broken or disconnected
Automatic
60 sec
yes
Stop the machine
ALA02
Sensor B2 broken or disconnected
Automatic
60 sec
yes
If present geothermal modulating pump it is
set at the top speed
ALA03
SensorB3 broken or disconnected
Automatic
60 sec
yes
It stops the regulation of the domestic circuit
ALA04
Sensor B4 broken or disconnected
Automatic
60 sec
yes
Stop the machine
ALA05
Sensor B5 broken or disconnected
Automatic
60 sec
yes
Stop the pump of solar collector
ALA06
Sensor B6 broken or disconnected
Automatic
60 sec
yes
Stop the functions enabled by the external
sensor
ALA07
Sensor B7 broken or disconnected
Automatic
60 sec
yes
Stop the machine
ALA08
Sensor B8 broken or disconnected
Automatic
60 sec
yes
Stop the pump of solar collector
ALA09
Sensor B9 broken or disconnected
Automatic
60 sec
yes
If compressor Siam it stops the compr.
ALA10
Sensor B10 broken or disconnected
Automatic
60 sec
yes
If present electronic expansion valve stop
the machine
ALA11
Sensor B11 broken or disconnected
Automatic
60 sec
yes
Stop the machine
ALA12
Ssensor B12 broken or disconnected
Automatic
60 sec
yes
Stop the machine
ALB01
Position ID3 high pressure
Manual
Immediate
yes
Stop the machine
ALB02
High pressure compressor 1 from
transducer
Manual
Immediate
yes
Stop the machine
ALB03
Low compressor/s pressure from
transducer
Automatic (par.
Hc05)
At starting: 40s (par.
Hc03) at regime: 10s
(par. Hc04)
yes
Stop the machine
ALC01
Position: ID2 Thermic compressor 1 or
inverter alarm
Manual
Immediate
yes
If 1 comp. enabled: stop the machine
If 2 comp. enabled: stop comp.1 (if comp. 2
available)
ALC02
Position: ID9 Thermic compressor 2
Manual
Immediate
yes
Stop comp.2 (if comp. 1 available)
ALC03
Envelope alarm
0: Max.rapp.compr.
1: Max.press.discharge
2: Current limit
3: Max.press.asp
4: Min.rapp.compr.
5: Min.diff.pressure.
6: Min.press.discharge
7: Min. press.asp.
Compressor turned off for operation out
envelope (just with compressor Siam)
Manual
60 sec (par. H1b14)
yes
Stop the compressor
ALC04
Alarms failed compressor ignition
(just with compressor Siam)
After 5 times per
hour it becomes
manual
60 sec (par. H1b11)
yes
Stop the compressor
ALC05
Max.tdischarge time (just with
compressor Siam)
After 3 times per
hour it becomes
manual
Immediate
yes
Stop the compressor
ALC06
Delta pressure < minimum required for
compr. oil return (just with compressor
Siam)
Automatic
120 sec (par. H1b12)
yes
Stop the compressor