21
www.templari.com
•
Example 2 condensate drain
•
Example 3 condensate drain with condensate drain element
The condensation water accumulated during the operation must be
carried away without it can freeze. To ensure the correct outflow the
heat pump must be in a horizontal position. The condensation water
pipe must have a minimum diametre of 18mm and must flow in the
drain channel without it can freeze. Don’t discharge the condensate
directly into purification basins and moats. The aggressive fumes
and the condensation pipe, if it isn’t protected against frost, can
cause irreparable damages to the evaporator.
In places where there are snowfalls, install the heat pump at least 25
cm from the floor to avoid clogging in the suction and condensate
drain area.
Frost proof
depth
min 250mm
Frost
proof
depth
6.7 Alignment of the heat pump KITA
Templari®
Put horizontally the heat pump
KITA Templari® so that the
condensate can flow. The product must be installed with
amortized feet, purchased separately. The amortized feet
increase the height of the product, facilitating the flow of
condensate and reducing vibrations.
6.8 Probe installation
All probe used for the operation of the plant must be installed
properly in the appropriate wells using a suitable thermal paste.
WARNINGS!
Installing the probes not in a proper way will voids the warranty.
7 Hydraulic connections
7.1 Equipment control
1
Insulate wires (even underground) between product and
heating system con un isolamento resistente ai raggi UV e
alle alte temperature.
2
To avoid the transmission of vibrations on adjacent
buildings, use connection lines to product with a lenght of
at least 0,75 m.
3
If the product isn’t installed in the hightest point of heating
circuit, install then in a suitable point some additional vent
valves.
4
Remove the covers (3) from the hydraulic fittings of the
circuit.
5
Install in the return of the heating circuit, between two
shut-off valves, an anti-dirty filter to clean at regular
intervals.
6
Install a fexible pipe (1) e (6) (to be made on site) with a
gasket and a closing valve in the discharge fittings and the
riturn of the heating circuit of the heat pump.
7
Control the connection seal.