12.6 Main menu
To enter the menu press the button
.
Press the buttons and to navigate manus. At the end of
operations, press
to come back to the main screen.
Here below the 8 menus:
A.
On-Off unit
B.
Setpoint
C.
Watch/Time table
D.
Inputs/Outputs
E.
Alarm history
F.
Board change
G.
Assistance
H.
Manufacturer
12.7 ON-OFF menu
On/Off Unit A01
Unit Heat-pump
OFF
SUMMER
Mask A01:
it permits to set the condition and the
operation mode. The state OFF set in this menu is always
conditioned (ex. antifreeze operation).
MasK A02:
It turns off without conditions the pump for
a certain period of time. Expired the time the function A01 is
rehabilitate.
12.8 SETPOINT menu
Thermoregulation Unit B01
Temp.HP
Setpoint nominal
(ON)
Cooling:
12.0°C
Heating:
35.0°C
DHW:
60.0°C
Mask B01:
Variations of nominal setpoint.
Mask B02:
Variations of Energy saving setpoint. We
suggest the use of the Energy saving during the night or during
long absences from home. To reduce the consumption of the
unit we suggest to use the climatic curve instead of setting the
Setpoint, because it permits a continuous flow.
Mask B03: it permits to activate the program of anti-legionella
cycles. For the setpoint we suggest 70°C as per manufacturer
data.
MasK B05:
it permits the choice of fan operation mode.
It is possible to chose between the following conditions:
•
POWERFULL: it is the most efficient condition, that also
involves the noisiness of the greater fan.
•
NORMAL: it is the condition of operation set by the
manufacturer, it permits a very good compromise between
efficiency and noisiness.
•
QUIET1 - QUIET2 - SILENT: in these conditions of operation
the fan is slowed down respectively of 10, 15, 20
percentage points. Those conditions permit to work with
a noisiness more and more reduced. We underline that
setting this function the efficiency of the machine too is
progressively reduced.
Mask B06:
Only in AIR version. Automatic Mode Change
to pass from cooling mode to heating mode defining a confort
zone in which neither mode is active. To activate the function
the difference between the cooling and heating setpoint has
to be equal to Delta Confort. It also allows to set the operation
mode of the internal fan. The internal fan can follow the
request (compressor speed) low medium or high or control the
condensation.
Mask B07:
Authomatic Season End. You have to set the
daily average temperature above which the heating function
turns off and the daily average temperature below which the
heating function turns on; if present the domestic function stay
active.
•
En. autoswitch: activate and deactivate the function.
•
HP disable Ext. T.: the daily average temperature above
which the heating function turns off
•
HP enable Ext. T.: the daily average temperature below
which the heating function turns on.
•
Average Ext. T.: the actual daily average temperature.
Mask B08:
Optimizer management. The optimizer is
an algorithm that allows to store energy using the thermal inertia
of the building when the conditions are more favorable.
•
Active optimizer: it activates or deactivates the
function.
•
Final Setpoint : it shows the reference value of the heat
pump including the Delta Optimizer.
•
Delta Optimizer: it shows the delta (positive or
negative) due to optimization algorithm.
•
Influence: it sets the minimum value (delta negative)
and maximum (delta positive). This function is needed
to limit the influence of optimizer if necessary.
Mask B09:
it allows to set a hysteresis in shutdown. Once
reached the Setpoint the machine, instead of turn off, continue
operating at minimum until reaching this target on setpoint set
up. If in the meanwhile the request increases again (ex. request
from the domestic) the compressor come back to the operating
regime required.