7.8 Scheme 4: Cooling/heating system and DHW with buffer.
PROBE B7
PROBE B4
GA
GA
RD
MA
USER INTERFACE
PROBE
B2
PROBE
B3
COLLECTOR
FY
VE
VE
RD
3W
UE
SIGNAL CABLES
OUT
IN
GA
MA
RD
3W
VE
FY
UE
An�-vibra�on joint
Manometer
Drin tap
3 way valve
Expansion vessel
Y-filter
External unit
DHW
DW
In this configuration, you MUST always keep open at least 25% of the collector area.
The bypass valve must have a broad scope to ensure the proper operation of the heat pump when the radiant system allows little
water passage.
ATTENZIONE!
Build a plant with buffer on outlet pipe is the least effective method and, although you can use it, we do not recommend its use.
The buffer used on outlet pipe must always comply with a minimum quantity of liters according to the heat pump KITA used:
KITA S 200 Liters, KITA M 300 Liters, KITA L 500 Liters