background image

- 2 -

R

EF

R

IGE

R

A

TI

O

N

 S

Y

S

TE

M

W

IR

ING

3. REFRIGERATION SYSTEM

3.1 General

The OPA 465-960 has two independent refrigeration 

circuits and two compressors to provide the flexibility 

and economy of two stage operation, i.e. utilising one 

or two circuits as conditions vary, plus the advantage of 

staggered starting, one stage being digital for improved 

control and system efficiency.
Each refrigeration system has been charged with 

HFC-410A (R410A) refrigerant; refer wiring diagram 

specification table for amount. ECO machines are 

supplied with a mini PDG service interface tool fitted for 

ease of service, maintenance and trouble shooting.
This charge is based on nominal capacity, nominal 

conditions and nominal airflow and is sufficient under 

these conditions to maintain a refrigerant superheat 

of approximately 6 Kelvin. If the unit is installed in 

subtropical or tropical conditions, has a high fresh air 

content or has been installed with maximum supply  

air quantity, the superheat should be checked and if 

found to be above 6 Kelvin, refrigerant may need to 

be added to the system to return the superheat  to the 

factory required state. 

These readings should be taken with each stage 

operating independently and after the  

space has achieved conditions. The additional charge 

should be recorded for future reference.

3.2 Compressors

The compressors are directional scroll type. The 

compressor lubricant is polyolester oil (POE). Note, this 

oil absorbs moisture quickly if exposed to open air.
On commissioning, the compressors must be checked 

for correct rotation (refer Start Up Procedure). A 

time delay prevents simultaneous starting of the 

compressors.

3.3 Economiser 

(Option) - ECO Plus Version

If the outdoor air temperature or heat content preferably, 

is below that of the return air the fresh air damper opens 

and the return air damper closes to provide the first 

stage of cooling. The fresh air damper should return 

to minimum setting and the return air damper open 

before the compressors  are allowed to operate to 

provide further cooling. A low limit thermostat is fitted to 

prevent compressors operating with a mixed air-on coil 

temperature below 18°C; resets at 20°C. This is by-

passed during heating mode.

4. WIRING

4.1  Electrical Requirements

Electrical work must be done by a qualified electrician.

  DANGER LIVE ELECTRICAL CONNECTIONS. ONLY QUALIFIED 

PERSONS WHO ARE COMPETENTLY TRAINED SHOULD 

PERFORM SERVICE AND MAINTENANCE TASKS.

The outdoor unit must be wired directly from a 

distribution board by means of a circuit breaker or 

H.R.C. fuse, and a mains isolator provided - preferably 

close to the unit.
Note: DO NOT USE REWIRABLE FUSES.
The OPA ECO is provided with a 24VAC control circuit 

thermostat (TZT Optional), on/off switch and/or time 

clock, field supplied and fitted. The control transformer 

240V primary is used for countries with 230-240V 

power supply. Alternatively control can be via a Modbus 

connection.
For countries with supply voltages 200-220V, change 

the primary voltage on the transformer to 208V.
Standard units are suitable for use with thermostats 

with either manual Heat/Cool selection or automatic 

changeover subject to the contact ratings of the 

thermostats.
A 24 hour power supply to the compressor crank case 

heaters is required, otherwise the warranty is void.
4.2 Unit Controller (UC6)
The temperzone Unit Controller 6 (UC6) is the 

successor to the OUC4 controller. The UC6 provides 

increased capability and flexibility in indoor-, outdoor- 

and packaged units. The complete controller combines 

the µPC controller board from Carel plus an interface 

board to connect temperzone standard sensors and 

plugs. The UC6 receives requests such as “Unit On/Off”, 

“Start 1 or 2 compressors”, “Activate HEAT (Reverse 

Cycle)” and transfers these requests to the outputs after 

enforcing safety timers. The UC6 ensures unit safety by

 continuously monitoring input signals such as pressures 

and temperatures. Beside the normal controls and unit 

safety the UC6 has many other functions, for example 

head pressure control, capacity control, superheat 

control, serial communications and more.
The Unit Controller provides system protection functions 

such as coil frost protection, de-icing, high head pressure 

and low suction pressure cut-out. It also protects against 

rapid cycling of the compressor(s) and loss of refrigerant. 

The UC6 regulates the superheat of the refrigeration 

system by controlling the position of an electronic 

expansion valve (EEV). Various methods of head 

pressure control (or limiting) are employed in temperzone 

units. The particular method used varies from model 

to model, but is also handled by the Unit Controller. 

In combination, these features deliver optimised 

performance across a wide operating temperature range.
As a result of the UC6’s control of these inter-related 

functions, the outdoor fans may take some time to start 

rotating after each compressor start. They may also run 

on when the compressor stops. The fans will stop during 

a de-ice cycle and the speed will vary either smoothly, 

or in steps, in order to protect against excessively low or 

high head pressure.
Refer to temperzone for operation & fault diagnostics 

information OR 

www.temperzone.biz

.

Summary of Contents for OPA 465RKTG-P

Page 1: ...supplied with the unit Flexible duct connections are recommended between the supply and return ducts and the unit Unit is shipped with wooden blocks installed under the compressors Ensure these blocks are removed from the compressor feet prior to starting the unit not required for operation Factory filter slides are fitted access to the filter access door should be considered when designing return...

Page 2: ...stribution board by means of a circuit breaker or H R C fuse and a mains isolator provided preferably close to the unit Note DO NOT USE REWIRABLE FUSES The OPA ECO is provided with a 24VAC control circuit thermostat TZT Optional on off switch and or time clock field supplied and fitted The control transformer 240V primary is used for countries with 230 240V power supply Alternatively control can b...

Page 3: ...f all electrical connections and sign the check label 10 Touch up any outdoor unit paintwork damage to prevent corrosion 5 3 Commissioning EC Plug Fans Six Keys service interface function description 1 Alarm Press Alarm button to access alarm operation a View the active alarm b Logger alarm data 2 Prg Press program button enter to main menu 3 Esc Return to menu s previous level 4 Enter Press the E...

Page 4: ...e system has an adequate amount of refrigerant Signals used for this check are mid coil temperatures TS1 TS2 suction temperatures ST1 ST2 and discharge line pressures HP1 and HP2 if present The check is not made during the first 5 minutes after a compressor is started to allow pressures and temperatures to settle If the compressor is a variable speed type or a digital scroll type then the check is...

Page 5: ... communications port then an alarm is generated Examples of such devices are a TZT 100 thermostat a Carel Power inverter Display indication for communications fault letter C flashing 7 TEST MODE Test mode can only be activated when both compressors are OFF To start test mode press and hold down the push button on the lower board between 1 and 5 seconds In test mode each output is activated for 5 t...

Page 6: ...00 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 2500 NOMINAL 9V 8V 7V 5V 6V 4 0 2 0 1 2 0 8 4 6 4 0 0 6 2 6 1 5 0 8 1500 2000 2500 3000 3500 4000 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 Nominal 500 8V 7V 9V 10V 6V 2 3 1 5 1 0 3 5 2 5 1 1 3 4 0 6 0 7 1 7 3000 3500 4000 4500 5000 0 100 200 300 AIR FLOW l s AVAILABLE EXT...

Page 7: ...If on the other hand a TZT with Modbus is used the installing contractor will see the label and wires and then wire them to the 24 volt terminals RS485 Terminal on UC6 Lower Board Connections Serial Card BMS TZT Controller Installation If a TZT100 controller is used in Modbus format these cables should be wired to the following terminals on the low voltage input terminal strip 24V Hot terminal to ...

Page 8: ...Check system operating pressures and history using PDG mini service interface tool fitted to all ECO machines 12 2 Three Monthly or every 1200 hrs of operation Check the indoor unit s indoor EC motor and plug fan operation and adjust if necessary using PDG mini service interface tool fitted to all ECO machines 12 3 Six Monthly 1 Check the tightness of electrical connections 2 Check the tightness o...

Page 9: ...nditioning heat hump unit seems to work properly Many new buildings especially a commercial buildings have a large amount of concrete and other structural materials that are generally cold and full of moisture This is most evident in the winter when trying to heat the building from scratch 13 5 Unit is leaking water Check the drain trap vent slope before moving on to Water carry over Reduce the ma...

Page 10: ... 10 OPA 465RKTG P ...

Page 11: ... 11 OPA 550RKTG P ...

Page 12: ... 12 OPA 705RKTG P ...

Page 13: ... 13 OPA 800RKTG P ...

Page 14: ... 14 OPA 855RKTG P ...

Page 15: ...OPA 960RKTG P ...

Page 16: ...uritius Bangalore Bangkok Hanoi Cambodia South Pacific Islands Bangladesh temperzone australia pty ltd Head Office Sydney 14 Carnegie Place Blacktown PO Box 6448 Delivery Centre Blacktown NSW 2148 Australia Email sales temperzone com au www temperzone biz Sydney 02 8822 5700 Brisbane 07 3308 8333 Melbourne 03 8769 7600 Adelaide 08 8115 2111 Perth 08 6399 5900 Townsville 07 4774 3506 Launceston 03 ...

Reviews: