background image

- 4 -

O

P

E

R

A

TIO

N

6. OPERATION

6.1  Remote on/off

The remote on/off function can be enabled or disabled 

by using a UC6 service tool.
When the function is enabled the remote on/off signal 

must connect to input DI7, signal return is DIC1. The 

remote on/off signal must be an external voltage free 

switched relay contact.
The unit is active when DI7 is connected to DIC1.

6.2  Variable duty units

The UC6 can control a unit where one of the two 

compressors is a variable speed compressor or a digital 

scroll compressor. Temperzone pre-configures the unit 

to the correct compressor type; a UC6 service tool is 

required if the compressor type configuration must be 

changed.
The capacity input signal must connect to input CS (0-

1V, duty 10% per 0.1V).
For digital scroll compressors the capacity output signal 

(compressor modulating valve control signal) is on 

output CCS.
The minimum compressor duty is: 

 

 20 to 30% for a variable speed compressor 

(depends on compressor model)

 

16% for a digital scroll compressor

When a capacity signal is present on input CS that is 

lower than the minimum duty (for example 0.0V) then the 

compressor will continue to operate on minimum duty. 

Safety functions may place further restrictions on the 

minimum duty and may act at any operating condition.

6.3  High pressure protection (HP)

If high pressure transducers are connected to inputs 

HP1 and HP2 then a compressor is switched off when 

the discharge line pressure reading exceeds 42.0bar.
Instead of high pressure transducers some systems 

may be fitted with high pressure switches. These also 

connect to inputs HP1 and HP2. When a high pressure 

switch activates (electrical circuit opens) the compressor 

is stopped.
Similarly, if the condensing temperature reported by an 

outdoor coil temperature sensor (connected to TS1 and 

TS2) reports a coil temperature above +66°C (cooling 

mode) the compressor is switched off.
The UC6 will automatically reduce capacity of a digital 

scroll compressor before the maximum value of 42bar / 

66°C is reached.
When a compressor is stopped due to high pressure 

it is held off for a period of 3 minutes, after which it is 

allowed to restart (provided pressure has fallen well 

below the maximum).
If three consecutive trips occur then the unit will be 

“locked out”. The trip counter is reset to 0 when there 

has been no compressor run request for longer than 60 

minutes.
Display indication when protection is active -  

number 4 (flashing)

6.4  Loss of refrigerant protection (LOR)

When a compressor is running the UC6 continuously 

monitors the various temperatures. The controller 

software applies logic that enables it to determine 

whether the system has an adequate amount of 

refrigerant. Signals used for this check are mid-coil 

temperatures (TS1TS2), suction temperatures (ST1

ST2 and discharge line pressures (HP1 and HP2, if 

present).
The check is not made during the first 5 minutes 

after a compressor is started to allow pressures and 

temperatures to settle.
If the compressor is a variable speed type or a digital 

scroll type then the check is made only when the 

capacity is at 100%.
When a compressor is stopped due to loss of refrigerant 

it is held off for a period of 3 minutes, after which it is 

allowed to restart.
If three consecutive trips occur then the unit will be 

“locked out”. The trip counter is reset to 0 when there 

has been no compressor run request for longer than 60 

minutes.
Display indication when protection is active -  

number 3 (flashing)

6.5  Indoor coil frost protection (FROST)

When the unit is cooling the evaporating temperature 

in the indoor coil must remain above -10°C (adjustable 

from -10°C to -2°C by using a UC6 service tool). If this 

temperature falls below the threshold then some amount 

of ice (frost) is likely to have formed on the indoor coil.
When indoor coil frost protection is activated the 

compressor is stopped for 15 minutes, after which it is 

allowed to restart.
If three consecutive trips occur then the unit will be 

“locked out”. The trip counter is reset to 0 when there 

has been no compressor run request for longer than 60 

minutes.
Display indication when protection is active -  

number 7 (flashing)

6.6  High discharge line temperature protection (HDT)

The controller monitors the discharge line temperature 

(inputs DT1DT2) and should it rise above 110°C the 

compressor will be stopped.
When high temperature protection is activated the 

compressor is stopped for at least 3 minutes. The 

compressor is allowed to restart after 3 minutes 

provided that the discharge line temperature has fallen 

to below 100°C.
If three consecutive trips occur then the unit will be 

“locked out”. The trip counter is reset to 0 when there 

has been no compressor run request for longer than 60 

minutes.
Units with a variable compressor or digital scroll 

compressor will automatically reduce capacity before 

the discharge temperature rises close to the threshold.
Display indication when protection is active -  

number 9 (flashing)

6.7  Compressor lock-out

Certain faults (as outlined in the preceding paragraphs) 

can cause the unit to be “locked out” if they occur 

three consecutive times while the compressor-run 

request has remained active. When a unit is locked out 

the compressor is not allowed to start until the lock-

out is manually reset. Lock-out protects the unit from 

repeatedly starting the compressor when a serious fault 

exists that requires the attention of a service technician.
When a unit is locked out the alarm relay output (NO7

NC7) will be active.

Summary of Contents for OPA 465RKTG-P

Page 1: ...supplied with the unit Flexible duct connections are recommended between the supply and return ducts and the unit Unit is shipped with wooden blocks installed under the compressors Ensure these blocks are removed from the compressor feet prior to starting the unit not required for operation Factory filter slides are fitted access to the filter access door should be considered when designing return...

Page 2: ...stribution board by means of a circuit breaker or H R C fuse and a mains isolator provided preferably close to the unit Note DO NOT USE REWIRABLE FUSES The OPA ECO is provided with a 24VAC control circuit thermostat TZT Optional on off switch and or time clock field supplied and fitted The control transformer 240V primary is used for countries with 230 240V power supply Alternatively control can b...

Page 3: ...f all electrical connections and sign the check label 10 Touch up any outdoor unit paintwork damage to prevent corrosion 5 3 Commissioning EC Plug Fans Six Keys service interface function description 1 Alarm Press Alarm button to access alarm operation a View the active alarm b Logger alarm data 2 Prg Press program button enter to main menu 3 Esc Return to menu s previous level 4 Enter Press the E...

Page 4: ...e system has an adequate amount of refrigerant Signals used for this check are mid coil temperatures TS1 TS2 suction temperatures ST1 ST2 and discharge line pressures HP1 and HP2 if present The check is not made during the first 5 minutes after a compressor is started to allow pressures and temperatures to settle If the compressor is a variable speed type or a digital scroll type then the check is...

Page 5: ... communications port then an alarm is generated Examples of such devices are a TZT 100 thermostat a Carel Power inverter Display indication for communications fault letter C flashing 7 TEST MODE Test mode can only be activated when both compressors are OFF To start test mode press and hold down the push button on the lower board between 1 and 5 seconds In test mode each output is activated for 5 t...

Page 6: ...00 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 2500 NOMINAL 9V 8V 7V 5V 6V 4 0 2 0 1 2 0 8 4 6 4 0 0 6 2 6 1 5 0 8 1500 2000 2500 3000 3500 4000 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 Nominal 500 8V 7V 9V 10V 6V 2 3 1 5 1 0 3 5 2 5 1 1 3 4 0 6 0 7 1 7 3000 3500 4000 4500 5000 0 100 200 300 AIR FLOW l s AVAILABLE EXT...

Page 7: ...If on the other hand a TZT with Modbus is used the installing contractor will see the label and wires and then wire them to the 24 volt terminals RS485 Terminal on UC6 Lower Board Connections Serial Card BMS TZT Controller Installation If a TZT100 controller is used in Modbus format these cables should be wired to the following terminals on the low voltage input terminal strip 24V Hot terminal to ...

Page 8: ...Check system operating pressures and history using PDG mini service interface tool fitted to all ECO machines 12 2 Three Monthly or every 1200 hrs of operation Check the indoor unit s indoor EC motor and plug fan operation and adjust if necessary using PDG mini service interface tool fitted to all ECO machines 12 3 Six Monthly 1 Check the tightness of electrical connections 2 Check the tightness o...

Page 9: ...nditioning heat hump unit seems to work properly Many new buildings especially a commercial buildings have a large amount of concrete and other structural materials that are generally cold and full of moisture This is most evident in the winter when trying to heat the building from scratch 13 5 Unit is leaking water Check the drain trap vent slope before moving on to Water carry over Reduce the ma...

Page 10: ... 10 OPA 465RKTG P ...

Page 11: ... 11 OPA 550RKTG P ...

Page 12: ... 12 OPA 705RKTG P ...

Page 13: ... 13 OPA 800RKTG P ...

Page 14: ... 14 OPA 855RKTG P ...

Page 15: ...OPA 960RKTG P ...

Page 16: ...uritius Bangalore Bangkok Hanoi Cambodia South Pacific Islands Bangladesh temperzone australia pty ltd Head Office Sydney 14 Carnegie Place Blacktown PO Box 6448 Delivery Centre Blacktown NSW 2148 Australia Email sales temperzone com au www temperzone biz Sydney 02 8822 5700 Brisbane 07 3308 8333 Melbourne 03 8769 7600 Adelaide 08 8115 2111 Perth 08 6399 5900 Townsville 07 4774 3506 Launceston 03 ...

Reviews: