background image

- 9 -

APPENDIX I 
PROTECTION FUNCTIONS

The UC8 implements system protection functions such as 

indoor coil frost, extreme high and low pressures, rapid on-

off cycling of the compressors, loss of refrigerant and more.
The following applies to all protection functions except 

where otherwise indicated:
Unit operating capacity may automatically be reduced 

before a protection function is activated. Such a reduction 

may be sufficient to prevent an actual trip from occurring.
When a compressor is stopped by a protection function it is 

held off for a period of 3 minutes, after which it is allowed to 

restart (provided the cause of the trip has cleared).
When a protection function is active and when a unit is 

locked out the alarm relay output “FLT” is active.
More detailed information about protection functions and 

troubleshooting refer to document “UC8 troubleshooting 

information”, available for free download from the 

temperzone internet website.

High pressure protection (HP) 

OPA Econex units are fitted with high pressure transducers 

connected to UC8 input HPT. A compressor is switched 

off when the discharge line pressure reading exceeds 

4151 kPa.
The display shows the letters ‘HP’ when protection is 

active.

Low pressure protection (LP)

OPA Econex units are fitted with low pressure transducers 

connected to UC8 input LPT. A compressor is switched off 

when the suction line pressure reading falls below 228 kPa.
The display shows the letters ‘LP’ when  

protection is active.

Indoor coil frost protection

When the unit is cooling the evaporating temperature in the 

indoor coil should remain above -8°C. If this temperature 

falls below -8°C then ice (frost) likely will form on the 

indoor coil. If the low temperature persists for longer than 6 

minutes then the protection function activates.
When indoor coil frost protection is 

activated the compressor is stopped for 6 

minutes, after which it is allowed to restart.

High discharge line temperature protection

The controller monitors the compressor discharge line 

temperature via a sensor connected to input ‘DL’ (red wires). 

The compressor is stopped when:
• The temperature rises above 115°C for longer than 15 

minutes.
• The temperature rises above 125°C  for longer than 2 

minutes.
The display shows the message ‘Hi-t’ when 

protection is active.

High discharge superheat protection

Discharge superheat is defined as the difference between 

the compressor discharge gas temperature and the 

condensing temperature. When this temperature differential 

becomes very high it is an indication that the compressor 

is being starved of refrigerant gas. Common reasons for 

this could be a lack of refrigerant (under-charged or loss-

of-charge) or a problem with the expansion device (for 

example a stuck accurator or loose wiring to an EEV).
The protection is activated when discharge superheat 

exceeds 45K for longer than 30 minutes.
The display shows the message ‘Hi-dSH’ 

when protection is active.

Low discharge superheat protection

Discharge superheat is defined as the difference between 

the compressor discharge gas temperature and the 

condensing temperature. When this temperature differential 

stays very low it can be an indication that the compressor 

is being flooded with liquid refrigerant. Common reasons 

for this could be an excess of refrigerant (over-charged) or 

a problem with the expansion device (for example a stuck 

accurator or loose wiring to an EEV).
The protection is activated when discharge superheat 

remains below the threshold for longer than 15 minutes. 

The threshold varies linearly from 0K at standard mode 

minimum capacity (40%) to 10K at nominal capacity (100%).
This protection function is disabled when a compressor 

operates at less than standard mode minimum capacity (< 

40%).
The threshold for a variable speed compressor operated in 

boost mode (capacity above 100%) is fixed at 10K.
The display shows the message  

‘LO-dSH’ when protection is active.

High evaporation temperature / high suction line

 

temperature protection

When the unit has a low pressure transducer connected to 

the compressor suction line then the controller calculates 

the evaporating temperature from the suction line pressure 

reading. If the unit does not have a low pressure transducer 

then the controller finds the evaporating temperature 

via a coil temperature sensor (input IC when the unit is 

cooling, input OC when the unit is heating, blue wires). 

Additionally the controller monitors the compressor suction 

line temperature via a sensor connected to input ‘SL’ (white 

wires).
The protection function stops the compressor when:
• The evaporating temperature remains above 27.5°C for 

longer than 15 minutes.

• The suction line temperature remains above 30°C for 

longer than 15 minutes.

The display shows the message ‘Hi-SL’ 

when protection is active.

Other alarms

The controller performs many other protection functions. 

For example:
• Signals from sensors and transducers must remain inside 

normal operating range.

• Modbus RTU communications with connected devices 

(e.g. TZT-100 or SAT-3 thermostat, a Carel Power+ 

inverter) must continue uninterrupted.

• Modbus RTU communications with a controller such 

as a BMS that is controlling the unit must continue 

uninterrupted.

Refer to document ‘UC8 Troubleshooting Guide’ for details.

Summary of Contents for Econex OPA 250RLTFP

Page 1: ...well ventilated space If the refrigerant gas comes into contact with fire a poisonous gas may occur Be aware that R32 does not contain an odour If indoors the appliance shall be stored in a room away...

Page 2: ...eparate drain tray beneath the unit could be used to drain condensate to a suitable drainage point Condensate drains should be U trapped outside the unit The trap should have a vertical height of at l...

Page 3: ...llows DIP switch 2 ON Equipment type Heat Pump DIP switch 3 OFF Equipment stages One DIP switch 4 ON Reverse cycle valve on Heating SAT 3 Refer SAT 3 Installation Set up Guide page 3 4 4 Communication...

Page 4: ...emperzone biz model search UC8 or com website 4 10 Setting the UC8 Modbus device address To view or change the Modbus device address of a UC8 follow these steps Power up the unit but leave the compres...

Page 5: ...er 2 Start compressor in Cooling mode 3 Check the outdoor fan motor runs smoothly Note The outdoor fan does not necessarily start rotating immediately after the compressor is started The fans may run...

Page 6: ...signals and transfers the signals to the outputs after enforcing safety timers and other protection functions If the compressor is held off or held on by a safety timer then the display shows message...

Page 7: ...door coil This usually means reversing the cycle for a few minutes during which time there is no heating and in fact a little cooling can occur 8 4 In a new building why does it take some days before...

Page 8: ...t 6K Compressor discharge line pressure kPa dLP Discharge line pressure 2447 kPa Condensing temperature C Ct Condensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temp...

Page 9: ...indication that the compressor is being starved of refrigerant gas Common reasons for this could be a lack of refrigerant under charged or loss of charge or a problem with the expansion device for exa...

Page 10: ...ked out the compressor is not allowed to start Lock out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician T...

Page 11: ...3 4 1 1 INPUT kW 2 5 1 5 0 5 2 0 1 0 3 0 3 5 Amps 500 1000 1500 2000 2500 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 0 NOMINAL INPUT kW 3 0 2 0 1 0 2 5 1 5...

Page 12: ...st IMPORTANT Digital compressors must be operating at 100 for at least 10 minutes when taking these readings System 1 Cool Cycle Low Pressure SLP kPa Outdoor Ambient temperature C Evap temperature Et...

Reviews: