TemperZone Econex OPA 250RLTFP Installation & Maintenance Download Page 4

- 4 -

4.7  Unit Controller (UC8)

The unit’s UC8 controller receives requests such as ‘Unit 

On/Off’, ‘Start compressors’, ‘Activate HEAT (Reverse 

Cycle)’ and transfer the requests to the outputs after 

enforcing safety timers.
Figure 4. UC8 Controller

The Unit Controller provides several system protection 

functions. These are covered in Appendix I (p.9).
For additional information, refer to the UC8 Controller label 

on the unit or www.temperzone.biz for operation & fault 

diagnostics information; model search ‘UC8’.

References available:

UC8 Operation Manual : Air-to-Air Units

UC8 Fault & Display Messages (as per unit label)

UC8 Quick Reference and Operation Fault Diagnosis

UC8 Troubleshooting Guide

UC8 Modbus Communications

UC8 BACnet Communications

UC8 Master-Slave Connection

4.8  Control using switched and 0-10V signals

An external controller that provides 24V AC switched 

signals or has a set of voltage-free relay contacts should 

be connected as per the diagram below. UC8 inputs ‘VF’ 

and ‘VC’ will accept a 0-10V capacity control signals. If no 

capacity control signal is available then link UC8 terminals 

VF’ and ‘5’ and ‘VC’ and ‘12’. 

BMS / external controller

Capacity

UC8

0-10V 0V

HIGH

MEDIUM

LOW

COMP2

COMP1

HEA

T

HI ME LO C1

CP HT C2

12 VC 0V

24V AC  or  12V DC

24V AC COM  or  0V

5 VF 0V

0-10V 0V

Comp.

Fan

4.9  Control via Modbus RTU communications

OPA Econex units can be fully monitored and controlled via 

Modbus RTU serial communications.  

The following is typical for most installations:
• Set DIP switches 11 and 12 to OFF on all UC8 controllers.
• Connect BMS terminal A / TX+ to terminal A1 on the  

UC8 controller via terminal block shown.

• Connect BMS terminal B / TX-  to terminal B1 on the  

UC8 controller via terminal block shown.

Multiple OPA units can be daisy-chained together. 

For detailed information about monitoring and control 

via Modbus RTU refer to document ‘UC8 Modbus 

communications’, available at www.temperzone.biz (model 

search ‘UC8’) or .com website.

4.10  Setting the UC8 Modbus device address

To view or change the Modbus device address of a UC8 

follow these steps:
• Power up the unit but leave the compressors off.
• Hold down the SW3 pushbutton on the UC8 circuit board 

until the display shows:  

‘0’ [release]   ‘1’   short press to ‘2,’ [long press]   A,  

[long press]

• The display will show the current Modbus device address. 

The factory default address is ‘44’. [Short press] the button 

to select higher numbers, for example press once to 

change the address to 45, press twice for address 46 and 

so forth. [Long press] to save the chosen address. After 

address 99 the number returns back to 1. 

• The controller returns to the default state (– ●).

4.11 Economiser Option (Controls by Others)

The Economiser package that is factory fitted consists of 

two opposed blade dampers, one for the fresh air and the 

other for the return air and complete with individual damper 

motors controllable from a 0 – 10V dc signal. The package 

also includes a fresh air weathercowl supplied as a kitset 

that must first be assembled, then fitted to the unitt – 

usually before the unit is lifted into place.
The damper control will be factory wired such that the return 

air damper will close proportionally as the fresh air damper 

opens proportionally and vice versa. The fresh air damper’s 

adjustable stop can be set such that it does not close 

100%; many installations may require a minimum fresh air 

introduction of 10 – 15% and the stop may be set on site to 

facilitate this. Set the economiser Fresh Air Damper motor 

‘stop’ to the equivalent negative static pressure as with 

F/A damper closed. This is to ensure the air flow volume 

remains constant and does not dramatically increase when 

introducing fresh air. Failure to set the correct ‘stop’ position 

could result in rain/moisture entrainment in the incoming 

fresh air resulting in water deposited inside the unit.
As previously mentioned, a 0 – 10V dc control signal is 

required to drive the dampers open and closed. This could 

be from a BMS or a temperature/humidity controller. 

LCD Display

Push button

Summary of Contents for Econex OPA 250RLTFP

Page 1: ...well ventilated space If the refrigerant gas comes into contact with fire a poisonous gas may occur Be aware that R32 does not contain an odour If indoors the appliance shall be stored in a room away...

Page 2: ...eparate drain tray beneath the unit could be used to drain condensate to a suitable drainage point Condensate drains should be U trapped outside the unit The trap should have a vertical height of at l...

Page 3: ...llows DIP switch 2 ON Equipment type Heat Pump DIP switch 3 OFF Equipment stages One DIP switch 4 ON Reverse cycle valve on Heating SAT 3 Refer SAT 3 Installation Set up Guide page 3 4 4 Communication...

Page 4: ...emperzone biz model search UC8 or com website 4 10 Setting the UC8 Modbus device address To view or change the Modbus device address of a UC8 follow these steps Power up the unit but leave the compres...

Page 5: ...er 2 Start compressor in Cooling mode 3 Check the outdoor fan motor runs smoothly Note The outdoor fan does not necessarily start rotating immediately after the compressor is started The fans may run...

Page 6: ...signals and transfers the signals to the outputs after enforcing safety timers and other protection functions If the compressor is held off or held on by a safety timer then the display shows message...

Page 7: ...door coil This usually means reversing the cycle for a few minutes during which time there is no heating and in fact a little cooling can occur 8 4 In a new building why does it take some days before...

Page 8: ...t 6K Compressor discharge line pressure kPa dLP Discharge line pressure 2447 kPa Condensing temperature C Ct Condensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temp...

Page 9: ...indication that the compressor is being starved of refrigerant gas Common reasons for this could be a lack of refrigerant under charged or loss of charge or a problem with the expansion device for exa...

Page 10: ...ked out the compressor is not allowed to start Lock out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician T...

Page 11: ...3 4 1 1 INPUT kW 2 5 1 5 0 5 2 0 1 0 3 0 3 5 Amps 500 1000 1500 2000 2500 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 0 NOMINAL INPUT kW 3 0 2 0 1 0 2 5 1 5...

Page 12: ...st IMPORTANT Digital compressors must be operating at 100 for at least 10 minutes when taking these readings System 1 Cool Cycle Low Pressure SLP kPa Outdoor Ambient temperature C Evap temperature Et...

Reviews: