Table 1, Information available on the UC8 display.
Item
Unit Abbreviation Examples
Compressor suction line pressure
kPa
SLP
Suction line pressure 1034 kPa
Evaporating temperature
°C
Et
Evaporating temperature 12°C
Compressor suction line
temperature
°C
SLt
Suction line temperature 18°C
Compressor suction side superheat K
SSH
Suction side superheat 6K
Compressor discharge line pressure kPa
dLP
Discharge line pressure 2447 kPa
Condensing temperature
°C
Ct
Condensing temperature 42 °C
Compressor discharge line
temperature
°C
dLt
Discharge line temperature 70°C
Compressor discharge side
superheat
K
dSH
Discharge side superheat 28K
De-‐ice sensor temperature
(located on fins of the outdoor coil)
°C
ICEt
De-‐ice sensor temperature 39°C
Capacity
%
CAP
Capacity 100%
Expansion valve 1 opening
%
EE1
Expansion valve 1 75% open
Expansion valve 2 opening
%
EE2
Expansion valve 2 75% open
10