Production Specification and Performance
True Online 6-20k UPSUserManual
133
3. Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
C-40
C
<95%
<1000m
0
C-70
C
NOTICE
:
If the UPS is installed or used in a place where the altitude is above than
1000m
,
the output power must be derated in use, please refer to the following:
Altitude (M)
1000
1500
2000
2500
3000
3500
4000
4500
5000
DeratingPower 100% 95%
91%
86%
82%
78%
74%
70%
67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Crest ratio
1%
0.9 lag
0.1%
of
normal
THD<1%
Full
load
(Linear
Load)
110% load: transfers to
Bypass mode after 1hour
130% load: transfers to
Bypass
mode
after
1
minute
150% load :transfers to
Bypass
mode
after
0.5minute and shutdown
the output after 1 minute
3:1
maximum