1.2
Parameter Description
(*Parameters that are not applicable are not shown)
Register
Address
Parameter
Notation
Parameter Description
Range
Default
Value
0
SP1
Set Point 1
(Used for Output 1)
Low: SP1L
High: SP1H
77.0°F
8
INPT
(See Pg. 11)
Input sensor selection
0
J_tC
: J type Thermocouple
1
K_tC
: K type Thermocouple
2
T_tC
: T type Thermocouple
3
E_tC
: E type Thermocouple
4
B_tC
: B type Thermocouple
5
R_tC
: R type Thermocouple
6
S_tC
: S type Thermocouple
7
N_tC
: N type Thermocouple
8
L_tC
: L type Thermocouple
9
U_tC
: U type Thermocouple
10
P_tC
: P type Thermocouple
11
C_tC
: C type Thermocouple
12
D_tC
: D type Thermocouple
13
Pt.dN
: PT100 Ω DIN curve
14
Pt.JS
: PT100 Ω JIS curve
15
4-20
: 4-20mA linear current input
16
0-20
: 0-20mA linear current input
17
0-5V
: 0-5VDC linear voltage input
18
1-5V
: 1-5VDC linear voltage input
19
0-10
: 0-10VDC linear voltage
input
0, 1 or 13
(Depends on
Model Ordered)
9
UNIT
Input unit selection
0
oC
:°C unit
1
oF
:°F unit
2
Pu
:Process unit
1
10
DP
Decimal point selection
0
No.dP
: No decimal point
1
1-dP
: 1 decimal digit
2
2-dP
: 2 decimal digit
3
3-dP
: 3 decimal digit
0
13
SP1L
Low limit of set point 1
(Span Value)
Low: -19999
High :SP1H
0.0° F
14
SP1H
High limit of set point 1
(Span Value)
Low: SP1L
High: 45536
1000.0°F
15
FILT
Filter damping time constant of
PV Sensor
(See Pg. 14)
0
0
: 0 second time constant
1
0.2
: 0.2 second time constant
2
0.5
: 0.5 second time constant
3
1
: 1 second time constant
4
2
: 2 second time constant
5
5
: 5 second time constant
6
10
: 10 second time constant
7
20
: 20 second time constant
8
30
: 30 second time constant
9
60
: 60 second time constant
2