Page 9 of 18
(*Parameters that are not applicable are not shown)
Register
Address
Parameter
Notation
Parameter Description
Range
Default
Value
16
DISP
Secondary display selection
0
None
: No Display
1
MV1
: Display MV1
2
MV2
: Display MV2
3
tIMR: Display Dwell Time
4
PRoF:
display Profile Status
0
17
PB
Proportional band value
(See Pg. 17)
Low: 0.0
High: 500.0°C (900.0°F)
10.0° C
(18.0° F)
18
TI
Integral time value
(See Pg. 17)
Low: 0
High: 3600 sec
100
19
TD
Derivative time value
(See Pg. 17)
Low: 0.0
High: 360.0 sec
25
20
OUT1
Output 1 function
0
REVR
: Reverse (heating) control
action
1
dIRt
: Direct (cooling) control
action
0
21
O1TY
FACTORY
SET, DO
NOT
CHANGE
Output 1 signal type
0
RELY
: Relay output
1
SSrd
: Solid state relay drive
output
2
4-20
: 4-20mA linear current
3
0-20
: 0-20mA linear current
4
0-5V
: 0-5VDC linear voltage
5
1-5V
: 1-5VDC linear voltage
6
0-10
: 0-10VDC linear voltage
1
22
O1FT
Output 1 failure transfer mode
(See Pg. 15)
Select BPLS (Bumpless transfer), or
0.0 ~ 100.0 % to continue output 1
control function if the sensor fails, or
select OFF (0) or ON (1) for ON-OFF
control
0
23
O1HY
Output 1 ON-OFF control
hysteresis. PB=0
Low: 0.1°C (0.2°F)
High: 50.0°C (90.0°F)
0.1° C
(0.2 °F)
24
CYC1
Output 1 cycle time
Low: 0.1
High: 90.0 sec.
1.0
26
RAMP
Ramp function selection
(See Pg. 13)
0
NoNE
: No Ramp Function
1
MINR
: Use
⁰
/minute as Ramp Rate
2
HRR
: Use
⁰
/hour as Ramp Rate
0