28
7-4 Data Conversion
The word data are regarded as unsigned (positive) data in the Modbus message. However, the actual value of the parameter may be
a negative value with decimal point. The high/low scale values for each parameter are used for the purpose of such conversion.
Let
M = Value of Modbus message
A = Actual value of the parameter
SL = Scale low value of the parameter
SH = Scale high value of the parameter
M = 65535
×
(A – SL)
SH – SL
)
(
A = SH – SL
×
(M + SL)
65535
(
)
*1 The error code is shown in the first column of Table A.1 page 30.
*2 Definition for the value of MODE register:
H’000X = Normal mode
H’010X = Calibration mode
H’020X = Auto-tuning mode
H’030X = Manual control mode
H’040X = Failure mode
*3 The PROG Code is defined in the following table
Model No. TEC-9100 TEC-8100 TEC-4100 TEC-7100 TEC-220 TEC-920
PROG Code 6.XX 11.XX 12.XX 13.XX 33.XX 34.XX
*4 The scale high/low values are defined in the following table for SP1, INLO, INHI, SP1L, SP1H, SHIF, PV, SV, RELO and REHI:
Conditions Non-linear Linear input Linear input Linear input Linear input
input DP = 0 DP = 1 DP = 2 DP = 3
Scale low -1999.9 -19999 -1999.9 -199.99 -19.999
Scale High 4553.6 45536 4553.6 455.36 45.536
*5 The scale high/low values are defined in the following table for PB, O1HY, RR, O2HY, and ALHY:
Conditions Non-linear Linear input Linear input Linear input Linear input
input DP = 0 DP = 1 DP = 2 DP = 3
Scale low 0.0 0 0.0 0.00 0.000
Scale High 6553.5 65535 6553.5 655.35 65.535
*6 The scale high/low values are defined in the following table for SP3:
Conditions ALFN=1 Non-linear Linear input Linear input Linear input Linear input
(TIMR) input DP = 0 DP = 1 DP = 2 DP = 3
Scale low -1999.9 -1999.9 -19999 -1999.9 -199.99 -19.999
Scale High 4553.6 4553.6 45536 4553.6 455.36 45.536
*7 The scale high/low values are defined in the following table for SP2:
For TEC-220 and TEC-920
Conditions OUT2=1 Non-linear Linear input Linear input Linear input Linear input
(TIMR) input DP = 0 DP = 1 DP = 2 DP = 3
Scale low -1999.9 -1999.9 -19999 -1999.9 -199.99 -19.999
Scale High 4553.6 4553.6 45536 4553.6 455.36 45.536
For TEC-9100, TEC-8100, TEC-7100 and TEC-4100:
Conditions Non-linear Linear input Linear input Linear input Linear input
input DP = 0 DP = 1 DP = 2 DP = 3
Scale low -1999.9 -19999 -1999.9 -199.99 -19.999
Scale High 4553.6 45536 4553.6 455.36 45.536
(xx denotes the software version)
H’0X00 = Alarm status is off
H’0x01 = Alarm status is on
The alarm status is shown in MV2 instead of
MODE for models TEC-220 and TEC-920.