24
Output 2 functions:
Dwell timer
Deviation high/low alarm
Deviation band high/low alarm
PV high/low alarm
PID cooling control
Alarm modes:
Normal, latching, hold, latching/hold.
Dwell timer:
0.1–4553.6 minutes
Data Communication
Interface:
RS-232 (1 unit), RS-485 (up to 247 units)
Protocol:
Modbus protocol RTU mode
Address:
1–247
Baud rate:
0.3 - 38.4Kbits/sec
Data bits:
7 or 8 bits
Parity bit:
None, even or odd
Stop bit:
1 or 2 bits
Communication buffer:
160 bytes
Analog Retransmission
Output Signal:
4-20 mA, 0-20 mA, 0-5V, 1-5V, 0-10V
Resolution:
15 bits
Accuracy:
±0.05% of span ±0.0025%/°C
Load Resistance:
0-500 ohms (for current output)
10K ohms minimum (for voltage output)
Output Regulation:
0.01% for full load change)
User Interface
Single 4-digit LED display
Keypad:
3 keys for TEC-220, 4 keys for TEC-920
Programming port:
For automatic setup, calibration, and
testing
Communication port:
Connection to PC for supervisory
control
Control Mode
Output 1:
Reverse (heating) or direct (cooling) action
Output 2:
PID cooling control, cooling P band 50~300% of
PB, dead band -36.0-36.0% of PB
ON-OFF:
0.1-90.0 (°F) hysteresis control (P band=0)
P or PD:
0–100.0% offset adjustment
PID:
Fuzzy logic modified
Proportional band 0.1-900.0°F
Integral time 0–1000 seconds
Derivative time 0–360.0 seconds
Cycle time:
0.1–90.0 seconds
Manual control:
Heat (MV1) and cool (MV2)
Auto-tuning:
Cold start and warm start
Failure mode:
Auto-transfer to manual mode while sensor
break or A-D converter damage
Ramping control:
0–900.0°F/minute or
0–900.0°F/hour ramp rate
Digital Filter
Function:
First order
Time constant:
0, 0.2, 0.5, 1, 2, 5, 10, 20, 30, 60 seconds
programmable
Environmental and Physical
Operating temperature:
14°F (-10°C) to 122°F (50°C)
Storage temperature:
-40°F (-40°C) to 140°F (60°C)
Humidity:
0 to 90% RH (non-condensing)
Insulation resistance:
20Mohms min. (at 500VDC)
Dielectric strength:
2000VAC, 50/60 Hz for 1 minute
Vibration resistance:
10–55 Hz, 10 m/s≈ for 2 hours
Shock resistance:
200m/s ≈ (20g)
Moldings:
Flame retardant polycarbonate
Dimensions:
TEC-220 — 1-3/64" (26.5 mm) H
×
2" (50 mm) W
×
4-3/8" (110.5 mm) D
Depth behind panel: 3-7/8" (98 mm)
TEC-920 — 1-7/8" (48 mm) H
×
1-7/8" (48 mm) W
×
3-3/4" (94 mm) D
Depth behind panel: 3-3/8" (86 mm)
Weight:
TEC-220—.26 lbs. (120 grams)
TEC-920—.31 lbs. (140 grams)
Approval Standards
Safety:
UL61010C-1
CSA C22.2 No. 24-93
EN61010-1 (IEC1010-1)
Protective class:
IP65 front panel for TEC-220
IP30 front panel for TEC-920, all indoor use
IP20 for terminals and housing with protective cover.
All indoor use.
EMC:
EN61326
Specifications,
continued…
Summary of Contents for tec-220
Page 2: ...NOTES...
Page 4: ...NOTES...
Page 8: ...4 1 5 Menu Overview...
Page 9: ...5 1 6 Parameter Descriptions...
Page 10: ...6 1 6 Parameter Descriptions continued...
Page 22: ...18 NOTES...
Page 34: ...30 Table A 1 Error Codes and Corrective Actions A 1 Error Codes...