Tempco tec-220 Instruction Manual Download Page 16

12

Heat only ON-OFF control:

Select REVR for OUT1. Set PB

(Proportional Band) to 0. O1HY is used to adjust dead band for

ON-OFF  control.  The  output  1  hysteresis  (O1HY)  is  enabled

when PB=0. The heat only on-off control function is shown in the

following diagram:

The ON-OFF control may introduce excessive process oscillation

even if hysteresis is minimized. If ON-OFF control is set (i.e.,

PB=0), TI, TD, CYC1, OFST, CYC2, CPB, and DB will be hid-

den  and  have  no  function  in  the  system.  The  auto-tuning  and

bumpless transfer function will be disabled as well.

Heat only P (or PD) control:

Select H.TPC or H.L I N for OUT1

and set TI1 and TI2 to 0, OFST is used to adjust the control offset

(manual reset). O1HY is hidden if PB is not equal to 0. 

OFST  function:

OFST  is  measured  in  %  with  a  range  of  0–

100.0%. 

In a steady state (i.e. process has stabilized at a temperature), if

the process value is lower than the set point by a constant value

(we’ll say 5°C) while the PB setting is set for 20°C, we can say

the temperature is lower than the setpoint by 25% of the PB set-

ting.  This  can  be  corrected  by  increasing  the  OFST  setting  to

25%.  After  adjusting  the  OFST  value,  the  process  value  will

eventually coincide with set point. 

Note that using the P control (TI set to 0), disables auto-tuning.

Refer to Section 3-12 “manual tuning” for the adjustment of P

and PD. Manual reset (adjust OFST) is sometimes not practical

since the load may change from time to time and OFST may need

to be adjusted repeatedly. PID control can avoid this situation.

Heat only PID control:

If REVR is selected for OUT1, PB and

TI should not be zero. Perform auto-tuning for the new process,

or set PB, TI, and TD with historical values. See section 3-11 for

auto-tuning operation. If the control result is still unsatisfactory,

then use manual tuning to improve control. See section 3-12 for

manual  tuning. The  unit  contains  an  advanced  PID  and  Fuzzy

algorithm to create a small overshoot and very quick response to

the process if it is properly tuned.

Control Outputs,

continued…

Cool  only  control: 

ON-OFF  control,  P  (PD)  control,  and  PID

control can be used for cool control. Set OUT1 to DIRT (direct

action). The other functions for cool only ON-OFF control, cool

only P (PD) control, and cool only PID control are the same as for

heat only control except that the output variable (and action) for

cool control is inverse to heat control.

NOTE:

ON-OFF control may result in excessive overshoot and

undershoot problems in the process. P (or PD) control will result

in a deviation of process value from the set point. It is recom-

mended to use PID control for heat-cool control to produce a sta-

ble and zero offset process value.

Other setup required:

O1TY, CYC1, O2TY, CYC2, O1FT and

O2FT are set in accordance with the types of OUT1 and OUT2

installed. CYC1 and CYC2 are selected according to the output 1

type (O1TY) and output 2 type (O2TY). Generally, select 0.5~2

seconds for CYC1 if SSRD or SSR is used for O1TY; 10~20 sec-

onds if relay is used for O1TY and CYC1 is ignored if linear out-

put is used. Similar conditions are applied for CYC2 selection.

You  can  use  the  auto-tuning  program  for  the  new  process  or

directly set the appropriate values for PB, TI, and TD according

to historical records for duplicate systems. If the control behavior

is still inadequate, then use manual tuning to improve the control.

See section 3-12 for manual tuning.

CPB (Cooling Proportional Band) Programming:

The cooling

proportional  band  is  measured  by  %  of  PB  with  a  range  of

50-300.  Initially  set  100%  for  CPB  and  examine  the  cooling

effect. If the cooling action should be enhanced, then decrease

CPB, if the cooling action is too strong, then increase CPB. The

value of CPB is related to PB and its value remains unchanged

throughout the auto-tuning procedures.

Adjustment of CPB is related to the cooling medium used. If air

is used as the cooling medium, initially set CPB to 100%, then

adjust as necessary. If oil is used as the cooling medium, initially

set CPB to 125%, then adjust as necessary. If water is used as the

cooling medium, initially set CPB to 250%, then adjust as necessary.

DB (Heating-Cooling Dead Band) programming:

The adjust-

ment of DB is dependent on the system requirements. If a more

positive value of DB (greater dead band) is used, an unwanted

cooling action can be avoided but an excessive overshoot over the

set point will occur. If a more negative value of DB (greater over-

lap) is used, an excessive overshoot over the set point can be min-

imized, but an unwanted cooling action will occur. It is adjustable

in the range -36.0% to 36.0% of PB. A negative DB value shows

an overlap area over which both outputs are active. A positive DB

value shows a dead band area over which neither output is active.

Output 2 ON-OFF control (alarm function):

Output 2 can also

be  configured  with  an  alarm  function.  There  are  six  kinds  of

alarm  functions  that  can  be  selected  for  output  2.  These  are:

DE.HI

(deviation  high  alarm), 

DE.LO

(deviation  low  alarm),

DB.HI

(deviation  band  out  of  band  alarm), 

DB.LO

(deviation

band  in  band  alarm), 

PV.HI

(process  high  alarm),  and 

PV.LO

(process  low  alarm).  Refer  to  figure  3.3  and  figure  3.4  for

descriptions of the deviation alarm and the process alarm.

Summary of Contents for tec-220

Page 1: ...re Controller Agency Approvals Manual TEC 220 920 Revision 9 2016 TEMPCO Electric Heater Corporation 607 N Central Avenue Wood Dale IL 60191 1452 USA Tel 630 350 2252 Toll Free 800 323 6859 Fax 630 35...

Page 2: ...NOTES...

Page 3: ...er 6 Specifications 23 Chapter 7 Modbus Communications 7 1 Functions Supported 25 7 2 Exception Responses 26 7 3 Parameter Table 26 7 4 Data Conversion 28 7 5 Communication Examples 29 Appendix A 1 Er...

Page 4: ...NOTES...

Page 5: ...ent or voltage control output The ASIC technology provides improved operating performance low cost enhanced reliability and higher density Fast sampling rate The sampling rate of the input A to D conv...

Page 6: ...to connect the programming port to a PC for automatic configuration The programming port is used for off line automatic setup and testing proce dures only Don t attempt to make any connection to thes...

Page 7: ...5 Restart the dwell timer when the dwell timer has timed out 6 Enter the manual control menu when in failure mode ENTER KEY Press for 5 seconds or longer Press for 5 seconds to 1 Enter setup menu The...

Page 8: ...4 1 5 Menu Overview...

Page 9: ...5 1 6 Parameter Descriptions...

Page 10: ...6 1 6 Parameter Descriptions continued...

Page 11: ...t model number and options on the label Switch off the power while checking Care must be taken to ensure that the maximum voltage rating specified on the label is not exceeded It is recommended that t...

Page 12: ...el can provide an average temperature readout and produce better results in most air heated processes Proper sensor type is also a very important factor in obtaining precise measurements The sensor mu...

Page 13: ...9 Control Output Wiring continued Load 120V 240V Mains Supply SSR 30mA 5V Pulsed Voltage Internal Circuit 5V 0V 33 33 _ _ 5 6 10 9 TEC 220 TEC 920 Figure 2 10 Output 1 Pulsed Voltage to Drive SSR _...

Page 14: ...10 If you use a conventional 9 pin RS 232 cable instead of TEC99014 the cable must be modified according to the following circuit diagram 2 9 Data Communication 2 8 Alarm Wiring...

Page 15: ...or Process Value If 4 20mA is selected for INPT SL specifies the input signal low i e 4mA SH specifies the input signal high i e 20mA S specifies the current input signal value and the conversion curv...

Page 16: ...t in a deviation of process value from the set point It is recom mended to use PID control for heat cool control to produce a sta ble and zero offset process value Other setup required O1TY CYC1 O2TY...

Page 17: ...er than SV SP2 or lower than SV SP2 a deviation band high alarm DB HI occurs When the process value is within the trigger levels a deviation band low alarm DB LO occurs There are four types of alarm m...

Page 18: ...SV is set to 200 C initially and changed to 100 C 30 minutes after power up The starting temperature is 30 C After power up the process runs like the curve shown in Figure 3 5 Note When the ramp func...

Page 19: ...ller is designed to use unfiltered signal for con trol even if the filter is applied A lagged filtered signal if used for control may produce an unstable process 3 10 Failure Transfer The controller w...

Page 20: ...is taking place Auto tuning mode is disabled as soon as either failure mode or manual control mode is entered Procedures Auto tuning can be applied either as the process is warming up cold start or wh...

Page 21: ...a 1km dis tance while RS 232 is not recommended for a distance of over 60 feet 20 meters Using a PC for data communication is the most economical method The signal is transmitted and received through...

Page 22: ...18 NOTES...

Page 23: ...C UNIT C DP 1_DP OUT1 REVR O1TY RELY CYC1 18 0 O1FT BPLS OUT2 TIMR O2FT ON Auto tuning is performed at 150 C for a new oven 4 2 Cool Only Control A TEC 920 is used to control a refrigerator at tempera...

Page 24: ...ec O1FT BPLS OUT2 COOL O2TY 4 20 O2FT BPLS Set SV at 120 0 C CPB at 125 and DB at 4 0 Apply auto tuning at 120 C for a new system to get optimal PID values See section 3 11 Adjustment of CPB is relate...

Page 25: ...r 2 seconds and the display will show and the unit will enter the calibration mode Perform step 2 to calibrate zero of A to D converter and step 3 to calibrate gain of A to D converter Step 2 Short th...

Page 26: ...calibrator source is set at 0 00 C with internal compen sation mode Perform step as 1 stated above then press the scroll key until the display shows Press the scroll key for at least 5 seconds The dis...

Page 27: ...Below 1mA for 4 20mA input Below 0 25V for 1 5V input unavailable for other inputs Sensor break responding time Within 4 seconds for TC RTD and mV inputs 0 1 second for 4 20mA and 1 5V inputs Chapter...

Page 28: ...ID Fuzzy logic modified Proportional band 0 1 900 0 F Integral time 0 1000 seconds Derivative time 0 360 0 seconds Cycle time 0 1 90 0 seconds Manual control Heat MV1 and cool MV2 Auto tuning Cold sta...

Page 29: ...egisters Query from master Response from slave Slave address 0 255 Function code 16 Starting address of register Hi 0 Starting address of register Lo 0 79 128 131 No of words Hi 0 No of words Lo 1 79...

Page 30: ...SP3 Set Point 3 6 6 R W 3 LOCK Lock code 0 65535 R W 4 INPT Input sensor selection 0 65535 R W 5 UNIT Measuring unit 0 65535 R W 6 DP Decimal point position 0 65535 R W 7 INLO Low scale value for lin...

Page 31: ...W 55 RTDH RTD calibration high coefficient 1999 9 4553 6 R W 56 CJLO Cold junction calibration low coefficient 199 99 455 36 R W 57 CJHI Cold junction calibration high coefficient 1999 9 4553 6 R W 5...

Page 32: ...4553 6 45536 4553 6 455 36 45 536 5 The scale high low values are defined in the following table for PB O1HY RR O2HY and ALHY Conditions Non linear Linear input Linear input Linear input Linear input...

Page 33: ...F 00 00 4E 1F 00 01 00 B4 00 64 OUT2 2 RELO 0 0 O2TY 0 O2FT 0 O2HY 0 1 CYC2 18 0 CPB 100 4E 1F 00 02 52 07 00 00 00 01 00 00 00 01 DB 0 ALFN 2 REHI 100 0 ALMD 0 ALHY 0 1 ALFT 0 COMM 1 00 01 00 02 00 0...

Page 34: ...30 Table A 1 Error Codes and Corrective Actions A 1 Error Codes...

Page 35: ...notice In addition Tempco reserves the right to make changes without notification to the Purchaser to materials or processing that do not affect compliance with any applicable specification TEC Temper...

Page 36: ...Experience the Advantages of our Diverse and Innovative Products Copyright 2012 TEHC All Rights Reserved 12P200E16 Electric Heating Elements Thermocouples and RTD Assemblies SCR Power Controls Solid S...

Reviews: