MENU FUNZIONI 

COD  DESCRIZIONE 

ACC 

UdM 

DEF 

RANGE 

F.01 

Indirizzo IP 

Usr

 

 

192.168.1.1

 

IP1.IP2.IP3.IP4 

IP1 0...255 
IP2 0...255 
IP3 0...255 
IP4 0...255 

F.02 

Subnet mask 

Usr

 

 

0.0.0.0 

SUB1.SUB2.SUB3.SUB4 

SUB1 0...255  
SUB2 0...255  
SUB3 0...255  
SUB4 0...255 

F.03 

Porta IP 

Usr

 

 

1001 

0…9999 

F.04 

Client/server 

Usr

 

 

Server 

Client/server 

F.05 

Indirizzo IP remoto 

Usr

 

 

0.0.0.0 

IP1.IP2.IP3.IP4 

IP1 0...255 
IP2 0...255 
IP3 0...255 
IP4 0...255 

F.06 

Porta IP remota 

Usr

 

 

1001 

0…9999 

F.07 

Indirizzo IP gatway 

Usr

 

 

0.0.0.0 

GW1.GW2.GW3.GW4 

GW1 0...255 
GW2 0...255 
GW3 0...255 
GW4 0...255 

F.01...F.03

 – Coordinate TCP-IP per applicazioni con interfaccia Ethernet. 

F.04 

– Attivazione della connessione TCP-IP. 

Server 

= Attende connessione da un 

client remoto.

 Client = 

Stabilisce connessione verso server remoto 

F.05...F.07 

– Coordinate per la connessione al server remote quando F.04 è 

impostato su client. 

   

FUNCTION MENU 

COD  DESCRIPTION 

ACC 

UoM 

DEF 

RANGE 

F.01 

Indirizzo IP 

Usr

 

 

192. 168. 

1. 

1

 

IP1.IP2.IP3.IP4 

IP1 0...255 
IP2 0...255 
IP3 0...255 
IP4 0...255 

F.02 

Subnet mask 

Usr

 

 

0.0.0.0 

SUB1.SUB2.SUB3.SUB4 

SUB1 0...255  
SUB2 0...255  
SUB3 0...255  
SUB4 0...255 

F.03 

Porta IP 

Usr

 

 

1001 

0…9999 

F.04 

Client/server 

Usr

 

 

Server 

Client/server 

F.05 

Indirizzo IP remoto 

Usr

 

 

0.0.0.0 

IP1.IP2.IP3.IP4 

IP1 0...255 
IP2 0...255 
IP3 0...255 
IP4 0...255 

F.06 

Porta IP remota 

Usr

 

 

1001 

0…9999 

F.07 

Indirizzo IP gatway 

Usr

 

 

0.0.0.0 

GW1.GW2.GW3.GW4 

GW1 
GW2 
GW3 
GW4 

F.01…F.03 

– TCP-IP coordinates for Ethernet interface application.

 

F.04 

– Enabling TCP-IP connection. 

Server

 = Awaits connections from a remote 

client. 

Client

 = Estabilishes a connection to the remote server  

F.05…F.07 

– Coordinates for the connection to the remote server when F.04 is set 

to client. 

 

   

 

Menu comandi 

 

Il menu comandi permette di eseguire operazioni saltuarie quali 
azzeramenti di misure, contatori, allarmi, ecc. 

 

Se è stata immessa la password per accesso avanzato, allora tramite il 

menu comandi è anche possibile effettuare delle operazioni automatiche 

utili ai fini della configurazione dello strumento. 

 

Con centralina in modalità MAN, premere 

MODE

 per 5s. 

 

Premere ▲fino a selezionare 

CMD

 

Premere 

AUT

 per accedere al 

Menu comandi

 

Selezionare comando desiderato con 

MAN

 o 

AUT

 

Premere e tenere premuto ▲ per tre secondi se si vuole eseguire 
comando. PCRL8/14 mostra 

OK?

 con countdown.  

 

Se si tiene premuto 

 fino alla fine del countdown il comando viene 

eseguito, mentre se si rilascia prima il tasto il comando viene annullato. 

 

Per uscire dal menu comandi premere e tenere premuto 

AUT

 

 

 

 

COD  COMANDO 

LIVELLO  

ACCESSO  

DESCRIZIONE 

C01 

AZZ. MANUTENZIONE  

Avanzato 

Azzera intervallo di manutenzione. 

C02 

AZZ. MANOIVRE STEP 

Avanzato

 

Azzera il contatore di manovre step. 

C03 

AZZ. STEP TRIMMING 

Avanzato

 

Ripristina le potenze originali 
nell’aggiustamento step. 

C04 

AZZ. ORE STEP 

Avanzato

 

Azzera i contaore di funzionamento 
step. 

C05 

AZZ. VALORI MASSIMI 

Avanzato

 

Azzera i picchi massimi registrati delle 
misure. 

C06 

AZZ. TPF 

SETTIMANALE 

Avanzato

 

Azzera memoria TPF settimanale. 

C07 

SETUP a DEFAULT 

Avanzato

 

Ripristina i parametri al default di 
fabbrica. 

C08 

SALVA COPIA SETUP 

Avanzato

 

Salva una copia di backup delle 
impostazioni di setup dell’ utente . 

C09 

RIPRIS. COPIA SETUP 

Avanzato

 

Ripristina i parametri al valore della 
copia utente. 

 

   

Commands menu 

 

The commands menu allows executing some occasional operations 
like reading peaks resetting, counters clearing, alarms reset, etc. 

 

If the Advanced level password has been entered, then the commands 

menu allows executing the automatic operations useful for the device 

configuration. 

 

The following table lists the functions available in the commands menu, 
divided by the access level required. 

 

With controller in MAN mode, press the 

MODE

 button for 5 seconds.

 

 

Press ▲ to select 

CMD

.

 

 

Press 

AUT

 to access the 

Commands menu

.

 

 

Select the desired command with 

MAN

 or 

AUT

.

 

 

Press and hold for three seconds ▲ if you want to execute the 
selected command. PCRL8/14 shows 

OK?

 with a countdown.

 

 

If you press and hold  ▲ until the end of the countdown the command 
is executed, while if you release the key before the end, the command 

is canceled.

 

 

To quit command menu press and hold 

AUT

 button.

 

 

COD  COMMAND 

ACCESS 

LEVEL 

DESCRIPTION 

C01 

RESET MAINTENANCE 

Advanced  Reset maintenance service 

interval. 

C02 

RESET STEP COUNT 

Advanced

 

Reset step operation counters. 
 

C03 

RESET STEP 

TRIMMING 

Advanced

 

Reload originally programmed 
power into step trimming. 

C04 

RESET STEP HOURS 

Advanced

 

Reset step operation hour meters. 

C05 

RESET MAX VALUES 

Advanced

 

Reset maximum peak values. 

C06 

RESET WEEKLY TPF 

Advanced

 

Resets weekly total power factor 
history. 

C07 

SETUP TO DEFAULT 

Advanced

 

Resets setup programming to 
factory default. 

C08 

SETUP BACKUP 

Advanced

 

Makes a backup copy of user  
setup parameters settings. 

C09 

SETUP RESTORE 

Advanced

 

Reloads setup parameters with the 
backup of user settings. 

 

 

   

 

Summary of Contents for PCRL8/14

Page 1: ...ENG User Manual PFC Controller J Automatic PFC systems all Series PC PCRL8 14 Automatic PFC systems...

Page 2: ...s forbidden also partial without authorization The information contained in this manual is accurate but we accept no responsibility for any errors or errors omissions The manufacturer also reserves th...

Page 3: ...10 3 3 Statement 11 3 4 Safety Standards 12 3 5 Warranty 12 4 GENERAL DESCRIPTION OF THE PANEL 13 4 1 Environmental conditions 13 4 2 Electromagnetic environment 13 4 3 Technical data of the equipment...

Page 4: ...p 4 43 ANNEX Wiring Diagram Declarations of conformity Test certificate Warranty certificate...

Page 5: ...This document assumes that in the places where the product has been destined the current rules of safety and hygiene of the work are observed The instructions drawings and documentation contained in...

Page 6: ...by the manufacturer 1 3 Storage of the instruction manual The Instruction Manual must be kept with care and must accompany the product in all the steps of ownership Storage should be taken care of wit...

Page 7: ...of the machine in a manner different from that indicated in the instructions for use but which may derive from easily predictable human behavior RESIDUAL RISK Risks that remain despite the integrated...

Page 8: ...enance repair or transport completely unplug the unit and disconnect all plugs or connectors 2 1 Transportation and storage Telegroup S r l assumes no responsibility if the equipment is moved without...

Page 9: ...el must be installed according to the instructions in this manual Failure to recognize the risks related to electricity could prove fatal Please keep this instruction manual for future reference User...

Page 10: ...at dangerous voltages repairs must only be performed by qualified service personnel Disconnect the mains power supply before carrying out any service or repair Check that there is no dangerous voltage...

Page 11: ...the Member States relating to electrical equipment intended to be used within certain voltage limits Directive 2014 30 UE Concerning the approximation of the laws of the Member States relating to elec...

Page 12: ...arts interlocked to the main switch by means of a door locking handle closing by locks Blind flange for cable passage located on the upper lower part of the equipment Fixing of the equipment to the fl...

Page 13: ...ff or it will function abnormally Since the panels are all tested and tested on site any operating anomalies will be due to incorrect connection and in particular to the incorrect positioning of the c...

Page 14: ...0 A A T A will have to be chosen whose current ranges from 2500 A 8 of 2500 200 A and 180A 110 of 180 A 200 A It is a good rule to install a C T with a double primary current that is actually circulat...

Page 15: ...the automatic power factor correction switch the voltage must be 0 The positioning of the C T It is essential for the correct functioning of the appliance The relative diagram is shown in the figure...

Page 16: ...ich the cables coming from the C T must be connected The output of the C T adder must be connected to the automatic rephasing Set the C T the ways to set this parameter are described in Appendix B as...

Page 17: ...cognize the current direction of the C T In case of cogeneration plants it is necessary to disable this function see advanced menu chapter and to ensure the correct connection of the C T The secondary...

Page 18: ...PC tablet o smartphone 7 Impostazione parametri da pannello frontale 7 Impostazione rapida TA 8 Tabella dei parametri 9 Allarmi 13 Descrizione degli allarmi 13 Propriet di default allarmi 14 Menu com...

Page 19: ...d settings Alarm messages in 6 languages English Italian French Spanish Portuguese German Expansion bus with 2 slot for EXP series expansion modules o RS232 RS485 USB Ethernet communications interface...

Page 20: ...orrere le altre misure come di consueto Mentre il display alfanumerico posizionato su MAN possibile attivare disattivare manualmente gli step Per selezionare uno step utilizzare i tasti o Lo step sele...

Page 21: ...a lista delle misure possibile impostare il setpoint del cosfi agendo sullo stesso valore impostato con P 19 Di seguito viene riportata una tabella con le misure visualizzate Misura Icona Descrizione...

Page 22: ...razioni il display visualizzer LOC per indicare la condizione di blocco Keypad lock A function to exclude all modification to operating parameters can be enabled measurement viewing is still provided...

Page 23: ...a i seguenti vantaggi o Consente di effettuare la configurazione e la manutenzione della PCRL8 14 senza la necessit di accedere al retro dell apparecchio e quindi di aprire il quadro elettrico o E gal...

Page 24: ...shows PAS password entry request Set the numeric password using and then press AUT to move to next digit If the password is correct the unit will show OK U or OK A depending on the entered password i...

Page 25: ...ser does not press any key for more than 2 minutes the system leaves the setup automatically and goes back to normal viewing without saving the changes done on parameters like EXIT N B a backup copy o...

Page 26: ...ilable The parameter code can be used however as a reference Note the parameters shown in the table with a shaded background are essential to the operation of the system thus they represent the minimu...

Page 27: ...rred to the total of the three capacitors for three phase applications P 07 Rated plate capacitor which is delivered in specified power P 06 If the capacitors are used to a voltage different lower tha...

Page 28: ...manovra ed visualizzata sulla pagina statistiche vita step Quando questa funzione abilitata viene inserita una pausa di 15sec fra l inserzione di uno step ed il successivo necessaria a misurare la var...

Page 29: ...p che ha il conteggio pi alto oltre il quale viene generato l allarme di manutenzione A12 Questo parametro va usato in alternativa a P 45 Se sia P45 che P 54 sono impostati ad un valore diverso da OFF...

Page 30: ...n codice identificativo e la descrizione dell allarme nella lingua selezionata Se vengono premuti dei tasti di navigazione delle pagine la scritta scorrevole con le indicazioni di allarme scompare mom...

Page 31: ...P 43 A11 Current THD too high The THD of the plant current is higher than the threshold set with P 44 A12 Maintenance requested The maintenance interval set with either P 45 or P 54 has elapsed To res...

Page 32: ...comando PCRL8 14 mostra OK con countdown Se si tiene premuto fino alla fine del countdown il comando viene eseguito mentre se si rilascia prima il tasto il comando viene annullato Per uscire dal menu...

Page 33: ...3 times consecutively and fast the dongle button At this point the display of the PCRL8 14 shows the first of the 6 possible commands D1 D6 Press to select the desired command Press AUT to execute th...

Page 34: ...co condensatori 1 misura calcolata su L2 L3 Capacitor overload current measure 1 reading calculated on L2 L3 Impostazione parametri P 03 L1 P 05 L2 L3 P 24 3PH Parameter setting P 03 L1 P 05 L2 L3 P 2...

Page 35: ...Inserzione con misure e rifasamento su MT Configuration with MV measurement and correction Misura tensione 3 misure di tensione concatenata L1 L2 L2 L3 L3 L1 su media tensione Voltage measure 3 ph to...

Page 36: ...d fuses F1A fast Ingressi amperometrici Current inputs Corrente nominale Ie 1A o 5A Rated current Ie 1A or 5A Campo di misura Per scala 5A 0 025 6A Per scala 1A 0 025 1 2A Measuring range For 5A scale...

Page 37: ...ance 15g IEC EN 60068 2 27 Resistenza alle vibrazioni 0 7g IEC EN 60068 2 6 Vibration resistance 0 7g IEC EN 60068 2 6 Connessioni Connections Tipo di morsetti Estraibili Terminal type Plug in removab...

Page 38: ...Via L Da Vinci 100 50028 Tavarnelle V P Loc Sambuca FI ITA P IVA 0438 634 0485 Ph 39 0558071267 Fax 39 0558071338 telegroup telegroup it www telegroup it...

Page 39: ...Via L Da Vinci 100 50028 Tavarnelle V P Loc Sambuca FI ITA P IVA 0438 634 0485 Ph 39 0558071267 Fax 39 0558071338 telegroup telegroup it www telegroup it...

Page 40: ...Via L Da Vinci 100 50028 Tavarnelle V P Loc Sambuca FI ITA P IVA 0438 634 0485 Ph 39 0558071267 Fax 39 0558071338 telegroup telegroup it www telegroup it...

Page 41: ...438 634 0485 Ph 39 0558071267 Fax 39 0558071338 telegroup telegroup it www telegroup it TELEGROUP S r l Via L Da Vinci 100 50028 Tavarnelle Val di Pesa Loc Sambuca FIRENZE ITALY Phone 39 055 80 71 267...

Page 42: ...waste from electrical and electronic equipment must take place at appropriate local collection centers that comply with local laws TELEGROUP capacitors are made without PCBs in compliance with decree...

Page 43: ...gh content of currents and harmonic voltages and with a correct short circuit coordination between the network Electrical and the Equipment For the choice of the most suitable type of equipment for yo...

Page 44: ...then short circuiting and grounding all the capacitors CEI EN 60831 1 prf 22 standard Avoid disconnecting a battery and re insert it manually in a shorter time than 30 s necessary for the discharge of...

Page 45: ...twork harmonics the nominal values It is good practice to note on a MAINTENANCE CARD any actions taken with the DATE of execution and relative observations check the efficiency of the pre insertion re...

Page 46: ...ing the capacitors The capacitors must be replaced with others of the same SERIES whenever the following anomalies are found Loss of liquid Case throat raised Absorbed fundamental current of less than...

Page 47: ...never the main switch off of the power factor correction equipment In the event of a fire in the environment where the appliance is installed do not use water or any means that could compromise the i...