Event Setting (OSD)
Supplementary Guide
PAGE
4
S/C
Short Circuit
LoZ
Low Impedance
HiZ
High Impedance
Notes:
The table below shows the summary between the resistance network and the condition result. Note
that this table is used as a reference. There may be a 10% tolerance for the resistance value in the
below table.
Resistance (Ω)
Condition
0~400
401~2780
2781~29.5k
29.5k~Infinity
DEOL (Normal Close)
Tamper Short
Normal (Close)
Alarm (Open)
Tamper Open
DEOL (Normal Open)
Tamper Short
Alarm (Close)
Normal (Open)
Tamper Open
SEOL (Normal Close)
Tamper Short
Normal (Close)
Alarm (N/A)
Alarm (Open)
SEOL (Normal Open)
Alarm (Close)
Normal (Open)
Alarm (N/A)
Tamper Open
NC without tamper
Normal (Close) Alarm (N/A)
Alarm (N/A)
Alarm (Open)
NO without tamper
Alarm (Close)
Alarm (N/A)
Alarm (N/A)
Normal (Open)
Alarm (N/A): Alarm is not applicable.
3.4. Event Setting (OSD)
3.4.1. Alarm (OSD)
Alarm can be used to detect events, such as fire and illegal entering by someone.
Alarm Sensor Type
Alarm sensors have two types: normal close (NC) and normal open (NO). Normal Close means the
normal circuit status is close and an alarm event is triggered if the circuit is open. Normal Open
means the normal circuit status is open and an alarm event is triggered if the circuit is close.
Alarm Setup Procedure
1.
Press on
[MENU]
button, select
[SETUP]
[EVENT HANDLER]
[ALARM]
2.
Select an alarm.