T3PS Series Programming Manual
32
5 1
9 6
1 8
Steps
1.
Connect the RS232 serial cable or
RS485 serial cable to the Remote
IN port on the real panel.
Connect the other end of the cable
to the PC.
RS 485 / 232
1
2.
Press the Function key to enter the
Normal configuration settings.
Set the following UART settings:
F-70 = 1 or 2
Interface: 0= Disable UART,
1= RS232 or 2 = RS485
F-71 = 0 ~ 7
Set the baud rate:
0=1200, 1=2400, 2=4800, 3=9600,
4=19200, 5=38400, 6=57600,
7=115200
F-72 = 0 or 1
Data bits: 0=7 or 1=8
F-73 = 0 ~3
Parity: 0 = none, 1 = odd, 2 = even
F-74 = 0 or 1
Stop bits: 0 = 1, 1 = 2
F-75 = 0 or 1
TCP: 0 = SCPI, 1 = TDK (emulation
mode)
F-76 = 00~30
UART address for multi-unit remote
connection.
F-77 = 0~3
Multi-Drop control
0 = Disable, 1 = Master, 2 = Slave, 3
= Display Information
F-78 = 00~30
Multi-Drop status display
Displayed parameter: AA-S
AA: 00~30 (Address),
S: 0~1 (Off-line/On-line status).