11.3.1
Mute alarms and the unit
User menu -> Silence
Once this key is pressed, it is transformed into
Rearm
.
This function lets you temporarily mute system and panel alarms to check if a fire has
actually broken out and reset them if necessary.
Procedures
In the event of false alarm:
Reset the panel (see
11.3.2 Reset alarms and the unit
).
In the event of real alarm:
Press the
Siren Reset
key to turn sirens back on.
11.3.2
Reset alarms and the unit
User menu ->Reset
This function resets triggered alarms and the unit.
If alarms or faults are not restored before the reset, after it will still be shown on the display
from the central.
It’s possible to perform a reset Hardware through the appropriate button on the
master board.
11.3.3
Evacuation
User menu ->Evacuation
This feature will put the panel into evacuation mode, activating all the outputs/sirens properly
configured.
By activating the evacuation all the output modules programmed as “Activate evacuation”
(see
10.3 Modules
) will be activated, even if their zone is not active, and if the logic function
where they are linked to is not yet valid.