Dual 40/50/100A Configurable Breaker Panel

Power

 :: T009-5XXXXXXXXXXX

© Telect, Inc.,  All Rights Reserved, 118267-3 A0

1.509.926.6000  ::  telect.com

8

Installation Guide 

118267-2 A0

Page 7

ALERT

!

ALERT! The LINE side connection of the breaker has live Vdc. Do not allow contact of the connector (or tools

holding the connector) to grounded ironwork or panel chassis.

12. While holding breaker out from the front of the panel, grasp

LINE

connector of breaker with needle-nose pliers.

13. Hold the

LINE

connector with pliers and then pull breaker, wiggling it until breaker is free from connector. Continue

to hold the

LINE

connector with the pliers. Do not allow the connector to contact the panel chassis.

14. With your free hand, pick up new breaker and check orientation of new breaker.
15. Press spade connector of new breaker into the pliers-held

LINE

connector until fully seated.

Visually inspect the connection to be sure full contact is made between the

LINE

connector and the breaker spade

connector.

16. Place the

LOAD

conductor connector on the

LOAD

spade connector of the breaker.

Visually inspect the connection.

17. Gently place breaker back into panel. Push on front of breaker until tabs are cleared and breaker is secure in panel.
18. If input power was turned off, restore input power and turn on breakers one at a time.
19. When new breaker is turned on, check output terminal for correct polarity.

A

CCESSORIES

The following lists optional and replacement items for the panel. For compression lugs, please refer to

Wire Sizing, La-

bel Convention, & Lug Chart

(Telect Part No. 117995) included with your panel.

1. Breakers are sold for repair/replacement of field breakers and not for reconfiguring the panel.

NOTE

For service and warranty, see our telect.com website, or eMAIL inquires to [email protected], or phone us at

800-551-4567 (domestic only) or 509-926-8915.

Item

Description

Part Number

Alarm Card

With

INPUT BREAKER

LEDs

400207

Circuit Breaker

1

1A long delay

115268

3A long delay

115266

5A long delay

115267

10A long delay

115269

15A long delay

115265

20A long delay

115270

Blank

113882

ETSI Mounting Brackets

Black

090-0041-0030

White

090-0041-0031

Front Cover

Clear

090-0001-0001

Designation Label

1-7, A & B

115353

ALERT! The LINE side connection of the breaker has live VDC. Do not allow contact of the connector (or tools 

holding the connector) to grounded ironwork or panel chassis.

12. 

While holding breaker out from the front of the panel, grasp 

LINE

 connector of breaker with needle-nose pliers.

13. Hold the 

LINE

 connector with pliers and then pull breaker, wiggling it until breaker is free from connector. Continue to 

hold the 

LINE

 connector with the pliers. Do not allow the connector to contact the panel chassis.

14. 

With your free hand, pick up new breaker and check orientation of new breaker.

15. 

Press spade connector of new breaker into the pliers-held 

LINE

 connector until fully seated. 

Visually inspect the connection to be sure full contact is made between the 

LINE

 connector and the breaker 

 

spade connector.

16. 

Place the 

LOAD

 conductor connector on the 

LOAD

 spade connector of the breaker. Visually inspect the connection.

17. 

Gently place breaker back into panel. Push on front of breaker until tabs are cleared and breaker is secure in panel.

18. 

If input power was turned off, restore input power and turn on breakers one at a time.

19. 

When new breaker is turned on, check output terminal for correct polarity.

Accessories 

The following lists optional and replacement items for the panel. For compression lugs, please refer to 

Wire Sizing, Label 

Convention & Lug Chart

 (Telect Part No. 117995) included with your panel.

Item 

Description 

Part Number 

Alarm card 

With

 INPUT BREAKER

 LEDs

400207

Circuit breaker

1

1A long delay

115268

3A long delay

115266

5A long delay

115267

10A long delay

115269

15A long delay

115265

20A long delay

115270

Blank

113882

ETSI Mounting Brackets

Black 

090-0041-0030

White

090-0041-0031

Front Cover

Clear

090-0001-0001

Designation Label

1-7, A & B

115353

1. Breakers are sold for repair/replacement of field breakers and not for reconfiguring the panel.

For service and warranty information see our telect.com website, email inquires to [email protected] or phone  

us at 509.926.6000.

Summary of Contents for T009-5 Series

Page 1: ...ompression inputs only White or black panels can be configured with any combination of 1A to 20A Carling M Series breakers oriented with the on symbol at either the bottom or top 50A thermal input bre...

Page 2: ...r dual hole lug Conductor size depends on input interruption device 20 in lb 2 25 N m max Input terminals Compressions Quantity Stud Lugs Cable Torque 4 2 BATT 2 RTN M5 with KEPS nut Use 8 mm 5 16 in...

Page 3: ...omer Service Department at 1 800 551 4567 domestic only or 1 509 926 6000 for further recourse NOTE Panel brackets provide either flush or extended EIA or WECO mounting in a 19 or 23 rack Panel is con...

Page 4: ...insi que pour l quipement ALERT ALERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter s Laboratories UL TUV et...

Page 5: ...tighten to 14 in lb 1 5 N m Compression Lug Inputs Screw Tight Vertical Horizontal Inputs Alarm Indicators 9 Make sure power is off open breaker dummy fuse or open fuse holder at power distribution u...

Page 6: ...l breaker out puts on each side must not exceed 40A for a panel with an optional thermal input breaker 50A for a panel having screw tight inputs connectors but without an optional thermal input breake...

Page 7: ...aced Then turn off input power to that side of panel 4 Place breaker to be replaced in the off position 5 Using a very small flat tipped screwdriver carefully pry out on bottom of breaker while applyi...

Page 8: ...nting Brackets Black 090 0041 0030 White 090 0041 0031 Front Cover Clear 090 0001 0001 Designation Label 1 7 A B 115353 ALERT The LINE side connection of the breaker has live VDC Do not allow contact...

Page 9: ...is closed and C to NO is open Input Power Failure POWER ON A or POWER ON B LED s will go off POWER FAIL relay de energizes so that C to NC opens and C to NO closes Input Breaker Opens input breakers...

Page 10: ...e Inputs Wire Binding A Side Inputs Compression Inputs With 50A Input Breakers Screw Tight Horizontal Inputs Without 50A Input Breakers Compression Inputs Without 50A Input Breakers 100A max side Scre...

Page 11: ...akers Installed with On at Top 3 White Enclosure Breakers installed with On at Top Panel Color Breaker Orientation 0 Screw Tight Horizontal Inputs with 50A Thermal Input Breakers Inputs Type of Connec...

Page 12: ...r its patent rights or the patent rights of others This document and the products described herein are subject to change without notice INPUT BREAKER B BATT 24V 48V 100A MAX 24V RTN BATT RTN GND CHS C...

Reviews: