Dual 40/50/100A Configurable Breaker Panel
Power
:: T009-5XXXXXXXXXXX
© Telect, Inc., All Rights Reserved, 118267-3 A0
1.509.926.6000 :: telect.com
8
Installation Guide
118267-2 A0
Page 7
ALERT
!
ALERT! The LINE side connection of the breaker has live Vdc. Do not allow contact of the connector (or tools
holding the connector) to grounded ironwork or panel chassis.
12. While holding breaker out from the front of the panel, grasp
LINE
connector of breaker with needle-nose pliers.
13. Hold the
LINE
connector with pliers and then pull breaker, wiggling it until breaker is free from connector. Continue
to hold the
LINE
connector with the pliers. Do not allow the connector to contact the panel chassis.
14. With your free hand, pick up new breaker and check orientation of new breaker.
15. Press spade connector of new breaker into the pliers-held
LINE
connector until fully seated.
Visually inspect the connection to be sure full contact is made between the
LINE
connector and the breaker spade
connector.
16. Place the
LOAD
conductor connector on the
LOAD
spade connector of the breaker.
Visually inspect the connection.
17. Gently place breaker back into panel. Push on front of breaker until tabs are cleared and breaker is secure in panel.
18. If input power was turned off, restore input power and turn on breakers one at a time.
19. When new breaker is turned on, check output terminal for correct polarity.
A
CCESSORIES
The following lists optional and replacement items for the panel. For compression lugs, please refer to
Wire Sizing, La-
bel Convention, & Lug Chart
(Telect Part No. 117995) included with your panel.
1. Breakers are sold for repair/replacement of field breakers and not for reconfiguring the panel.
NOTE
For service and warranty, see our telect.com website, or eMAIL inquires to [email protected], or phone us at
800-551-4567 (domestic only) or 509-926-8915.
Item
Description
Part Number
Alarm Card
With
INPUT BREAKER
LEDs
400207
Circuit Breaker
1
1A long delay
115268
3A long delay
115266
5A long delay
115267
10A long delay
115269
15A long delay
115265
20A long delay
115270
Blank
113882
ETSI Mounting Brackets
Black
090-0041-0030
White
090-0041-0031
Front Cover
Clear
090-0001-0001
Designation Label
1-7, A & B
115353
ALERT! The LINE side connection of the breaker has live VDC. Do not allow contact of the connector (or tools
holding the connector) to grounded ironwork or panel chassis.
12.
While holding breaker out from the front of the panel, grasp
LINE
connector of breaker with needle-nose pliers.
13. Hold the
LINE
connector with pliers and then pull breaker, wiggling it until breaker is free from connector. Continue to
hold the
LINE
connector with the pliers. Do not allow the connector to contact the panel chassis.
14.
With your free hand, pick up new breaker and check orientation of new breaker.
15.
Press spade connector of new breaker into the pliers-held
LINE
connector until fully seated.
Visually inspect the connection to be sure full contact is made between the
LINE
connector and the breaker
spade connector.
16.
Place the
LOAD
conductor connector on the
LOAD
spade connector of the breaker. Visually inspect the connection.
17.
Gently place breaker back into panel. Push on front of breaker until tabs are cleared and breaker is secure in panel.
18.
If input power was turned off, restore input power and turn on breakers one at a time.
19.
When new breaker is turned on, check output terminal for correct polarity.
Accessories
The following lists optional and replacement items for the panel. For compression lugs, please refer to
Wire Sizing, Label
Convention & Lug Chart
(Telect Part No. 117995) included with your panel.
Item
Description
Part Number
Alarm card
With
INPUT BREAKER
LEDs
400207
Circuit breaker
1
1A long delay
115268
3A long delay
115266
5A long delay
115267
10A long delay
115269
15A long delay
115265
20A long delay
115270
Blank
113882
ETSI Mounting Brackets
Black
090-0041-0030
White
090-0041-0031
Front Cover
Clear
090-0001-0001
Designation Label
1-7, A & B
115353
1. Breakers are sold for repair/replacement of field breakers and not for reconfiguring the panel.
For service and warranty information see our telect.com website, email inquires to [email protected] or phone
us at 509.926.6000.