background image

Dual 40/50/100A Configurable Breaker Panel

Power

 :: T009-5XXXXXXXXXXX

© Telect, Inc.,  All Rights Reserved, 118267-3 A0

1.509.926.6000  ::  telect.com

6

Installation Guide 

13. 

Repeat Steps 11 and 12 for Feed B and observe that 

POWER ON B

 LED turns on (green).

14. 

Press and hold ALARM RESET on front of panel for 5 seconds to verify that all LEDs are in working order.

15. 

With one or all circuit breakers off, test fuse alarm relay contacts at 

FUSE ALARM

 terminals on rear  

of panel:

• 

Expect an open circuit (∞Ω) between Terminals 

C

 and 

NC

.

• 

Expect continuity (0Ω) between Terminals 

C

 and 

NO

.

16. 

With both Feeds A and B on, recheck POWER FAIL terminals:

• 

Expect continuity (0Ω) between Terminals 

C

 and 

NC

.

• 

Expect an open circuit (∞Ω) between Terminals 

C

 and 

NO

.

17. 

Recheck that all circuit breakers on panel are off.

18. 

For output wiring, do either of the following:

•  If using lugs

, strip off 

 in. (~1 cm) of insulation from one end of copper output wires and then crimp on ring 

or forked, single-hole lugs, as required by NEC. (Screw terminals will accommodate lugs for up to 10 AWG.)

•  If using bare wire

, strip off 5/8 in. (~1.5 cm) of insulation. (Stranded wires should be tinned.)

Remember: Output wires must be rated at or above the amperage rating of the output circuit breaker. For 

example, use no smaller than #12 AWG output wiring for 20A output fuses. Do not exceed 16A continuous 

load for a 20A breaker.

118267-2 A0

Page 5

13. Repeat Steps 11 and 12 for Feed B and observe that

POWER ON B

LED turns on (green).

14. Press and hold ALARM RESET on front of panel for 5 seconds to verify that

all

LEDs are in working order.

15. With one or all circuit breakers off, test fuse alarm relay contacts at

FUSE ALARM

terminals on rear of panel:

Expect an open circuit (

∞Ω)

between Terminals

C

and

NC

.

Expect continuity (0

)

 

between Terminals

C

and

NO

.

16. With both Feeds A and B on, recheck

POWER FAIL

terminals:

Expect continuity (0

) between Terminals

C

and

NC

.

Expect an open circuit (

∞Ω) 

between Terminals

C

and

NO

.

17. Recheck that all of circuit breakers on panel are off.
18. For output wiring, do either of the following:

If using lugs

, strip off

3

/8

in. (~1 cm) of insulation from one end of copper output wires and then crimp on ring or

forked, single-hole lugs, as required by NEC. (Screw terminals will accommodate lugs for up to 10 AWG.)

If using bare wire

, strip off

5

/8

in. (~1.5 cm) of insulation. (Stranded wires should be tinned.)

Remember: Output wires must be rated at or above the amperage rating of the output circuit breaker. For example,

use no smaller than #12 AWG output wiring for 20A output fuses. Do not exceed 16A continuous load for a 20A

breaker.

ALERT

!

ALERT! Local electrical and operating company guidelines recommend that the individual load not exceed

80% of circuit breaker capacity (for example, 10A breaker x .80 = 8A max. load).

Total load for all breaker out-

puts on each side

must not exceed —

• 40A for a panel with an optional thermal input breaker,

• 50A for a panel having screw-tight inputs connectors, but

without

an optional thermal input breaker, or

• 100A for a panel having compression input connectors, but

without

an optional thermal input breaker.

19. Clean output terminals and lugs with a nonabrasive, nonmetallic pad.
20. If installed, remove covers over output and alarm connectors.
21. Telect recommends that you lightly coat anti-oxidant on lugs and output

BATTERY

and

RETURN

terminals before

connecting lugs/wires to outputs. (NEC specifies only one lug and load for each output terminal.) Tighten screws to

9 in.-lb (1.01 N•m).

22. Connect other end of output wires to

load

.

23. Use designation labels (supplied) to record outputs, as specified by

operating company standard installation procedures.

24. Make sure inputs at

loads are disabled

by removing all power cards or

all input fuses at load equipment.
Always follow recommended operating company guidelines when dis-

abling load equipment.

25.

One by one

, turn on circuit breakers on this panel and check voltage

and polarity

at input of loads

.

26. With all circuit breakers on

, the

BREAKER ALARM

LED must go off.

Test fuse alarm relay contacts at

FUSE ALARM

terminals on rear of

panel:

Expect continuity (0

) between Terminals

C

and

NC

.

Expect an open circuit (

∞Ω) 

between Terminals

C

and

NO

.

Designation Label

ALERT! Local electrical and operating company guidelines recommend that the individual load not exceed 80% 

of circuit breaker capacity (for example, 10A breaker x .80 = 8A max. load). Total load for all breaker outputs

on each side must not exceed —

• 40A for a panel with an optional thermal input breaker

• 50A for a panel having screw-tight inputs connectors, but without an optional thermal input breaker

• 100A for a panel having compression input connectors, but without an optional thermal input breaker

19. 

Clean output terminals and lugs with a nonabrasive, nonmetallic pad.

20. 

If installed, remove covers over output and alarm connectors.

21. 

Telect recommends that you lightly coat antioxidant on lugs and output 

BATTERY

 and 

RETURN

 terminals before 

connecting lugs/wires to outputs. (NEC specifies only one lug and load for each output terminal.) Tighten screws to 9 

in.-lb (1.01 N•m).

22. 

Connect other end of output wires to load.

23. 

Use designation labels (supplied) to record outputs, as specified by 

 

operating company standard installation procedures.

24. 

Make sure inputs at loads are disabled by removing all power cards or 

 

all input fuses at load equipment.

Always follow recommended operating company guidelines when 

 

disabling load equipment.

25. 

One by one, turn on circuit breakers on this panel and check voltage 

 

and polarity at input of loads.

26. 

With all circuit breakers on

, the 

BREAKER ALARM

 LED must go off.  

Test fuse alarm relay contacts at 

FUSE ALARM

 terminals on rear of panel:

• 

Expect continuity (0Ω) between Terminals 

C

 and 

NC

.

• 

Expect an open circuit (∞Ω) between Terminals 

C

 and 

NO

.

Designation Label

Summary of Contents for T009-5 Series

Page 1: ...ompression inputs only White or black panels can be configured with any combination of 1A to 20A Carling M Series breakers oriented with the on symbol at either the bottom or top 50A thermal input bre...

Page 2: ...r dual hole lug Conductor size depends on input interruption device 20 in lb 2 25 N m max Input terminals Compressions Quantity Stud Lugs Cable Torque 4 2 BATT 2 RTN M5 with KEPS nut Use 8 mm 5 16 in...

Page 3: ...omer Service Department at 1 800 551 4567 domestic only or 1 509 926 6000 for further recourse NOTE Panel brackets provide either flush or extended EIA or WECO mounting in a 19 or 23 rack Panel is con...

Page 4: ...insi que pour l quipement ALERT ALERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter s Laboratories UL TUV et...

Page 5: ...tighten to 14 in lb 1 5 N m Compression Lug Inputs Screw Tight Vertical Horizontal Inputs Alarm Indicators 9 Make sure power is off open breaker dummy fuse or open fuse holder at power distribution u...

Page 6: ...l breaker out puts on each side must not exceed 40A for a panel with an optional thermal input breaker 50A for a panel having screw tight inputs connectors but without an optional thermal input breake...

Page 7: ...aced Then turn off input power to that side of panel 4 Place breaker to be replaced in the off position 5 Using a very small flat tipped screwdriver carefully pry out on bottom of breaker while applyi...

Page 8: ...nting Brackets Black 090 0041 0030 White 090 0041 0031 Front Cover Clear 090 0001 0001 Designation Label 1 7 A B 115353 ALERT The LINE side connection of the breaker has live VDC Do not allow contact...

Page 9: ...is closed and C to NO is open Input Power Failure POWER ON A or POWER ON B LED s will go off POWER FAIL relay de energizes so that C to NC opens and C to NO closes Input Breaker Opens input breakers...

Page 10: ...e Inputs Wire Binding A Side Inputs Compression Inputs With 50A Input Breakers Screw Tight Horizontal Inputs Without 50A Input Breakers Compression Inputs Without 50A Input Breakers 100A max side Scre...

Page 11: ...akers Installed with On at Top 3 White Enclosure Breakers installed with On at Top Panel Color Breaker Orientation 0 Screw Tight Horizontal Inputs with 50A Thermal Input Breakers Inputs Type of Connec...

Page 12: ...r its patent rights or the patent rights of others This document and the products described herein are subject to change without notice INPUT BREAKER B BATT 24V 48V 100A MAX 24V RTN BATT RTN GND CHS C...

Reviews: