© Telect, Inc., All Rights Reserved, 132152-12 A0
1.509.926.6000 :: telect.com
7
100A/60A Universal Voltage GMT Fuse Panels
With Enhanced Power/Fuse & Bay Alarms
Power
:: HPGMTXX & GMTXX
1. If necessary, remove three screws and reposition/
re-align brackets on sides of distribution the panel,
as shown in the illustration on the right.
2. Locate an unused rack position, normally at the top
of the rack. Mount the panel to the rack using four,
#12-24 thread-cutting screws and lock washers
provided, as shown in Figure 4.
3. Tighten screws to 35 in.-lb (4.29 N•m).
4. Remove the transparent terminal cover, shown in
Figure 5.
Flush
Extended by 2 in.
Extended by 4 in.
Bracket Oriented for 19-in. Rack
Bracket Oriented for 23-in. Rack
Figure 3 - Bracket Orientation
Figure 4 - Rack Mounting
WARNING! Failure to properly ground this
equipment can create hazardous conditions for
installation personnel and for the equipment.
WARNING
!