100A/60A Universal Voltage GMT Fuse Panels
With Enhanced Power/Fuse & Bay Alarms
Power
:: HPGMTXX & GMTXX
Figure 6 - Input Connections on a 100A Panel
ALERT
!
ALERT! Only service personnel may replace fuses. The installer must verify that a readily accessible
protection device is incorporated in the building wiring feeding the fuse panel: 125A (max.) protection
device for a 100A panel; 75A (max.) for a 60A panel.
For input wiring on a 60A panel —
a. Strip off about 3⁄4 in. (10 mm) of insulation at end of input conductors (min. #6 AWG for a 60A feed).
b. If desired (highly recommended), lightly coat anti-oxidant on the bare conductor.
c. Insert the bare conductor into the barrel connector as indicated in the illustration, and then tighten the
screw to 16 in.-lb (1.8 N•m), max.
DO NOT REMOVE CAPS*
* Screws located below caps are used for
installing internal wiring at the factory.
Figure 7 - Input Connections on a 60A Panel