3
100A/60A Universal Voltage GMT Fuse Panels
With Enhanced Power/Fuse & Bay Alarms
Power
:: HPGMTXX & GMTXX
1.2 Specifications
Inputs:
Voltage & Range
±20 Vdc to ±60 Vdc @ 20°C ±22 Vdc to ±58 Vdc @
55°C
Max. Input Load Rating
60A/100A depends on model
Max. Power Dissipation at Full Load
• < 50W per side (max.) for panels rated for 60A
• < 75W per side (max.) for panels rated at 100A
% of Full Load Power Dissipation
less then 1% for all models
Max. Input Interruption Device
• 75A for 60A panels • 125A for 100A panels
Input Terminals
100A Panels
Dual 1/4-20 studs on 5/8 in. centers. Torque KEPS nut
(using 7/16 in. or 12 mm socket) to ~50 in.-lb (~5.6 N•m),
max.
60A Panels
Barrel-style screw-down terminals for #14 AWG to #6
AWG bare conductor. Torque to 16 in.-lb (1.8 N•m), max.
Outputs:
Max. GMT Output Fuse (ea.)
• 20A for all but GMT20
• 15A for Model GMT20
Max. GMT Output Load (ea.)
• 14A continuous for all but Model GMT20
• 10.5A for Model GMT20
Max. Total GMT Output Per Side
• 100A for 100A panels
• 60A for 60A panels
Output Terminals
(Wire-Binding Screw Posts)
• #6-32 for all panels except Model GMT20
• #3-48 for Model GMT20
GMT Output Wire Size Range
• #22 to #14 AWG, depending on output fuse (.6A to 20A) for all but GMT20
• #30 to #16 AWG, depending on output fuse (.18A to 15A) for Model GMT20
Interrupt Rating
450A
Short-Circuit Withstand Current
450A
Alarms:
Alarm Relay Contacts
Dry Form-C contacts (1A @ 30 Vdc, 0.3A @ 100 Vdc,
0.5A @ 125 Vac)
Max. Alarm Power Rating
@24V: 72 mA (1.73W)
@48V: 147 mA (7.06W)
Alarm Wire Size
#22 to #18 AWG
Alarm Terminals
Wirewrap