© Telect, Inc., All Rights Reserved, 132152-12 A0
1.509.926.6000 :: telect.com
6
100A/60A Universal Voltage GMT Fuse Panels
With Enhanced Power/Fuse & Bay Alarms
Power
:: HPGMTXX & GMTXX
1.5 Installation
ALERT
!
ALERT! Install this product within a restricted access location where access is through the use of a tool,
lock and key, or other means of security, and is controlled by the authority responsible for the location.
This product must be installed and maintained only by qualified technicians.
Verify all connections meet requirements specified in local electric codes or operating company
guidelines before supplying power. Unit shall be protected by a listed circuit breaker or branch-rated fuse
rated maximum 75A (for 60A-rated feeds) and maximum 125A (for 100A-rated feeds).
All panels except Models GMT10FA and HPGMT20 can be mounted in 19-in. EIA racks. Telect also offers bracket
kits for WECO and ETSI racks. (See our website at telect.com.) GMT10FA and HPGMT20 only fit 23-in. racks.
All panels can be flush-mounted or extended by 2 in. or 4 in. beyond the rack flange.