Telect GMTXX Installation Manual Download Page 1

100A/60A Universal Voltage GMT Fuse Panels 
With Enhanced Power/Fuse & Bay Alarms

Power

  ::  HPGMTXX & GMTXX

© Telect, Inc.,  All Rights Reserved, 132152-12 A0
1.509.926.6000  ::  telect.com

Applies to : GMT10  ::  GMT10FA  ::  GMT20  ::  GMT20S  ::  HPGMT10-BLK  ::  HPGMT20  ::  HPGMT20RC  ::  HPGMT20S

Installation Guide

Summary of Contents for GMTXX

Page 1: ...Fuse Panels With Enhanced Power Fuse Bay Alarms Power HPGMTXX GMTXX Telect Inc All Rights Reserved 132152 12 A0 1 509 926 6000 telect com Applies to GMT10 GMT10FA GMT20 GMT20S HPGMT10 BLK HPGMT20 HPGMT20RC HPGMT20S Installation Guide ...

Page 2: ...Figure 1 GMT Fuse Panel 1 Figure 2 GMT Series Comparison Chart 2 Figure 3 Bracket Orientation 7 Figure 4 Rack Mounting 7 Figure 5 Ground Lug Connection 8 Figure 6 Input Connections on a 100A Panel 9 Figure 7 Input Connections on a 60A Panel 9 Figure 8 Status LEDs on Face of 10 Figure 9 Alarm Terminals on Rear of Panel 10 Figure 10 Output Connections 10 Figure 11 Designation Card 11 Figure 12 Alarm...

Page 3: ...Output screw post terminals accept either ring or forked lugs as well as bare wire Power fuse and bay alarms terminals along with external bay alarm trigger terminals are wirewrap pins GMT Series panels differ in load rating 60A or 100A capacity 10 15 or 20 GMTs per side single or dual feed and total front access GMT10FA panels vs panels with rear side terminals All panels are 1RU The GMT fuse hol...

Page 4: ...139903 and NEBS Level 3 certified and RoHS 5 6 compliant The HPGMT20RC is RoHS 6 6 compliant All specifications for the HPGMT20RC are the same as the HPGMT20 Features 60A Max Input x x x x 100A Max Iput x x x 20A Max Fuse Position x x x x x x 15A Max Fuse Position x Universal VDC x x x x x x x Dual Bus x x x x x Single Bus x x Fuse Positions per Feed 10 10 20 20 10 20 20 Rack Units 1 1 1 1 1 1 1 W...

Page 5: ...in lb 5 6 N m max 60A Panels Barrel style screw down terminals for 14 AWG to 6 AWG bare conductor Torque to 16 in lb 1 8 N m max Outputs Max GMT Output Fuse ea 20A for all but GMT20 15A for Model GMT20 Max GMT Output Load ea 14A continuous for all but Model GMT20 10 5A for Model GMT20 Max Total GMT Output Per Side 100A for 100A panels 60A for 60A panels Output Terminals Wire Binding Screw Posts 6 ...

Page 6: ...or all except TFA HPGMT20b 17 x 1 75 x 9 in 432x44x229mm Width x Height x Depth for GMT10FA HPGMT20c 21 x 1 75 x 9 in 533x44x229mm a Without mounting brackets b All 1RU panels and fit either a 19 in or 23 in rack c Models GMT10FA HPGMT20 only fit 23 in racks Fit Finish Material 16 gauge steel Color White powder coat for all but HPGMT10 BLK black Weights Approximate All Single Dual Panels with 10 G...

Page 7: ... consideration to the connection of the equipment to the supply circuit and the ef fect that overloading of the circuits might have on overcurrent protection and supply wiring Use appropriate consideration for equipment nameplate ratings when addressing this concern Reliable Earthing Maintain reliable earthing of rack mounted equipment Pay particular attention to supply connections other than dire...

Page 8: ...e installed and maintained only by qualified technicians Verify all connections meet requirements specified in local electric codes or operating company guidelines before supplying power Unit shall be protected by a listed circuit breaker or branch rated fuse rated maximum 75A for 60A rated feeds and maximum 125A for 100A rated feeds All panels except Models GMT10FA and HPGMT20 can be mounted in 1...

Page 9: ...osition normally at the top of the rack Mount the panel to the rack using four 12 24 thread cutting screws and lock washers provided as shown in Figure 4 3 Tighten screws to 35 in lb 4 29 N m 4 Remove the transparent terminal cover shown in Figure 5 Flush Extended by 2 in Extended by 4 in Bracket Oriented for 19 in Rack Bracket Oriented for 23 in Rack Figure 3 Bracket Orientation Figure 4 Rack Mou...

Page 10: ...breaker phoney fuse or open fuse holder at primary power distribution unit PDU before connecting this panel s input cables to that PDU 10 For input wiring wiring used as inputs to this distribution the panel do one of the following Refer to the following illustrations For input wiring on a 100A panel see page 9 for 60A input wiring instructions a Crimp dual hole compression lugs onto 8 to 1 0 AWG ...

Page 11: ...feeding the fuse panel 125A max protection device for a 100A panel 75A max for a 60A panel For input wiring on a 60A panel a Strip off about 3 4 in 10 mm of insulation at end of input conductors min 6 AWG for a 60A feed b If desired highly recommended lightly coat anti oxidant on the bare conductor c Insert the bare conductor into the barrel connector as indicated in the illustration and then tigh...

Page 12: ...erminals C and NO 14 Also test fuse alarm relay contacts at FUSE alarm terminals then Expect continuity 0Ω between Terminals C and NC Expect an open circuit 00Ω between Terminals C and NO 15 Repeat Steps 12 through 14 to power up Side B PWR A and PWR B LEDs must both be green 16 With PWR A and PWR B lit test power fail relay and contacts at PWR A and PWR B alarm terminals Expect continuity 0Ω betw...

Page 13: ...river or Phillips screwdriver for cross re cessed screw heads to no greater than 5 in lb 0 6 N m Connect other end of output wire to load 19 Record circuit assignments in accordance with operating company procedures and guidelines The manufacturer s designation card shown below is a 10 in 254 mm by 21 2 in 57 mm card that folds in half to fit a card holder located below the status LEDs 20 Make sur...

Page 14: ...all operable GMT fuse before proceeding If desired connect remote external audio visual panel alarm indicator wires solid wires 22 to 18 AWG to wirewrap PWR and FUSE alarm pins on rear of panel as shown below on the right 23 If desired connect remote audio visual bay alarms indicator wires to the MAJ major and MIN minor alarm pins Also install switch closure wires to the A activate and R reference...

Page 15: ... conductors with straight dual hole lugs for 1 4 in studs on 5 8 in centers Table 1 Input Lugs Source 1 0 AWG 2 AWG 4 AWG 6 AWG 8 AWG Telect 06117 02 06117 04 06117 01 06117 11 T B 54206 Die Code 29 54205 Die Code 24 542040416 Die Code 21 Panduit LCDN2 14A Q Die Code 33 LCD4 14A L Die Code 29 LCD6 14A L Die Code 24 LCD8 14A L Die Code 21 Burndy YA25L2NT14 Die Code12 YA4CL2TC14 Die Code 8 YA6CL2TC1...

Page 16: ...ter covers order part number 116915 for GMT fuses up to 15A Telect recommends using only UL recognized supplementary protectors GMT Fuse Part Numbers GMT Fuse Colored Designation Pin Part No 18A Yellow YEL 130781 102435 21 1 4A Violet VIO 100151 102435 2 1 2A Red RED 004001 102435 5 3 4A Brown BRN 004008 102435 7 1A Gray GRY 100991 102435 8 11 3A White WHT 004006 102435 9 11 2A White Yellow WHT YE...

Page 17: ...ve the alarm card remove the screws gently slide out status LED bezel and alarm card and then disconnect the header cables near the far end of the alarm card 1 7 Diagrams The diagrams that follow are representative of Telect s GMT Series of power panels ALARM PCB PWR A FUSE A C GND RTN BATT INPUT A PWR B GMT OUTPUT A BATT 5 1 3 4 2 FUSE B MINOR ALM MAJOR ALM MAJ MIN PWR A PWR B FUSE NC C NO R A NC...

Page 18: ...00 584 2 2 00 50 8 4 00 101 6 DO NOT REMOVE PLASTIC CAPS 1 2 3 4 5 6 7 8 9 10 20A GMT FUSE MAX 20A GMT FUSE MAX 11 12 13 14 15 16 17 18 19 20 0 29 7 5 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 MAJ MIN PWR A PWR B FUSE NC C NO R A BATT RTN BATT RTN GMT20S 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 48 24 V SINGLE INPUT BUS 60A INPUT 60A MAX Barrel Connector 3 48 Screw Posts 5 8 15 9...

Page 19: ...ncludes phoney fuses Actual fuses are sold separately Transparent Plastic Terminal Cover EIA Brackets WECO ETSI Bracket Kits are Available R E AR VIE W R OTATE D TOP VIE W FR ONT VIE W ALM ALM B B A A MINOR MAJOR FUSE PWR FUSE PWR 22 31 566 7 23 00 584 2 2 00 50 8 4 00 101 6 1 2 3 4 5 6 7 8 9 10 20A GMT FUSE MAX 20A GMT FUSE MAX 1 2 3 4 5 6 7 8 9 10 B INPUT 100A MAX 10 9 8 7 6 5 4 3 2 1 BATT RTN A...

Page 20: ... ONT VIE W 11 69 296 8 0 45 11 4 A B INPUT BUS 100A INPUT BUS 100A 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 20A GMT FUSE MAX 20A GMT FUSE MAX 1 2 3 4 5 6 7 8 9 10 11 12 13 14 5 1 2 3 4 16 17 18 15 19 20 HPGMT20 0 28 7 2 5 8 15 9 1 4 20 Studs With KEPS Nuts Flat Washers 6 32 Screw Posts 0 29 7 5 5 8 15 9 10 32 Studs With KEPS Nuts Flat Washers R E AR VIE W R OTATE D INPUT 100A MAX 20 19 18 17 16 15...

Page 21: ...OR MINOR FUSE PWR FUSE PWR DO NOT REMOVE PLASTIC CAPS A B INPUT BUS 60A 6 7 8 9 10 20A GMT FUSE MAX 5 1 2 3 4 6 7 8 9 10 20A GMT FUSE MAX 5 1 2 3 4 MAJ MIN PWR A PWR B FUSE NC C NO A R 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 BATT RTN 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 BATT RTN INPUT BUS 60A 23 00 584 2 1 72 43 7 22 31 566 7 1 25 31 7 21 00 533 4 2 00 50 8 4 00 101 6 11 23 285 2 9 00 228 6...

Page 22: ...lect Inc All Rights Reserved 132152 12 A0 1 509 926 6000 telect com 20 100A 60A Universal Voltage GMT Fuse Panels With Enhanced Power Fuse Bay Alarms Power HPGMTXX GMTXX This page intentionally left blank ...