1.3 Inspection
Inspect equipment after unpacking and compare it to the packing list.
Immediately report any shipping damage, defects, or missing parts to Telect at 1-800-551-4567.
Keep all documentation that comes with your shipment.
Telect is not liable for shipping damage. If the product is damaged, notify the carrier and call
Telect’s Customer Service Department at 1-800-551-4567 (domestic only) or 1-509-926-6000 for
further recourse.
NOTE:
For service or warranty information, please visit telect.com website, or email inquiries to
[email protected] and click on the “Support” tab, or phone us at 800-551-4567 (domestic only)
or 509-926-6000.
Alarm contact ratings, continuous
2A at 30 VDC
0.6A at 60 VDC
1A at 120 VAC
Alarm board power ratings
@20V: 100 mA (2 W)
@24V: 153 mA (3.672 W)
@27V: 166 mA (4.48 W)
@30V: 167 mA (5.01 W)
@42V: 173 mA (7.27 W)
@48V: 175 mA (8.4 W)
@56V: 179 mA (10.02W)
@60V: 181 mA (10.86 W)
Max. operating temperature at max.
load ratings
55°C (131°F)
Min. operating temperature at max. load ratings -10°C (14°F)
Ambient operating temp. at half-load
72°C (162°F)
Max. surface temperature of fuses at 26°C
(79°F) ambient
Front face: 59°C (138°F)
Top/Bottom face: 91°C (196°F)
Max. panel heat dissipation @ full load
80W per side for 8, 20A KLM fuses
26W per side for 8, 12A GMT fuses
Panel heat dissipation @ typical load
Less than 100W per side
Electrical