7
PRESSES Threshold (A)
1
0.5
2
1.0
3
1.5
4
2.0
5
2.5
6
3.0
7
3.5
8
4.0
9
4.5
The control unit uses a current threshold for motor stop. The thresholds may therefore be changed during configuration according to the selected mode (
DIP4-5
):
1. Turn the control unit OFF then ON again.
2. Within
10 seconds
from power ON, set
DIP6
to
ON
.
WITHIN 30 SECONDS:
3. Press
P1
as many times as the desired level, from
1
(minimum = 0.5 A) to
9
(maximum = 4.5 A).
4. Set
DIP6
to
OFF
to store the new value.
L4 will then flash as many times as the stored level.
If
P1
is not pressed within 30 seconds,the procedure is
automatically ended and the threshold remains unchanged.
ATTENTION:
at the end of the procedure, DIP6 must be set to OFF and remain in that position during standard
operation of the control unit.
SETTING OF THE CURRENT THRESHOLD DURING CONFIGURATION
DIP6=
ON
< 10 s
< 30 s
P1
...
/
DIP6=
OFF
...
L4 flashes
2.4
3. SELF-LEARNING OF LIMIT SWITCHES
(start from and intermediate point of the run)
MOTOR 1
first, then
MOTOR 2
Press
P1
and
P2
simultaneously
twice
in quick succession and
hold them the second time for
5 s
< 1 s
P2
+
P1
( 5 s)
P2
+
P1
complete
closing
complete
opening
complete
closing
complete
opening
...
...
...
...
=
default value, unless otherwise indicated
on the technical label of the product.
ON
1 2 3 4 5 6
DO NOT
change the DIP configuration. This change would be signalled by a new intermittent sound and the flashing of L3, and would require a new configuration procedure.
LEDs L1 and L2 flash during motor movements.